Z1DA--Replace Mechanical Systems in Buildings 18 & 60 PN:657-19-103JB
Solicitation number
36C25520R0063
Issued by

About this file

This pre-solicitation notice announces a forthcoming solicitation for replacement of mechanical systems in two buildings at the Jefferson Barracks Division of the VA Saint Louis Health Care System. The project cost is estimated between $2-5 million. The NAICS code is 238220, with a small business size standard of $16.5 million. The duration is estimated at 426 calendar days. This project is a competitive total set-aside for Service-Disabled Veteran-Owned Small Businesses. The solicitation will be posted on April 7, 2020 to FedBizOpps. A site visit is scheduled and attendance is encouraged. No hard copies will be provided and phone questions will not be accepted. Questions shall be emailed to the specified addresses. The successful prime contractor must perform at least 25% of construction labor. Registration in SAM and VetBiz is required to submit an offer, which shall be evaluated using Best Value Lowest Price Technically Acceptable. Award will be made without discussions unless necessary.

36C25520R0063 657-19-103JB - Combined Drawings 100PCT_Part1.pdf

View the file

Other files

File Type Posted
36C25520R0063-014.pdf PDF
36C25520R0063-016.pdf PDF
36C25520R0063-011.pdf PDF
36C25520R0063-006.pdf PDF
36C25520R0063-008.pdf PDF
36C25520R0063-015.pdf PDF
36C25520R0063-004.pdf PDF
36C25520R0063-009.pdf PDF
36C25520R0063-002.docx DOCX document
36C25520R0063-013.pdf PDF
36C25520R0063-007.pdf PDF
36C25520R0063-010.pdf PDF
36C25520R0063-012.pdf PDF
36C25520R0063-005.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4 160 VO LTS

