S02-589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A.pdf
PDF 1 MB Posted
- Solicitation number
- 36C25524R0036
About this file
This document is a set of 100% design drawings for project 589A7-24-408 to renovate Building 61 at the Robert J. Dole VA Medical Center in Wichita, Kansas.
The project scope is limited to renovating the old VBA area, including the Veteran's Service Area, offices, computer lab, and director's conference rooms, along with adjacent corridors. The drawings detail the demolition plan, new floor plan design, HVAC system, electrical/power/communications, fire safety, and door hardware. Key aspects include installing new LED lighting, HVAC terminal units, ductwork, power/data receptacles, and physical access controls with PIV card readers. The contractor will be responsible for patching, painting, and repairing finishes in the work area.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S02-Technical Questions-part II-589A7-24-408 Renovate bldg.61 for VEO.pdf | ||
| 36C25524R0036_4.docx | DOCX document | |
| S02-Technical Questions-part I-589A7-24-408 Renovate bldg.61 for VEO.pdf | ||
| S04-589A7-24-408 Pre-Bid Meeting Attendance.pdf | ||
| 36C25524R0036_3.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT 589A7-24-408
RENOVATE BUILDING 61 FOR VEO AND
PATIENT BENEFITS
DESIGN DRAWINGS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Jarod Rutliff
AutoCAD SHX Text Dwg Sht 100
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Drawing Sheet Index 100 COVER SHEET 101 EXISTING FLOOR PLAN & PROJECT LOCATION 102 NEW FLOOR PLAN DESIGN 103 GENERAL DEMOLITION PLAN 104 NEW HVAC DESIGN PLAN - INDOOR 105 REFLECTED CEILING PLAN 106 NEW ELEC/POWER/COMM/PHYS SEC PLAN 107 FIRE SAFETY PLAN 108 HARDWARE BASIS OF DESIGN AND SCHEDULE
1-ELEV-N
AutoCAD SHX Text
DIRECTOR'S
AutoCAD SHX Text 126D
AutoCAD SHX Text
DIRECTOR'S
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 126E
AutoCAD SHX Text
DIRECTOR'S
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
COMPUTER LAB
AutoCAD SHX Text 129A
AutoCAD SHX Text
COMMUNICATION
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 129B
AutoCAD SHX Text
VETERAN'S
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
DIRECTOR'S
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text H+S
AutoCAD SHX Text H+S
AutoCAD SHX Text Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Dwg Sht 101
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING FLOOR PLAN & PROJECT LOCATION General Notes: 1. Primary project scope is limited to old VBA area circled in orange. It includes the following rooms & areas: Primary project scope is limited to old VBA area circled in orange. It includes the following rooms & areas: 1.1. Veteran's Service Area (129), Office (129B), Computer Lab (129A), Director's Conference Room's (126E and 127), and adjacent corridors. Veteran's Service Area (129), Office (129B), Computer Lab (129A), Director's Conference Room's (126E and 127), and adjacent corridors. 2. Although project scope does not include significant work in the EHRM data closet or neighboring spaces such as the Director's Suite, these areas will be made Although project scope does not include significant work in the EHRM data closet or neighboring spaces such as the Director's Suite, these areas will be made accessible on an as-needed bases to support the work of the project. Contractor must plan for access to these spaces in advance and coordinate with COR. 3. Contractor must field verify all existing conditions compared to the drawings and notify VA/COR of discrepancies immediately. This is applicable for all drawings. Contractor must field verify all existing conditions compared to the drawings and notify VA/COR of discrepancies immediately. This is applicable for all drawings. 4. Any needed patching, painting, and repair of finishes in the work area caused by construction fall on the responsibility of the contractor.Any needed patching, painting, and repair of finishes in the work area caused by construction fall on the responsibility of the contractor.
