36C25527Q0047_1.docx

DOCX document 157 KB Posted

Attached to
J091--Aboveground Fuel Tank Inspection Services - Kansas City VAMC
Solicitation number
36C25527Q0047
Issued by

About this file

Summary

This is a Solicitation/Contract/Order for Commercial Products and Commercial Services (Standard Form 1449) for a five-year Indefinite Delivery, Indefinite Quantity (IDIQ) contract issued by the Department of Veterans Affairs Network Contracting Office (NCO) 15, based in Leavenworth, Kansas. The solicitation is set aside exclusively for Service-Disabled Veteran-Owned Small Business (SDVOSB) concerns. The contract covers annual inspection, maintenance, repair, certification, and fuel oil filtering services for sixteen aboveground storage tanks (ASTs) at the Kansas City VA Medical Center in Kansas City, Missouri. The solicitation was issued on November 16, 2026, with offers due by December 11, 2026, at 7:00 AM CST, and an award/effective date of January 19, 2027. A site visit is scheduled for November 30, 2026, at 9:00 AM CT, and questions are due by December 4, 2026, at 7:00 AM CST.

The contract period consists of five consecutive twelve-month ordering periods from January 19, 2027, through January 18, 2032, with annual services to be completed in February of each ordering period. Pricing is structured with seventeen contract line items (CLINs) per ordering period: one CLIN for comprehensive annual AST interior and exterior inspection with STI SP001 certification and tank integrity testing, and sixteen individual CLINs for fuel oil filtration, recirculation, treatment, and third-party laboratory analysis of fuel samples for each tank. Required work includes compliance with STI SP001, ASTM standards, EPA regulations, NFPA 110, and OSHA requirements, with specific fuel quality testing parameters mandated. The contractor must hold all necessary EPA, OSHA, and state environmental permits, employ API 653-certified inspectors with STI SP001 adjunct certification or equivalent, maintain comprehensive insurance coverage, and provide hazardous waste disposal manifests and Safety Data Sheets. Services are limited to Monday through Friday during regular business hours, coordinated with the Contracting Officer's Representative. The guaranteed minimum and contract ceiling amounts are to be determined pending offeror pricing submissions. Contract administration is handled by the VA Network Contracting Office with payment processed monthly in arrears through electronic funds transfer to the VA Financial Services Center in Austin, Texas.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

36C25527Q0047

PAGE 1 OF

1. REQUISITION NO.

2. CONTRACT NO.

3. AWARD/EFFECTIVE DATE

4. ORDER NO.

5. SOLICITATION NUMBER

6. SOLICITATION ISSUE DATE

a. NAME

b. TELEPHONE NO. (No Collect Calls)

8. OFFER DUE DATE/LOCAL

TIME

9. ISSUED BY

CODE

10. THIS ACQUISITION IS

UNRESTRICTED OR

SET ASIDE:

% FOR:

SMALL BUSINESS

HUBZONE SMALL

BUSINESS

SERVICE-DISABLED

VETERAN-OWNED

SMALL BUSINESS

WOMEN-OWNED SMALL BUSINESS

(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED

SMALL BUSINESS PROGRAM

EDWOSB

8(A)

NAICS:

SIZE STANDARD:

11. DELIVERY FOR FOB DESTINA-

TION UNLESS BLOCK IS

MARKED

SEE SCHEDULE

12. DISCOUNT TERMS

13a. THIS CONTRACT IS A

RATED ORDER UNDER

DPAS (15 CFR 700)

13b. RATING

14. METHOD OF SOLICITATION

RFQ

IFB

RFP

15. DELIVER TO

CODE

16. ADMINISTERED BY

CODE

17a. CONTRACTOR/OFFEROR

CODE

FACILITY CODE

18a. PAYMENT WILL BE MADE BY

CODE

TELEPHONE NO.

UEI:

EFT:

PHONE:

FAX:

17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER 18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED

SEE ADDENDUM

19.

20.