D UST CO LLECTO R

LIQ

UEFIED PETRO

LEUM

G

AS

FLAM

M

ABLE G

AS 2

TRASH CO M PACTO R

P S

ILVER

B

UILDING

1 23

B UILDING 23

VA PO LICE

E LECTR IC AC CESS

TRANSFO RM ER

TRANSFO RM ER

TRANSFO RM ER

H VAC UNIT

E LECTRI C PANEL

H VAC UNIT

S&C PAD M O UNTED G EAR

CATALO G # 55152-C3DG IG 2P1V M O DEL# PM H-9E E13299 SG -52

13278

1CC

56G

3T 183

1CC

1G

1CC

5 4

4T

60G 51T

60T

52SG

52G

53G 53T

1CC

104T

102T

101T

1CC

55G th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

02/10/2020

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

657-19-103JB

/1

/2

:3 :5

P

M

00-GI-001

COVER SHEET FCA - REPLACE MEHCANICAL

SYSTEMS BLDG 18 & 60

TL SD

18 & 60

Drawing # 1 of 77

U.S. DEPARTMENT OF VETERANS AFFAIRS

VA ST. LOUIS HEALTH CARE SYSTEM

VA PROJECT NUMBER: 657-19-103JB

JEFFERSON BARRACKS

##-XX-###

SG = STRUCTURAL GENERAL

SF = STRUCTURAL FRAMING

MG = MECHANICAL GENERAL

MP = MECHANICAL PIPING

MH = MECHANICAL HVAC

PG = PLUMBING MEDICAL GAS

PL = PLUMBING FIXTURES

EG = ELECTRICAL GENERAL

EL = ELECTRICAL LIGHTING

DRAWING INDEX LEGEND

SHEET TYPE DESIGNATORS

0 = GENERAL

1 = PLANS

2 = ELEVATIONS

3 = SECTIONS

4 = LARGE-SCALE VIEWS

5 = DETAILS

6 = SCHEDULES & DIAGRAMS

7 = USER DEFINED

8 = USER DEFINED

9 = 3D REPRESENTATIONS

BUILDING NUMBER

FLOOR NUMBER ON PLAN SHEETS

SHEET NUMBER

OVERALL CAMPUS SITE PLAN, BUILDING NUMBER, AND PROJECT LOCATOR

P la n N or th

True North

FCA - REPLACE MECHANICAL

SYSTEMS BLDG 18 & 60

PROJECT

LOCATION

PROJECT

LOCATION

SHEET INDEX

SHEET

NUMBER SHEET NAME

00-GI-001 COVER SHEET

00-AS-101 ARCHITECTURAL SITE PLAN

00-AE-501 CHILLER PAD PLAN & STRUCTURAL DETAILS

18-AL-101 ARCHITECTURAL LIFE SAFETY AND PHASING PLAN

18-AL-102 ARCHITECTURAL LIFE SAFETY AND PHASING PLAN

60-AL-101 ARCHITECTURAL LIFE SAFETY AND PHASING PLAN

18-AD-101 ARCHITECTURAL DEMOLITION REFLECTED CEILING PLAN - FLOOR 00

18-AD-111 ARCHITECTURAL DEMOLITION REFLECTED CEILING PLAN - FLOOR 01

18-AD-121 ARCHITECTURAL DEMOLITION REFLECTED CEILING PLAN - FLOOR 02

18-AD-131 ARCHITECTURAL DEMOLITION REFLECTED CEILING PLAN - FLOOR 03

60-AC-101 ARCHITECTURAL REFLECTED CEILING PLAN - FLOOR 01

00-MG-001 MECHANICAL ABBREVIATIONS AND GENERAL NOTES

00-MG-002 MECHANICAL SYMBOLS

00-MG-501 MECHANICAL DETAILS

00-MG-502 MECHANICAL DETAILS

00-MG-503 MECHANICAL DETAILS

00-MG-504 MECHANICAL DETAILS

00-MG-505 MECHANICAL DETAILS

00-MG-506 MECHANICAL DETAILS

00-MG-507 MECHANICAL DETAILS

00-MG-508 MECHANICAL DETAILS

00-MG-601 MECHANICAL EQUIPMENT SCHEDULES

00-MG-602 MECHANICAL EQUIPMENT SCHEDULES

00-MG-701 MECHANICAL CONTROLS

00-MG-702 MECHANICAL CONTROLS

18-MG-801 MECHANICAL PHASING PLAN

18-MD-101 MECHANICAL DEMOLITION PLAN - SUB-BASEMENT

18-MD-102 MECHANICAL DEMOLITION PLAN - FLOOR 00

18-MD-111 MECHANICAL DEMOLITION PLAN - FLOOR 01

18-MD-121 MECHANICAL DEMOLITION PLAN - FLOOR 02

18-MD-131 MECHANICAL DEMOLITION PLAN - FLOOR 03

18-MD-141 MECHANICAL DEMOLITION PLAN - FLOOR 04

18-MH-101 MECHANICAL HVAC PLAN - FLOOR 00

18-MH-111 MECHANICAL HVAC PLAN - FLOOR 01

18-MH-121 MECHANICAL HVAC PLAN - FLOOR 02

18-MH-131 MECHANICAL HVAC PLAN - FLOOR 03

18-MH-141 MECHANICAL HVAC PLAN - FLOOR 04

18-MH-401 MECHANICAL HVAC LARGE-SCALE VIEWS

18-MH-601 MECHANCIAL RISER DIAGRAM - HVAC