DIRECTORS
AutoCAD SHX Text 126G
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 129C
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 129D
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 129E
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 129F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 129G
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 129H
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 129A
AutoCAD SHX Text E&E
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 126E
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
ROI
AutoCAD SHX Text 129B
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text Print
AutoCAD SHX Text Shred
AutoCAD SHX Text Print
AutoCAD SHX Text Shred
AutoCAD SHX Text Print
AutoCAD SHX Text Print
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 126H
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR
AutoCAD SHX Text 129B
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 127A
AutoCAD SHX Text 127A-2
AutoCAD SHX Text
AutoCAD SHX Text 126E-2
AutoCAD SHX Text 126G
AutoCAD SHX Text 129C
AutoCAD SHX Text 129D
AutoCAD SHX Text 129E
AutoCAD SHX Text 129F
AutoCAD SHX Text 129G
AutoCAD SHX Text 129H
AutoCAD SHX Text 129A-2
AutoCAD SHX Text 129A-1
AutoCAD SHX Text 129-2
AutoCAD SHX Text 129-1
AutoCAD SHX Text 126H
AutoCAD SHX Text 127A-1
AutoCAD SHX Text 126E-1
AutoCAD SHX Text 127A-3
AutoCAD SHX Text NEW FLOOR PLAN DESIGN General Notes: 1. 36" solid core wooden door with PIV/badge reader access as shown on Sheet 106. 36" solid core wooden door with PIV/badge reader access as shown on Sheet 106. 2. 36" solid core wooden doors with keyed access for office spaces and conference room. 36" solid core wooden doors with keyed access for office spaces and conference room. 3. See Sheet 108 for door hardware schedule See Sheet 108 for door hardware schedule 4. 3-5/8" 20ga studs with " gypsum board. 3-5/8" 20ga studs with " gypsum board. 58" gypsum board. 5. Plastic Laminate countertops at all service windows and windowsills Plastic Laminate countertops at all service windows and windowsills 6. Carpet Tile flooring and resilient wall base.Carpet Tile flooring and resilient wall base.
AutoCAD SHX Text Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Dwg Sht 102
AutoCAD SHX Text
H+S
AutoCAD SHX Text H+S
AutoCAD SHX Text Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Dwg Sht 103
AutoCAD SHX Text
AutoCAD SHX Text
GENERAL DEMOLITION PLAN General Notes: 1. Demo all existing carpet and flooring from existing space. Demo all existing carpet and flooring from existing space. 2. Completely remove the walls and doors marked orange. Completely remove the walls and doors marked orange. 3. Remove walls for door opening in locations marked pink Remove walls for door opening in locations marked pink 4. VA retains right of first refusal for any furniture or equipment left in the space. Please coordinate with COR for removal. VA retains right of first refusal for any furniture or equipment left in the space. Please coordinate with COR for removal. 5. Remove existing LED & fluorescent lamps, ballasts, and troffers. Remove existing LED & fluorescent lamps, ballasts, and troffers. 6. Remove existing power receptacles, data junction boxes, and switchesRemove existing power receptacles, data junction boxes, and switches
S 175
AutoCAD SHX Text S 175
AutoCAD SHX Text S 175
AutoCAD SHX Text S 175
AutoCAD SHX Text S 175
AutoCAD SHX Text S 175
AutoCAD SHX Text S 175
AutoCAD SHX Text S 175
AutoCAD SHX Text S 50
AutoCAD SHX Text S 50
AutoCAD SHX Text S 100
AutoCAD SHX Text S 100
AutoCAD SHX Text S 100
AutoCAD SHX Text S 100
AutoCAD SHX Text S 100
AutoCAD SHX Text S 100
AutoCAD SHX Text S 100
AutoCAD SHX Text S 100
AutoCAD SHX Text S 100
AutoCAD SHX Text S 125
AutoCAD SHX Text S 125
AutoCAD SHX Text S 125
AutoCAD SHX Text S 125
AutoCAD SHX Text S 150
AutoCAD SHX Text S 150
AutoCAD SHX Text S 150
AutoCAD SHX Text S 150