21.

22.

23.

24.

ITEM NO.

SCHEDULE OF SUPPLIES/SERVICES

QUANTITY

UNIT

UNIT PRICE

AMOUNT

(Use Reverse and/or Attach Additional Sheets as Necessary)

25. ACCOUNTING AND APPROPRIATION DATA

26. TOTAL AWARD AMOUNT (For Govt. Use Only) 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED.

27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED

28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________

29. AWARD OF CONTRACT: REF. ___________________________________ OFFER

COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND

DATED ________________________________. YOUR OFFER ON SOLICITATION

DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY

(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE

ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED

SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:

30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER) 30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED

AUTHORIZED FOR LOCAL REPRODUCTION

(REV. NOV 2021)

PREVIOUS EDITION IS NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.212

7. FOR SOLICITATION

INFORMATION CALL:

STANDARD FORM 1449

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES

OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30

589-27-2-1829-0010 36C25527Q0047 11- -2026 Erika Kobulnicky/Erika.Kobulnicky@va.gov 913-946-1991 12-11-2026

7:00 AM

CST

36C255 Department of Veterans Affairs Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth KS 66048 X X 562910 $22 Million N/A X Department of Veterans Affairs Kansas City VA Medical Center 4801 East Linwood Boulevard Kansas City MO 64128-2226 36C255 Department of Veterans Affairs Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth KS 66048

36C255 Department of Veterans Affairs Financial Services Center http://www.fsc.va.gov/einvoice.asp Austin TX 877-353-9791 512-460-5429 See CONTINUATION Page The Contractor shall furnish all labor, supervision, parts, materials, equipment, and any other resources necessary to complete the work in accordance with the Performance Work Statement (PWS) for the Kansas City VAMC.

1. This is a total SDVOSB set-aside.

2. This solicitation is for a five (5) Year IDIQ with five twelve-month Ordering Periods: 01/19/2027 -01/18/2032.

Individual task orders will be issued by NCO 15 Contracting Officer (CO).

3. This procurement is being competed in accordance with FAR Part 13 Simplified Acquisition Procedures.

4. Evaluation Criteria:

Price, technical, and past performance

5. Site visit:

9:00 am CT, November 30, 202 Building 6

6. Questions due no later than 7:00am, December 4, 2026, CST

7. Offers due 7:00 am CST Friday, December 11, 2026.

IMPORTANT: For additional details see B.2 PWS, B.3 Price Schedule and Addendum to FAR 52.212-1 Instructions to Offerors.

See CONTINUATION Page X X X one(1) Lisa Buchanan Contracting Officer Table of Contents