18-MP-100 MECHANICAL PIPING PLAN - SUB-BASEMENT

18-MP-101 MECHANICAL PIPING PLAN - FLOOR 00

18-MP-111 MECHANICAL PIPING PLAN - FLOOR 01

18-MP-121 MECHANICAL PIPING PLAN - FLOOR 02

18-MP-131 MECHANICAL PIPING PLAN - FLOOR 03

18-MP-401 MECHANICAL PIPING LARGE-SCALE VIEWS

18-MP-601 MECHANCIAL RISER DIAGRAM - PIPING

60-MD-111 MECHANICAL DEMOLITION PLAN - FLOOR 01

60-MD-121 MECHANICAL DEMOLITION PLAN - FLOOR 02

60-MH-111 MECHANICAL HVAC PLAN - FLOOR 01

60-MH-121 MECHANICAL HVAC PLAN - FLOOR 02

00-EG-001 ELECTRICAL ABBREVIATIONS AND GENERAL NOTES

00-EG-002 ELECTRICAL SYMBOLS

00-EG-501 ELECTRICAL DETAILS

00-EG-502 ELECTRICAL SEISMIC DETAILS

18-EG-503 ELECTRICAL PANEL SCHEDULES

18-EG-504 ELECTRICAL EQUIPMENT SCHEDULE

18-EG-601 ELECTRICAL ONE LINE

18-ED-101 ELECTRICAL DEMOLITION PLAN - FLOOR 00

18-ED-111 ELECTRICAL DEMOLITION PLAN - FLOOR 01

18-ED-121 ELECTRICAL DEMOLITION PLAN - FLOOR 02

18-ED-131 ELECTRICAL DEMOLITION PLAN - FLOOR 03

18-EP-101 ELECTRICAL POWER PLAN - FLOOR 00

18-EP-111 ELECTRICAL POWER PLAN - FLOOR 01

18-EP-121 ELECTRICAL POWER PLAN - FLOOR 02

18-EP-131 ELECTRICAL POWER PLAN - FLOOR 03

18-EI-101 ELECTRICAL INSTRUMENTATION PLAN - FLOOR 00

18-EI-111 ELECTRICAL INSTRUMENTATION PLAN - FLOOR 01

18-EI-121 ELECTRICAL INSTRUMENTATION PLAN - FLOOR 02

18-EI-131 ELECTRICAL INSTRUMENTATION PLAN - FLOOR 03

60-ED-111 ELECTRICAL DEMOLITION PLAN - FLOOR 01

60-ED-121 ELECTRICAL DEMOLITION PLAN - FLOOR 02

60-EP-111 ELECTRICAL POWER PLAN - FLOOR 01

60-EP-121 ELECTRICAL POWER PLAN - FLOOR 02

60-EI-111 ELECTRICAL INSTRUMENTATION PLAN - FLOOR 01

60-EI-121 ELECTRICAL INSTRUMENTATION PLAN - FLOOR 02

60-EG-501 ELECTRICAL PANEL SCHEDULES

60-EG-601 ELECTRICAL ONE LINE

DISCIPLINE DESIGNATORS EXAMPLES

GI = GENERAL INFORMATION

GC = GENERAL CONTRACT

CS = CIVIL SITE

AD = ARCHITECTURAL DEMOLITION

AS = ARCHITECTURAL SITE

AE = ARCHITECTURAL ELEMENTS

FLOOR PLANS, ELEVATIONS, DETAILS

AI = ARCHITECTURAL INTERIORS

AG = ARCHITECTURAL GRAPHICS

AF = ARCHITECTURAL FINISHES

AC = ARCHITECTURAL CEILING PLAN

AW = ARCHITECTURAL WAYFINDING

AP = ARCHITECTURAL SPACE PLANNING

FLOOR PLANS & SCHEDULES

AL = ARCHITECTURAL LIFE SAFETY

DRAWINGS

AREA MAP

N o rt h

Robert Thornbrugh

MVP

4 160 VO LTS

D UST CO LLEC TO R

L

IQ

UE

FIED

PETR

O

LEUM

G

AS

F

LAM

M

A

BLE G

AS 2

T RAS H CO M PAC TO R

P S

IL

VER

B

UILD

ING

1 23

B UIL DING 23

V A PO LICE

E LE CT RIC A CCE SS

T RAN SFO R M ER

T RAN SFO R M ER

T RAN SFO R M ER

H VA C U NIT

E LE CTR IC PAN EL

H VA C U NIT

S &C PA D M O U NTED G EAR

C ATAL O G # 55152 -C3DG IG 2P1 V M O D EL# P M H-9E E13 299 SG -52

1 3278

REFER TO DETAIL 1/00-AE-501

FOR ENLARGED PLAN.

TEMPORARY GRAVEL LOT FOR

CONSTRUCTION STAGING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

02/10/2020

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

657-19-103JB

/1

/2

:3 :5

P

M

00-AS-101

ARCHITECTURAL SITE PLAN FCA - REPLACE MEHCANICAL

SYSTEMS BLDG 18 & 60

MVP SD

18 & 60

Drawing # 2 of 77

Plan North

True North

1" = 100'-0"

ARCHITECTURAL SITE PLAN

EXISTING CHILLER AND PAD TO BE

REMOVED. REFER TO MECHANICAL

DRAWINGS FOR MORE INFORMATION.

LINE OF NEW

CHILLER

6"

4"

6' - 0" 7' - 4 3/4" 6' - 0"

4"

6"

/4

LINE OF EXISTING CURB

EXISTING MECHANICAL AREA WELL

M30-P1 BOLLARD SYSTEM. TYP.