AutoCAD SHX Text S 150
AutoCAD SHX Text S 150
AutoCAD SHX Text R 525
AutoCAD SHX Text R 100
AutoCAD SHX Text R 350
AutoCAD SHX Text R 100
AutoCAD SHX Text R 350
AutoCAD SHX Text R 125
AutoCAD SHX Text R 125
AutoCAD SHX Text R 350
AutoCAD SHX Text R 450
AutoCAD SHX Text R 450
AutoCAD SHX Text R 450
AutoCAD SHX Text R 200
AutoCAD SHX Text R 100
AutoCAD SHX Text R 125
AutoCAD SHX Text R 150
AutoCAD SHX Text
VAV
AutoCAD SHX Text
VAV
AutoCAD SHX Text
VAV
AutoCAD SHX Text
VAV
AutoCAD SHX Text
EXISTVAV
AutoCAD SHX Text
EXIST. VAV
AutoCAD SHX Text R 125
AutoCAD SHX Text R 150
AutoCAD SHX Text Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Dwg Sht 104
AutoCAD SHX Text
AutoCAD SHX Text
NEW HVAC DESIGN PLAN - INDOOR Mechanical General Notes 1. Install new supply terminal units, ductwork, temperature controlles, and diffusers as shown. Install new supply terminal units, ductwork, temperature controlles, and diffusers as shown. 2. Final locations for each temperature controller placement will be coordinated with the Wichita VA/COR. Final locations for each temperature controller placement will be coordinated with the Wichita VA/COR. 3. Install new return ductwork as shown and tie into existing return. Install new return ductwork as shown and tie into existing return. 4. Relocate existing ductwork, piping, electrical conduits, and cabling as necessary to accomplish final installation as shown. Relocate existing ductwork, piping, electrical conduits, and cabling as necessary to accomplish final installation as shown. 5. Coordinate routing of plumbing and HVAC piping with ductwork, lights, architectural ceiling and structural elements. Piping shall rise and drop, jog or offset as required to avoid conflicts. Coordinate routing of plumbing and HVAC piping with ductwork, lights, architectural ceiling and structural elements. Piping shall rise and drop, jog or offset as required to avoid conflicts. Ductwork shall take precedence over all piping except where grade must be maintained for drainage. 6. All supply, return, and exhaust branches to grilles, registers, and diffusers shall have a manual balance damper. All supply, return, and exhaust branches to grilles, registers, and diffusers shall have a manual balance damper. 7. All controls to tie into existing building control system and report back to head end unit in the boiler plant. All controls to tie into existing building control system and report back to head end unit in the boiler plant. 8. Any insulating material that needs to be removed or is damaged shall be replaced to match existing. Any insulating material that needs to be removed or is damaged shall be replaced to match existing. 9. Field verify all conditions and include both a pre and post-construction TAB of the HVAC system. Field verify all conditions and include both a pre and post-construction TAB of the HVAC system. 10. Equipment startup, verification of operational safeties, and tuning per manufacturer's specifications shall be completed by the contractor.Equipment startup, verification of operational safeties, and tuning per manufacturer's specifications shall be completed by the contractor.
Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Dwg Sht 105
AutoCAD SHX Text
AutoCAD SHX Text
REFLECTED CEILING PLAN General Notes: 1. Install new 2'x4' LED troffers in the locations shown. Install new 2'x4' LED troffers in the locations shown. 2. Lights will be wired to respective switch locations shown on drawing 106. Lights will be wired to respective switch locations shown on drawing 106. 3. Supply/return/exhaust diffuser and grille locations shown for reference alongside general 2'x2' suspended ceiling plan. Supply/return/exhaust diffuser and grille locations shown for reference alongside general 2'x2' suspended ceiling plan. 4. Sprinkler locations shown for reference, see dwg sht 107 for more detail.Sprinkler locations shown for reference, see dwg sht 107 for more detail.