SECTION A1
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES1
SECTION B - CONTINUATION OF SF 1449 BLOCKS4
B.1 CONTRACT ADMINISTRATION DATA4
B.2 Performance Work Statement (PWS)5
B.3 PRICE/COST SCHEDULE13
ITEM INFORMATION13
B.4 DELIVERY SCHEDULE32
SECTION C - CONTRACT CLAUSES33
C.1 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION)33
C.2 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)38
C.3 52.216-18 ORDERING (AUG 2020)39
C.4 52.216-19 ORDER LIMITATIONS (OCT 1995)40
C.5 52.216-22 INDEFINITE QUANTITY (NOV 2025) (DEVIATION)40
C.6 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)41
C.7 52.219-27 NOTICE OF SET-ASIDE FOR, OR SOLE-SOURCE AWARD TO, SERVICE-DISABLED VETERAN-OWNED SMALL BUSINESS (SDVOSB) CONCERNS ELIGIBLE UNDER THE SDVOSB PROGRAM (NOV 2025) (DEVIATION)41
C.8 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS (DEVIATION APR 2026)42
C.9 52.240-91 SECURITY PROHIBITIONS AND EXCLUSIONS (NOV 2025) (DEVIATION)43
C.10 52.240-93 BASIC SAFEGUARDING OF COVERED CONTRACTOR INFORMATION SYSTEMS (DEVIATION) (NOV 2025)53
C.11 52.252-6 AUTHORIZED DEVIATIONS IN CLAUSES (NOV 2020)54
C.12 VAAR 852.204-72 PERSONNEL VETTING AND CREDENTIALING (DEVIATION) (MAR 2026)54
C.13 VAAR 852.211-72 TECHNICAL INDUSTRY STANDARDS (NOV 2018)57
C.14 VAAR 852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING—CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (OCT 2026) (DEVIATION)58
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS60
D.1 USDOL WAGE DETERMINATION INCORPORATED BY REFERENCE60
D.2 QUALITY ASSURANCE SURVEILLANCE PLAN (QASP)61
D.3 FUEL TECHNICAL MATRIX…………………………………………………………......65
SECTION E - SOLICITATION PROVISIONS66
E.1 52.212-1 INSTRUCTIONS TO OFFERORS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION)66
ADDENDUM TO FAR 52.212-1, INSTRUCTIONS TO OFFERORS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES67
E.2 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB 1998)71
E.3 52.212-2 EVALUATION- COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION)72
E.4 52.216-1 TYPE OF CONTRACT (NOV 2025) (DEVIATION)72
E.5 52.219-1 SMALL BUSINESS PROGRAM REPRESENTATIONS (NOV 2025) (DEVIATION)72
E.6 52.240-90 SECURITY PROHIBITIONS AND EXCLUSIONS REPRESENTATIONS AND CERTIFICATIONS (NOV 2025) (DEVIATION)75
E.7 52.252-5 AUTHORIZED DEVIATIONS IN PROVISIONS (NOV 2020)79
E.8 VAAR 852.252-70 SOLICITATION PROVISIONS OR CLAUSES INCORPORATED BY REFERENCE (JAN 2008)79

SECTION B - CONTINUATION OF SF 1449 BLOCKS

B.1 CONTRACT ADMINISTRATION DATA

1. Contract Administration: All contract administration matters will be handled by the following individuals:

a. CONTRACTOR:

b. GOVERNMENT:

Contracting Officer 36C255 Lisa Buchanan/ Lisa.Buchanan1@va.gov Contract Specialist 36C255 Erika Kobulnicky/ Erika.Kobulnicky@va.gov Department of Veterans Affairs Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth KS 66048

2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:

[X]
52.232-33, Payment by Electronic Funds Transfer—System for Award Management, or
[]
52.232-36, Payment by Third Party

3. INVOICES: Invoices shall be submitted in arrears:

a. Quarterly[]
b. Semi-Annually[]
c. Other[X] Monthly In arrears per accepted tank service

4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment Requests.

Department of Veterans Affairs Financial Services Center Austin, TX http://www.fsc.va.gov/einvoice.asp ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:

AMENDMENT NO
DATE

B.2 Performance Work Statement (PWS) Aboveground Fuel Tank Inspection and Fuel Oil Filtering Facility: Kansas City VA Medical Center, 4801 Linwood Blvd. Kansas City, MO 64128 Contracting Officer's Representative (COR): Zachary Homan, Maintenance & Operations Supervisor Kansas City VA Medical Center Alternate COR: Matthew Caldwell, Boiler Plant Supervisor Kansas City VA Medical Center

1. PURPOSE AND SCOPE

This contract is for annual inspection, maintenance, repair, certification, and fuel oil filtering services for all Aboveground Storage Tanks (ASTs) located at the Kansas City VA Medical Center. As part of the Medical Center's Spill Prevention, Control and Countermeasure (SPCC) Plan Program, the VA requires the services of a qualified contractor to perform the required services on all ASTs with a capacity of 55 gallons or greater, totaling sixteen (16) tanks. All work shall comply with applicable STI standards, ASTM standards, EPA regulations, NFPA 110 Chapter 8, and OSHA 29 CFR 1910, as amended.