SEE DETAIL 2/00-AE-501.

A

A

B B

/4

21' - 0 3/4"

1' - 6" 8" 9' - 11 3/8" 9' - 9 3/8" 8" 1' - 6"

5' - 10" 5' - 10"

SEE PLAN

#4 BARS @ 12" O.C.

EXISTING GRADE

NEW CHILLER. SEE

MECHANICAL.

8"

1" CHAMFER (ALL SIDES

4" FENCE POST (BY

CONTRACTOR). SET IN

CONCRETE 4" MIN.

EMBEDMENT DEPTH.

LINE OF EXISTING BUILDING

#4 BARS @ 12" O.C.

NEW CHILLER. REFER TO

MECHANCIAL DRAWINGS.

#4 BARS @ 12" O.C.

8"

(M A

X

#4 BARS @ 12" O.C.6

SEE PLAN

8"

6"

4" FENCE POST (BY

CONTRACTOR). SET IN

CONCRETE 4" MIN.

EMBEDMENT DEPTH

1" CHAMFER

(ALL SIDES)

6"

1" CHAMFER (ALL SIDES)

4" FENCE POST (BY

CONTRACTOR). SET IN

CONCRETE 4" MIN.

EMBEDMENT DEPTH.

3" MIN. COVER (TYP.)

4"

FIXED BOLLARD IN

REINFORCED

CONCRETE FOOTINGDIRECTION OF

IMPACT

CONCEPTUAL SECTION VIEW

NOTES:

1. CONTRACTOR SHALL PROVIDE M30-P1 BOLLARD SYSTEMS, PER ASTM F256-07.

2. INSTALLATION AND LOCATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.

3. DO NOT SCALE DRAWINGS.

4. CONTRACTOR SHALL HAVE BOLLARDS DESIGNED BY MANUFACTURER TO MEET PROJECT REQUIREMENTS.

5. ALL INFORMATION CONTAINED HERIN WAS CURRENT AT THE TIME OF DEVELOPMENT BUT MUST BE REVIEWED

AND APPROVED BY THE PRODUCT MANUFACTURER TO BE CONSIDERED ACCURATE.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:3 :5

P

M

00-AE-501

CHILLER PAD PLAN & STRUCTURAL

DETAILS

18 & 60

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

MVP SD Drawing # 3 of 77

3/16" = 1'-0"

PLAN DETAIL @ NEW CHILLER PAD

1" = 1'-0"

SECTION A-A

1" = 1'-0"

SECTION B-B

GENERAL STRUCTURAL NOTES:

1. THE DRAWINGS INDICATE THE SIZE AND RELATIVE LOCATION OF

STRUCTURAL MEMBERS, THE DESIGN LOADS AND OTHER

INFORMATION PERTINENT TO THE STRUCTURAL DESIGN. THEY

DO NOT INDICATE THE METHODS OF CONSTRUCTION.

2. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS

BEFORE BEGINNING CONSTRUCTION.

3. THE CONTRACTOR HAS THE OPTION TO INSTALL THE SLAB IN

ACCORDANCE WITH SECTION B-B IF THE SLAB SHOWN IN

SECTION A-A CANNOT BE ACHIEVED DUE TO THE SLOPE OF THE

EXISTING GRADE RESULTING IN AN EXCESS OF CUTTING AND

FILLING FOR A LEVEL SLAB.

CONCRETE AND SLAB NOTES:

1. REINFORCING BARS MUST CONFORM TO ASTMA615 (60KSI).

2. CONCRETE MUST HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH

(f'c) OF 3000PSI. (AIR ENTRAINED)

3. ALL SLAB EDGES SHALL BE CHAMFERED 1" ON EXPOSED EDGES U.N.O.

4. MAINTAIN A MINIMUM OF 6" CONCRETE EDGE DISTANCE FROM

EDGE OF FENCE POST AND EDGE OF CONCRETE SLAB.

