This is a Presolicitation Notice for a construction services requirement issued by the Department of Veterans Affairs, Network Contracting Office (NCO) 15. The VA seeks a contractor to install a continuous water monitoring system at the St. Louis VAMC Jefferson Barracks facility to comply with VHA Directive 1061 for Legionella prevention. The project involves installing monitoring equipment across five buildings (Buildings 3, 51, 52, 53, and 59) to continuously measure incoming cold water pressure and temperature, cold water distal points, hot water distal points, hot water source equipment supply and return temperatures, and midpoint temperatures at each riser. The contractor must also provide full training on the new water monitoring equipment and related instrumentation and control systems.
The solicitation is set aside exclusively for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) under 38 USC 8127(d). The estimated project cost ranges from $500,000 to $1,000,000, with a firm-fixed contract type and a performance period of 210 calendar days from Notice to Proceed. The NAICS code is 238220 (Plumbing, Heating and Air-Conditioning Contractors) with a small business size standard of $19.0 million. The solicitation package is scheduled for release on December 7, 2026, with proposals due on or about January 15, 2027. Award will be made to the highest technically rated offeror with a fair and reasonable price without discussions. Prospective contractors must be registered in SAM and the Veterans Small Business Certification database. An organized site visit will be scheduled, and all inquiries should be directed via email to Jennifer.Hill@va.gov, the Contracting Officer at the NCO address in Leavenworth, Kansas (zip code 66048).
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Presolicitation Notice Presolicitation Notice
| SUBJECT* |
| 657-27-111JB, Install Continuous Water Monitoring System, |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 66048 |
| SOLICITATION NUMBER* |
| 36C25527R0019 |
| RESPONSE DATE/TIME/ZONE |
| 12-07-2026 14:00 CENTRAL TIME, CHICAGO, USA |
| ARCHIVE |
| 15 DAYS AFTER THE RESPONSE DATE |
| SET-ASIDE |
| SDVOSBC |
| PRODUCT SERVICE CODE* |
| Z2DA |
| NAICS CODE* |
| 238220 |
| PLACE OF PERFORMANCE |
| St. Louis VAMC |
Jefferson Barracks
1 Jefferson Barracks Drive
St. Louis MO
| POSTAL CODE |
| 63125 |
| COUNTRY |
| USA |
CONTACT INFORMATION
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway
Leavenworth KS 66048
POINT OF CONTACT*
Contracting Officer Jennifer Hill Jennifer.Hill@va.gov 913-946-1198
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
Project # 657-27-111JB, Install Continuous Water Monitoring System
The Department of Veterans Affairs, Network Contracting Office (NCO) 15, has a requirement for Installing a Continuous Water Monitoring System, project number 657-27-111JB, located at the U.S Department of Veterans Affairs, Str. Louis VAMC Jefferson Barracks 1 Jefferson Barracks Drive St. Louis, MO 63125 The following narrative is intended to provide an overview of the scope of work for the proposed project.
Period of Performance 210 calendar days after Notice to Proceed (NTP) Scope of Work Contractor shall completely prepare site for building operations, including demolition and removal of existing structures, and furnish labor and materials and perform work for project 657-27-111JB.
Justification: This project is required to be in compliance with VHA Directive 1061 to provide Legionella Prevention measuring devices.
Building 3:
• 1 incoming cold water continuous monitoring with pressure and temperature
• 1 cold water distal – Furthest point from incoming cold water
• 1 hot water distal – Furthest point from incoming hot water
• 1 hot water source equipment supply temperature
• 1 hot water source equipment return temperature
• Monitoring cold and hot temperature at midpoints at each riser Building 51:
• 1 incoming cold water continuous monitoring with pressure and temperature
• 2 cold water distal -Furthest point from incoming cold water
• 1 hot water distal – Furthest point from incoming hot water
• 1 hot water source equipment supply temperature
• 1 hot water source equipment return temperature
• Monitoring cold and hot temperature at midpoints at each riser Building 52:
• 1 incoming cold water continuous monitoring with pressure and temperature
• 1 cold water distal – Furthest point from incoming cold water
• 1 hot water distal – Furthest point from incoming hot water
• 1 hot water source equipment supply temperature
• 1 hot water source equipment return temperature
• Monitoring cold and hot temperature at midpoints at each riser Building 53:
• 1 incoming cold water continuous monitoring with pressure and temperature
• 1 cold water distal – Furthest point from incoming cold water
• 1 hot water distal – Furthest point from incoming hot water
• 1 hot water source equipment supply temperature
• 1 hot water source equipment return temperature
• Monitoring cold and hot temperature at midpoints at each riser Building 59:
• 1 incoming cold water continuous monitoring with pressure and temperature
• 1 cold water distal – Furthest point from incoming cold water
• 1 hot water distal – Furthest point from incoming hot water
• 1 hot water source equipment supply temperature
• 1 hot water source equipment return temperature
• Monitoring cold and hot temperature at midpoints at each riser Provide full training of new water monitoring equipment and basic I&C training relating to this project.
Contractor work must fully comply with VHA Directive 1061 The estimated project cost range to complete this work is Between $500,000 and $1,000,000.
Pursuant to 38 USC 8127(d) and in accordance with Public Law 109-461, the Veterans Benefits, Health Care and Information Technology Act of 2006, this construction project will be solicited as a Total set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB).
The North American Industry Classification Code (NAICS) for this procurement is 238220 Plumbing, Heating and Air-Conditioning Contractors, with a small business size standard of $19.0 million.
Contract Type: Firm Fixed. The duration of the project is estimated to be 210 calendar days from Notice to Proceed. This completion period includes final inspection and cleanup of the premises.
Award will be made utilizing Highest technically rated with a fair and reasonable price approach in accordance with Federal Acquisition Regulation Part 15.
Proposal submission instructions will be included in the solicitation package.
The government plans to award without discussions.
The offeror is responsible to monitor and download any amendments from the Contract Opportunities (https:// sam.gov) website, which may be issued to this solicitation.
In accordance with FAR 52.204-7, Required SAM, and in accordance with Veterans Affairs Acquisition Regulation (VAAR) 802.101, prospective contractors must be registered in SAM and in the Veteran Small Business Certification (sba.gov) databases under the applicable NAICS.
Firms may obtain SAM information at http://www.sam.gov and Veteran Small Business Certification (sba.gov) information at https://veterans.certify.sba.gov The solicitation package with project specifications and drawings should be available for download on or about December 7, 2026 and the proposal due date will be on or about January 15, 2027. An organized site visit will be scheduled and specific date and time will be made available at time of solicitation issuance. Only one site visit will be scheduled and interested offerors are highly encouraged to attend. No hard copies of the solicitation or drawings will be provided; and telephone requests or questions will NOT be accepted.
Please email requests or questions to Jennifer.Hill@va.gov and ensure that the subject line reads "Install Continuous Water Monitoring System, Project Number 657-27-111JB; Solicitation Number: 36C25527R0019.
| *=Required Field |
| Presolicitation Notice |
Presolicitation Notice
File details come from the government source that posted it. Updated .