The Contractor shall furnish all labor, supervision, materials, parts, tools, equipment, and any other resources necessary to complete the work described in this PWS, whether specifically listed or implied by the scope. The Contractor shall provide a high level of quality and workmanship and is responsible for the proper capture, containment, transport, and disposal of all fuel, water, and filtration waste generated during performance.

The Contractor shall also perform the following duties as required:

· Coordinate all work with the COR and the Operations Foreman at the Boiler Plant (Building 4) prior to beginning any task

· Perform all services Monday through Friday, during regular business hours only

· Submit a written request to the COR in advance of any required access or service interruption, stating the reason, proposed date, exact time, and estimated duration

· Project shall conform to all Records Management and Privacy Language requirements

· Any repair or deficiency-correction work identified during inspection that falls outside the base scope of this PWS shall be documented in writing with parts, labor, and rationale, and priced separately. Such work will be treated as a modification to this contract, with a distinct Contract Line-Item Number (CLIN) established by the Contracting Officer prior to commencement of work

2. APPLICABLE STANDARDS AND REFERENCES

· STI SP001 – Standard for Inspection of In-Service Shop-Fabricated Aboveground Storage Tanks

· ASTM D975-26b – Standard Specification for Diesel Fuel (all diesel fuel quality tests in Section 3, Item 4)

· NFPA 110 Chapter 8 – Emergency and Standby Power Systems

· EPA 40 CFR Part 112 – SPCC Plan Requirements

· OSHA 29 CFR 1910 – Safety and Health Regulations for General Industry

· VA Handbook 6500.6 – Security Considerations

· Applicable VA Master Specifications Copies of all referenced standards (STI SP001, ASTM D975-26b, NFPA 110 Chapter 8, and applicable VA Master Specifications) are not provided with the solicitation. Offerors are responsible for independently obtaining current copies of all referenced standards from their respective publishing organizations.

3. SCOPE OF WORK

Item 1 – Annual AST Interior and Exterior Inspection and Certification The Contractor shall perform annual interior and exterior inspections of all sixteen (16) ASTs listed in Section 3, Item 5 (Tank Inventory), and provide STI SP001 certification for each tank. Work shall include:

· Inspection of paint condition, and evaluation of rust for treatment, re-paint, repair, or replacement needs

· Inspection for indications of fuel leakage on or near any exposed components of each AST and its associated piping systems

· Inspection of component/tank damage other than rust

· Inspection of container supports and foundations

· Inspection of all signage required by applicable regulations, including but not limited to NFPA, ASME, OSHA, DVA, and EPA

· Inspection of all exposed piping and appurtenances for proper support and protection from moving vehicles

· Inspection of cathodic protection, such as sacrificial anodes, where installed (no tanks are installed on bare soil requiring cathodic protection testing)

· Verification of AST labeling of contents, size, last inspection date, safe gauge height, and year built

· Inspection of tank overfill protection devices, such as direct vision gauges, high liquid level alarms, flow restrictions, or high liquid level shut-off devices

· Testing of tank integrity, including hydrostatic and/or other non-destructive testing methods, and evaluation for signs of deterioration and discharges

· Exercising of all fuel oil valves connected to the piping system for each AST

· Replacement of any component that has failed or is beyond economical repair, including but not limited to piping, fittings, gauges, pumps, valves, and supports/brackets, as authorized by the COR

· Contractor must complete annual testing within 30 days, before or after the previous year's testing date, in accordance with Joint Commission requirements Item 2 – Fuel Oil Filtration (Polishing) and Recirculation The Contractor shall provide annual fuel oil filtration and recirculation services for all tanks listed in Section 3, Item 5, to remove water and contaminants from stored fuel. Work shall include:

· Coarse straining using a full-size basket strainer with a 100-mesh basket

· Separation using a coalescing membrane process that causes emulsified water to form into droplets as contaminated fuel passes through

· Fine filtration using a primary filter element rated at 2 microns absolute.