5. CAST-IN-PLACE FENCE POSTS WITH A MINIMUM DEPTH OF 4" INTO

CONCRETE PAD

DESIGN CRITERIA:

1. BUILDING CODE: 2015 INTERNATIONAL BUILDING CODE (IBC)

2. WIND DESIGN DATA: (ASCE 7-10)

BASIC WIND SPEED, V 120 MPH

BUILDING CATEGORY IV

EXPOSURE CATEGORY B

3. SEISMIC DESIGN DATA: (ASCE 7-10)

SOIL SITE CLASS (ASSUMED) D

SEISMIC CATEGORY D

SS 0.451

S1

RISK CATEGORY IV

SEISMIC IMPORTANCE FACTOR, IE 1.5

ANALYSIS PROCEDURE USED MECHANICAL EQUIPMENT CH.13

4. GEOTECHNICAL INFORMATION

ALLOWABLE SOIL BEARING PRESSURE (ASSUMED) 1500 PSF

ACTIVE LATERAL PRESSURE 42 PCF

COEFFICIENT OF FRICTION 0.3

5. SPECIAL LOADS

CHILLER UNIT 5044 LBS

1" = 1'-0"

BOLLARD DETAIL

GEOTECHNICAL NOTES:

1. ALL BACKFILL UNDER SLAB ON GRADE SHALL BE COMPACTED TO 95% MINIMUM

COMPACTION PER ASTM D-698.

2. A LAYER OF COARSE ROCK AGGREGATE 6" IN THICKNESS SHALL BE USED BELOW

THE SLAB IN ACCORDANCE WITH EARTHWORK SPECIFICATION.

Plan North True North

UP

UP

UP

UP

UP

UP

UP

UP

FE

FAP

FAP

FAP

DF

FEC

6" A.F.F.

6" A.F.F.

AP

RAD

RAD RAD RAD

RAD

RAD

RAD

RADRADRAD

AP

FLOOR ELEVATION

-10' - 1"

RAD

PHASE I

PIPE CHASE

Z001

MECH. RM.

CORRIDOR

H001

CORRIDOR

H002

ELEVATOR

MACHINE RM.

STAIRWELL NO. 2

S002

TOILET, UNISEX

TOILET, FEMALE

HAC

BREAK RM.

OFFICE

OFFICE, CHIEF

OFFICE

OFFICE

VENDING

H003

OFFICE

MECH. RM.

003A

MECH. RM.

OI&T

003B

ELEVATOR LOBBY

CHASE

CH-3-B

ELEVATOR

E1

AP

FEC

FAP

FEC FEC

FAP

FAP

FAP

RAD RAD

RAD

RADRAD

RADRAD

RADRADRAD

RADRAD

RADRAD

RADRADRADRADRAD

RADRAD

RAD

RAD

RAD RAD

RAD RAD RAD

RAD

RAD RAD

RAD

RAD

RAD

RAD

DN

RAD

PHASE III

PHASE II

OFFICE

OFFICE

OFFICE

FILE RM.

OFFICE

OFFICE

124 WORK RM.

STORAGE

TOILET, MALE

ELEVATOR LOBBY

TOILET, FEMALE

STAIRWELL NO. 2

S102

CORRIDOR

H102

CORRIDOR

H103

OI&T

OFFICE

CORRIDOR

H101

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

LIBRARY

CORRIDOR

H104

CONFERENCE RM.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

114 OFFICE

114A

OFFICE

BREAK RM.

115A

OFFICE, OPEN

OFFICE

OFFICE, CHIEF

113A

OFFICE

OFFICE

OFFICE

CORRIDOR

H105

CLOSET

115C

CLOSET

115B

ELEVATOR

E1

STAIRWELL NO. 3

S103

RECEPTION

STAIRWELL NO. 1

S101

CHASE

CH-1-1

Plan North True North KEYPLAN th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:3 :0

P

M

18-AL-101

ARCHITECTURAL LIFE SAFETY AND

PHASING PLAN

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

MVP SD Drawing # 4 of 77

3/32" = 1'-0"

FLOOR PLAN - BUILDING 18 - FLOOR 00

1 Plan North

True North

3/32" = 1'-0"

FLOOR PLAN - BUILDING 18 - FLOOR 01

2 Plan North

True North

CODE ANALYSIS - BUILDING 18

NOTE: THE CONSTRUCTION TYPE WAS DETERMINED FROM REVIEW OF THE ORIGINAL CONSTRUCTION DOCUMENTS DATED 3-26-1981 TITLED: RELOCATE ADMINISTRATION AND VISUAL INSPECTION BY THE DESIGN

TEAM.