s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Dwg Sht 106
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NEW ELEC/POWER/COMM/PHYSICAL SECURITY General Notes: 1. Install NEMA 5-20R receptacles, light switches, and data receptacles in areas shown. Install NEMA 5-20R receptacles, light switches, and data receptacles in areas shown. 1.1. Occupancy sensor switches can be installed in main waiting room, offices, and conference room. Occupancy sensor switches can be installed in main waiting room, offices, and conference room. 1.2. General purpose on/off switches can be installed in all other locations. General purpose on/off switches can be installed in all other locations. 2. PIV card reader / badge scanner for restricted access to be installed and tied to access doors via electric strike in locations shown. PIV card reader / badge scanner for restricted access to be installed and tied to access doors via electric strike in locations shown. 2.1. Contractor to utilize C-Cure system with installation of card reader. Contractor will be responsible for all necessary licenses. Contractor to utilize C-Cure system with installation of card reader. Contractor will be responsible for all necessary licenses. 2.2. Coordinate with VA/COR for IP address needs and to verify whether iSTAR Ultra SE door panel & associated supply is available to connect to. If not, contractor will need to Coordinate with VA/COR for IP address needs and to verify whether iSTAR Ultra SE door panel & associated supply is available to connect to. If not, contractor will need to furnish and install necessary equipment in nearby electrical closet. 2.3. Contractor to install 8-port multimode fiber switch if existing infrastructure referenced in note 2.2 isn't available. Contractor to run CAT6a cable from new panel to tie into Contractor to install 8-port multimode fiber switch if existing infrastructure referenced in note 2.2 isn't available. Contractor to run CAT6a cable from new panel to tie into said switch. 3. Main hallway/corridor finishes to be made to match existing where modifications take place. This includes but is not limited to patching, drywall, paint, textured surface finishes, Main hallway/corridor finishes to be made to match existing where modifications take place. This includes but is not limited to patching, drywall, paint, textured surface finishes, stainless steel panels, ceiling tiles, and vinyl cove base. 3.1. At a minimum this will be required for new wall finishes where previous doors were located.At a minimum this will be required for new wall finishes where previous doors were located.
AutoCAD SHX Text
H+S
AutoCAD SHX Text H+S
AutoCAD SHX Text H+S
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR
AutoCAD SHX Text Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Dwg Sht 107
AutoCAD SHX Text
AutoCAD SHX Text
FIRE SAFETY PLAN 1. Fire alarm horn & strobe combo to be mounted in shown locations alongside pull box. All other locations to have strobe-only alarm installed. Fire alarm horn & strobe combo to be mounted in shown locations alongside pull box. All other locations to have strobe-only alarm installed. 2. Contractor shall field verify fire suppression coverage and provide shop drawings for review prior to install. Contractor shall field verify fire suppression coverage and provide shop drawings for review prior to install. 3. Existing sprinklers in the space are marked in their approximate locations on the drawing with green & red circles. Existing sprinklers in the space are marked in their approximate locations on the drawing with green & red circles. 3.1. Green indicates where the existing location should work with the new floor plan with minimal changes. Green indicates where the existing location should work with the new floor plan with minimal changes. 3.2. Red indicates where the existing location interferes with planned HVAC, new walls or new lighting plans. Red indicates where the existing location interferes with planned HVAC, new walls or new lighting plans. 3.3. Orange indicates the proposed locations for new or relocated sprinklers Orange indicates the proposed locations for new or relocated sprinklers 4. Sprinkler piping, heads, and escutcheons will need to be modified to service the same general locations they're currently in. This includes coordinating around light fixtures and HVAC Sprinkler piping, heads, and escutcheons will need to be modified to service the same general locations they're currently in. This includes coordinating around light fixtures and HVAC plans. 5. Other adjustments to be coordinated with the COROther adjustments to be coordinated with the COR
Designed
AutoCAD SHX Text Drawn
AutoCAD SHX Text Checked
AutoCAD SHX Text Approved
AutoCAD SHX Text Title
AutoCAD SHX Text Sheet of
AutoCAD SHX Text File No.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Date
AutoCAD SHX Text Approved
AutoCAD SHX Text Description
AutoCAD SHX Text Job Class
AutoCAD SHX Text Date
AutoCAD SHX Text 4/5/24
AutoCAD SHX Text Rev. A - Corrected DWG Sheet
AutoCAD SHX Text Numbering and added Sheet 108
AutoCAD SHX Text J. Rutliff
AutoCAD SHX Text
ROBERT J DOLE VAMC
AutoCAD SHX Text
ENGINEERING - FOR OFFICIAL USE ONLY (FOUO/CUI)
AutoCAD SHX Text 5500 E Kellogg Ave
AutoCAD SHX Text Wichita, KS 67218
AutoCAD SHX Text 589A7-24-408
AutoCAD SHX Text
BUILDING 61 1ST FLOOR
AutoCAD SHX Text Dwg Sht 108
AutoCAD SHX Text
| Sheets and Views |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-100 |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-101 |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-102 |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-103 |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-104 |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-105 |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-106 |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-107 |
| 589A7-24-408 Renovate Bldg 61 - 100 percent bid dwgs - Rev A-108 |