· Ensure all filters and strainers are restriction-free. Replace all restricted filters and clean strainers as needed.

· Water emulsification agents shall not be used at any stage of the filtration process

· Post-filtration samples shall meet the water and sediment limit in Item 4 (ASTM D2709, maximum 0.05% by volume).

· Capture, containment, transport, and disposal of all fuel and water contaminants removed during filtration; the Contractor shall provide the EPA identification number and waste manifest for any waste removed as required by the generator status confirmed by the Government.

· Water removed from the fuel system shall be contained, sampled, and characterized before disposal. The Contractor shall notify the COR before any water is disposed of and shall not discharge water or fuel to the environment. Disposal costs, waste characterization, and manifest signature responsibility:

Item 3 – Fuel Oil Treatment The Contractor shall treat all fuel with a stabilizing additive and biocide annually following filtration, to ensure and extend viable fuel usability. Work shall include:

· Application of cetane boosters, stabilizers, and biocides as needed; minimum cetane rating for diesel fuel shall not be less than 40

· All treatment chemicals shall be EPA-approved; Safety Data Sheets (SDS/MSDS) for all chemicals used shall be provided to the COR Item 4 – Fuel Oil Quality Analysis and Testing The Contractor shall take fuel samples from each diesel tank before and after filtration and submit them to a nationally accredited third-party laboratory for analysis per ASTM D975-26b (or current edition), consisting of the following tests and limits:

· Flash point, ASTM D93: minimum 52 °C.

· Water and sediment, ASTM D2709: maximum 0.05% by volume.

· Distillation, 90% recovered, ASTM D86: 282 to 338 °C.

· Kinematic viscosity at 40 °C, ASTM D445: minimum 1.9 mm²/s; maximum 4.1 mm²/s.

· Ash, ASTM D482: maximum 0.01% by mass.

· Sulfur, ASTM D5453: maximum 15 µg/g.

· Copper strip corrosion, ASTM D130: No. 3 maximum (3 hours at a minimum of 50 °C).

· Cetane number, ASTM D613: minimum 40. AND cetane index, ASTM D976: minimum 40.

· Cold filter plugging point (CFPP), ASTM D6371: maximum -16 °C (3 °F).

· Ramsbottom carbon residue on 10% distillation residue, ASTM D524: maximum 0.35% by mass.

· Lubricity, HFRR at 60 °C, ASTM D6079: maximum 520 µm.

· Electrical conductivity, ASTM D2624: minimum 25 pS/m.

· Fuel oil quality analysis shall be for post-cleaning verification purposes

· Fuel oil shall be tested for black algae and treated accordingly Samples shall be collected by an EPA-approved method that prevents cross-contamination between tanks, labeled with the collection date, and maintained under chain of custody. Laboratory reports shall be delivered to the COR and shall identify any result outside the limits above. Submission and report deadlines: The laboratory submission deadline is 2 business days after collection. Reports are due no later than 12 business days after the laboratory receives the sample.

Item 5 – Tank Inventory The following sixteen (16) tanks are included in the scope of this PWS:

Tank ID
Capacity (gal)
Type
Fuel
Boiler 1
30,000
AST
#2 Fuel Oil
Boiler 2
30,000
AST
#2 Fuel Oil
Boiler 3
30,000
AST
#2 Fuel Oil
Maint. Vehicle
400
AST
#2 Fuel Oil
Gas Maint. V
400
AST
Gasoline
Gov. Vehicle Tank
5,000
AST
Gasoline
Gen 26-A
500
Remote AST
Diesel
Gen 26-B
2,200
Belly Tank
Diesel
Gen 26-C
2,000
Remote Belly Tank
Diesel
Gen 28-A
1,850
Belly Tank
Diesel
Gen 2
194
Belly Tank
Diesel
Gen 28
6,000
Remote AST
Diesel
Day Tank 28
400
AST
Diesel
Gen 19
600
Belly Tank
Diesel
300KW Trailer
300
Belly Tank
Diesel
600KW Trailer
2,000
Belly Tank
Diesel

The tank inventory is subject to change. The Government may add, remove, or modify tanks during the period of performance by written modification. Added tanks shall be priced under the procedures in Section 1.