PROJECT DESCRIPTION: REPLACEMENT OF MECHANICAL SYSTEM

BUILDING USE: OFFICE ADMINISTRATION

BUILDING CONSTRUCTION TYPE: TYPE V

BUILDING OCCUPANCY: GROUP B

OCCUPANCY SEPARATION: NOT REQUIRED

FIRE RESISTANCE: PER IBC 2018, TABLE 601

RATING REQUIREMENTS: TYPE II-B

STRUCTURAL FRAME 0 HR

BEARING WALLS

EXTERIOR 0 HR

INTERIOR 0HR

NON-BEARING WALLS

EXTERIOR <5'-0" 1 HR

5'-0" TO 10'-0" 1 HR

10'-0" TO 30'-0" 0 HR

> 30'-0" 0 HR

INTERIOR 0 HR

FLOOR CONSTRUCTION 0 HR

ROOF CONSTRUCTION 0 HR

RATED CORRIDORS: NOT REQUIRED

PLUMBING FIXTURE COUNT: THE HISTORIC NUMBER OF FIXTURES WILL BE MAINTAINED.

NO ADDITIONS OR DELETIONS.

APPLICABLE CURRENT CODES

2018 INTERNATIONAL BUILDING CODE (IBC)

2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC)

2018 INTERNATIONAL MECHANICAL CODE (IMC)

2018 INTERNATIONAL PLUMBING CODE (IPC)

NATIONAL FIRE PROTECTION ASSOCIATION STANDARDS (NFPA)

2020 NATIONAL ELECTRICAL CODE (NEC)

2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

2013 ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS

2005 ASME A17.3 SAFETY CODE FOR ELEVATORS AND ESCALATORS

2017 ICC / ANSI A117.1

2018 NFPA 101 LIFE SAFETY CODE

KEY NOTES:

PROVIDE CLASS II INFECTION CONTROL BARRIER FOR DUST CONTROL. PROVIDE 45-MINUTE RATED DOOR ASSEMBLY

IN TEMPORARY 1-HOUR RATED INFECTION CONTROL BARRIER.

2 NEW 6'-0" x 7'-0" WOOD DOOR IN HOLLOW METAL DOOR FRAME. MATCH EXISTING WOOD DOOR SPECIES AND

FINISH COLOR. PAINT HOLLOW METAL FRAME TO MATCH EXISTING.

ILSM - MAINTAIN THE ACCESS/EXIT POINTS FOR ANY OCCUPIED SPACE.3

AP

FAP

FEC

FAP

FEC

AP

FAP

FEC

RAD

RAD

RAD

RAD

RAD

RAD

RAD

RADRAD

RADRADRADRADRAD

RADRAD

RAD

RAD RAD

RAD RAD RAD RAD

RAD

RAD RAD

RAD RAD RAD RAD RAD

RAD

RAD

RAD

RAD

DN

RADRADRAD

PHASE V

PHASE IV

OFFICE

217C

OFFICE

217D

OFFICE

217E

OFFICE, SUPV.

HAC

OFFICE

215A

OFFICE

OFFICE

OFFICE

217A

OFFICE

217B

STAIRWELL NO. 1

S201

OFFICE

OFFICE

OFFICE

OFFICE

OI&T

ELEC. CLOSET

TOILET, MALE

TOILET, FEMALE

STAIRWELL NO. 2

S202

OFFICE

OFFICE

OFFICE, SUPV.

OFFICE, CHIEF

CORRIDOR

H203

CORRIDOR

H202

ELEVATOR LOBBY

CORRIDOR

H204

OFFICE

207A

OFFICE

207B

OFFICE

OFFICE

210B

OFFICE

210A

OFFICE

205A

CORRIDOR

H201

KITCHENETTE

212A

ELEVATOR

E1

CHASE

CH-2-1

STAIRWELL NO. 3

S203

AP

FAP

FAPFEC

FEC

FAP

RAD

RADRAD

RADRADRADRAD

RAD

RAD

RADRADRADRADRADRADRADRADRAD

RAD

RAD

RAD RAD

RAD RAD RAD RAD RAD

RAD

RAD

RAD

RADRAD

RAD

RAD

RAD

DN

RAD

RAD RAD RAD RAD

PHASE VII

PHASE VI

STAIRWELL NO. 1

S301

CREDENTIALS

SUPERVISOR

CREDENTIALS

OFFICE

TELEHEALTH

SUPERVISOR

KITCHEN

HAC

CORRIDOR

H302

CORRIDOR

H303

TOILET, MALE

ELEVATOR LOBBY

TOILET, FEMALE

STAIRWELL NO. 2

S302

OI&T

ELEC. CLOSET

CORRIDOR

H304

OFFICE

305A

OFFICE

CONFERENCE RM.