Item 6 – Tank Repair and Maintenance (As-Needed) Tank repair and maintenance items identified during annual inspections and testing that fall outside routine PWS scope shall be quoted separately by the Contractor and authorized by the COR prior to performance, per Section 1 (Purpose and Scope) modification/CLIN procedures.

4. GENERAL REQUIREMENTS

· The Contractor shall submit the format for all required reports within 14 calendar days of contract award and/or before any contracted services are performed

· Contractor must commence services within 14 calendar days of contract award

· All work shall be coordinated with and approved by the COR, Zachary Homan, prior to commencement of any task. In his absence, the Alternate COR, Matthew Caldwell, shall serve as the point of contact

· Contractor shall possess all required licenses, certifications, and equipment necessary to perform the requested services, including current STI SP001 certification as defined below

· Contractor shall hold all applicable EPA, OSHA, and state environmental permits/licenses required to handle fuel oil, perform hazardous waste disposal, and operate on a VA federal facility

· The Contractor shall verify the state registration status of each aboveground storage tank, including any Missouri registration required for tanks over 660 gallons

· All work shall be performed by qualified, licensed personnel as applicable to the scope

· Certified inspector means either (a) an API 653 certified inspector with STI SP001 adjunct certification, or (b) an inspector certified by the Steel Tank Institute to SP001. Formal internal and external tank inspections shall be performed by a certified inspector.

· The Contractor shall maintain insurance for the duration of the contract and shall provide certificates of insurance to the Contracting Officer prior to Notice to Proceed for: (a) general liability insurance; (b) pollution liability insurance covering fuel handling, fuel spills, and transport and disposal of fuel, water, and filtration waste; and (c) workers' compensation and employer's liability insurance, in amounts specified by the Contracting Officer. The Department of Veterans Affairs shall be named as additional insured where applicable. Certificates shall be renewed and resubmitted upon any policy renewal or change in coverage

· The Contractor shall maintain the work area in a clean, safe, and orderly condition always

· All removed materials, fuel/water contaminants, and hazardous waste shall be disposed of in accordance with applicable federal, state, and local regulations. Copies of hazardous waste disposal manifests (e.g., for used filters and oily water) shall be provided to the COR for all waste generated during service

· Services will be coordinated with the Operations Foreman at the Boiler Plant (Building 4), Monday through Friday, during regular business hours only Government Responsibilities:

· The COR, or Alternate COR in their absence, shall be reasonably available to coordinate scheduling, provide facility access, and respond to Contractor requests for guidance or authorization within the timeframes specified in this PWS

· The Government shall provide the Contractor's personnel with facility access and badging support necessary to perform the required services, subject to standard VA security and background check requirements

· The Government shall provide timely review and response to Contractor-submitted reports, deficiency lists, and repair/replacement proposals in accordance with the Inspection and Acceptance terms in Section 1 and the performance standards identified in the Quality Assurance Surveillance Plan (QASP)

· The Government will perform the monthly visual inspections required by the facility SPCC Plan. The Contractor's annual inspection does not replace the monthly inspections.

Contractor performance under this PWS will be monitored and evaluated by the Government in accordance with the Quality Assurance Surveillance Plan (QASP) issued as a companion document to this PWS. The QASP defines the performance standards, acceptable quality levels, and surveillance methods applicable to each task identified in Section 3.

5. DELIVERABLES

#
Deliverable
Due
1
Report Format Submission
14 calendar days after award
2
Inspection Report (per tank, including deficiencies)
14 calendar days after completion of service
3
Master Deficiency List and Repair/Replacement Proposal
With Inspection Report
4
Repair Completion Report and Certification
14 calendar days after completion of authorized repairs
5
Fuel Oil Lab Analysis Reports (per tank, pre/post filtration)
10–12 business days after sample submission
6
Hazardous Waste Disposal Manifests
Upon generation of waste
7
SDS/MSDS for Treatment Chemicals
Prior to or with treatment service

6. WARRANTY

The Contractor shall provide a minimum one (1) year warranty on all labor and any installed or replaced materials from the date of final acceptance by the Government for each service cycle. Equipment or materials manufacturer warranties shall be passed through to the Government and shall not be less than one (1) year.

7. PERIOD OF PERFORMANCE

The period of performance for this contract shall consist of five one-year Ordering Periods, as follows:

Period
Duration
Ordering Period One
January 19, 2027 – January 18, 2028
Ordering Period Two
January 19, 2028 – January 18, 2029
Ordering Period Three
January 19, 2029 – January 18, 2030
Ordering Period Four
January 19, 2030 – January 18, 2031
Ordering Period Five
January 19, 2031 – January 18, 2032

Annual services under each period of performance shall be completed within 30 calendar days before or after the corresponding date of the prior years’ service, in accordance with Joint Commission requirements.

The annual AST inspection under each ordering period shall be conducted in February. Specific dates shall be coordinated with and approved by the COR.

8. RECORDS AND INFORMATION MANAGEMENT

Records Management The Contractor will comply with the Department of Veterans Affairs' Veterans Health Administration (VHA) Directive 6300(2), which outlines the policies and procedures for the management of records. This directive ensures that all records, including paper and electronic, are properly maintained, accessed, and disposed of in compliance with federal regulations and VA policies. The Contractor shall adhere to all provisions of VHA Directive 6300(2), including but not limited to:

1. Record Creation and Collection: Ensuring that all records are created and collected in a manner that meets VA's standards and requirements.

2. Record Maintenance and Accessibility: Maintaining records in a secure environment where they are protected from unauthorized access, alteration, or destruction, and ensuring they are accessible as required by VA policies and federal laws.

3. Record Disposition: Disposing of records in accordance with VA's record retention and disposition schedules, ensuring that all procedures for destroying records are secure and compliant with applicable regulations.

4. Training and Compliance: Ensuring that all personnel involved in the handling of VA records are adequately trained in records management policies and procedures and are aware of the importance of compliance with VHA Directive 6300(2).

B.3 PRICE/COST SCHEDULE

This is a Five-Year IDIQ Contract with Pricing Periods:

The Guaranteed Minimum: To Be Determined The Contract Ceiling for the Life of the Contract is: To Be Determined

ITEM INFORMATION

Ordering Period One
Period 01-19-2027 through 01-18-2028 $
ITEM NUMBER
DESCRIPTION OF SUPPLIES/SERVICES
QUANTITY
UNIT
UNIT PRICE
AMOUNT
1.00
YR

Annual interior and exterior inspection and STI SP001-compliant certification of all sixteen (16) aboveground storage tanks listed in the PWS (PWS Item 1). Performed in February of the ordering period. Includes tank integrity testing, exercising of fuel oil valves, inspection report for each tank, master deficiency list, and repair/replacement proposal.

Ordering Period One POP Begin: 01-19-2027 POP End: 01-18-2028

1.00
YR

Boiler 1 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Boiler 2 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

POP Begin: 01-19-2027

PRODUCT/SERVICE CODE: J091 - Maintenance, Repair, and Rebuilding of Equipment - Fuels, Lubricants, Oils, and Waxes

1.00
YR

Boiler 3 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Maint. Vehicle – 400-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gas Maint. V – 400-gallon AST, Gasoline. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gov. Vehicle Tank – 3,000-gallon AST, Gasoline. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-A – 500-gallon Remote AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-B – 2,200-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-C – 2,000-gallon Remote Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 28-A – 1,850-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 2 – 194-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

POP Begin: 01-19-2027 POP End: 01-18-2028 PRINCIPAL NAICS CODE: 562910 - Remediation Services PRODUCT/SERVICE CODE: J091 - Maintenance, Repair, and Rebuilding of Equipment - Fuels, Lubricants, Oils, and Waxes

1.00
YR

Gen 28 – 6,000-gallon Remote AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Day Tank 28 – 400-gallon AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 19 – 600-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

300KW Trailer – 129-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

600KW Trailer – 2,000-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

Ordering Period Two
Period 01-19-2028 through 01-18-2029 $
1.00
YR

Annual interior and exterior inspection and STI SP001-compliant certification of all sixteen (16) aboveground storage tanks listed in the PWS (PWS Item 1). Performed in February of the ordering period. Includes tank integrity testing, exercising of fuel oil valves, inspection report for each tank, master deficiency list, and repair/replacement proposal.

Ordering Period Two POP Begin: 01-19-2028 POP End: 01-18-2029

1.00
YR

Boiler 1 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Boiler 2 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Boiler 3 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Maint. Vehicle – 400-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gas Maint. V – 400-gallon AST, Gasoline. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gov. Vehicle Tank – 3,000-gallon AST, Gasoline. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-A – 500-gallon Remote AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-B – 2,200-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-C – 2,000-gallon Remote Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 28-A – 1,850-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 2 – 194-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 28 – 6,000-gallon Remote AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Day Tank 28 – 400-gallon AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 19 – 600-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

300KW Trailer – 129-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

600KW Trailer – 2,000-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

Ordering Period Three
Period 01-19-2029 through 01-18-2030 $
1.00
YR

Annual interior and exterior inspection and STI SP001-compliant certification of all sixteen (16) aboveground storage tanks listed in the PWS (PWS Item 1). Performed in February of the ordering period. Includes tank integrity testing, exercising of fuel oil valves, inspection report for each tank, master deficiency list, and repair/replacement proposal.

Ordering Period Three POP Begin: 01-19-2029 POP End: 01-18-2030

1.00
YR

Boiler 1 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Boiler 2 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Boiler 3 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Maint. Vehicle – 400-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gas Maint. V – 400-gallon AST, Gasoline. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR
__________________
__________________

Gov. Vehicle Tank – 3,000-gallon AST, Gasoline. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-A – 500-gallon Remote AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-B – 2,200-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-C – 2,000-gallon Remote Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 28-A – 1,850-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 2 – 194-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 28 – 6,000-gallon Remote AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Day Tank 28 – 400-gallon AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 19 – 600-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

300KW Trailer – 129-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

600KW Trailer – 2,000-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

Ordering Period Four
Period 01-19-2030 through 01-18-2031 $
1.00
YR

Annual interior and exterior inspection and STI SP001-compliant certification of all sixteen (16) aboveground storage tanks listed in the PWS (PWS Item 1). Performed in February of the ordering period. Includes tank integrity testing, exercising of fuel oil valves, inspection report for each tank, master deficiency list, and repair/replacement proposal.

Ordering Period Four POP Begin: 01-19-2030 POP End: 01-18-2031

1.00
YR

Boiler 1 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Boiler 2 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Boiler 3 – 30,000-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Maint. Vehicle – 400-gallon AST, #2 Fuel Oil. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gas Maint. V – 400-gallon AST, Gasoline. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gov. Vehicle Tank – 3,000-gallon AST, Gasoline. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-A – 500-gallon Remote AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-B – 2,200-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 26-C – 2,000-gallon Remote Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 28-A – 1,850-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 2 – 194-gallon Belly Tank, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Gen 28 – 6,000-gallon Remote AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4). Includes capture, containment, transport, and disposal of all fuel, water, and filter waste with manifests; Safety Data Sheets; chain of custody; and laboratory reports.

1.00
YR

Day Tank 28 – 400-gallon AST, Diesel. Annual fuel oil filtration (polishing) and recirculation, fuel oil treatment, and fuel sampling with third-party laboratory analysis (PWS Items 2, 3, and 4).

This is the start of the file's text. The full file is on GovTribe.