OFFICE

OFFICE

306A

OFFICE

OFFICE

BREAK RM.

OFFICE

OFFICE

311A

OFFICE

311E

OFFICE

OFFICE

311D

OFFICE

311B

OFFICE

311C

ELEVATOR

E1

CHASE

CH-3-1

VESTIBULE

H304A

STAIRWELL NO. 3

S303

TELEHEALTH

SUPPLIES

TELEHEALTH

WORKROOM

CORRIDOR

H301A

CORRIDOR

H301

CREDENTIALS

SUPPLIES

Plan North True North KEYPLAN th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:3 :1

P

M

18-AL-102

ARCHITECTURAL LIFE SAFETY AND

PHASING PLAN

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

MVP SD Drawing # 5 of 77

3/32" = 1'-0"

FLOOR PLAN - BUILDING 18 - FLOOR 02

Plan North True North

Plan North True North3/32" = 1'-0"

FLOOR PLAN - BUILDING 18 - FLOOR 03

CODE ANALYSIS - BUILDING 18

NOTE: THE CONSTRUCTION TYPE WAS DETERMINED FROM REVIEW OF THE ORIGINAL CONSTRUCTION DOCUMENTS DATED 3-26-1981 TITLED: RELOCATE ADMINISTRATION AND VISUAL INSPECTION BY THE DESIGN

TEAM.

PROJECT DESCRIPTION: REPLACEMENT OF MECHANICAL SYSTEM

BUILDING USE: OFFICE ADMINISTRATION

BUILDING CONSTRUCTION TYPE: TYPE V

BUILDING OCCUPANCY: GROUP B

OCCUPANCY SEPARATION: NOT REQUIRED

FIRE RESISTANCE: PER IBC 2018, TABLE 601

RATING REQUIREMENTS: TYPE II-B

STRUCTURAL FRAME 0 HR

BEARING WALLS

EXTERIOR 0 HR

INTERIOR 0HR

NON-BEARING WALLS

EXTERIOR <5'-0" 1 HR

5'-0" TO 10'-0" 1 HR

10'-0" TO 30'-0" 0 HR

> 30'-0" 0 HR

INTERIOR 0 HR

FLOOR CONSTRUCTION 0 HR

ROOF CONSTRUCTION 0 HR

RATED CORRIDORS: NOT REQUIRED

PLUMBING FIXTURE COUNT: THE HISTORIC NUMBER OF FIXTURES WILL BE MAINTAINED. NO ADDITIONS

OR DELETIONS.

APPLICABLE CURRENT CODES

2018 INTERNATIONAL BUILDING CODE (IBC)

2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC)

2018 INTERNATIONAL MECHANICAL CODE (IMC)

2018 INTERNATIONAL PLUMBING CODE (IPC)

NATIONAL FIRE PROTECTION ASSOCIATION STANDARDS (NFPA)

2020 NATIONAL ELECTRICAL CODE (NEC)

2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

2013 ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS

2005 ASME A17.3 SAFETY CODE FOR ELEVATORS AND ESCALATORS

2017 ICC / ANSI A117.1

2018 NFPA 101 LIFE SAFETY CODE

KEY NOTES:

PROVIDE ICRA BARRIER FOR THE DUST CONTROL.

ILSM - MMAIINTAIN THE ACCESS/EXIT POINTS FOR ANY COCCUPIED SPACE.2

FAP

FAP

FE

FE

FE

FAP

FE

FE

FE

FAP

LOADING DOCK

FAP

FAP

Plan North

True North

KEYPLAN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

02/10/2020

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

657-19-103JB

/1

/2

:3 :0

P

M

60-AL-101

ARCHITECTURAL LIFE SAFETY AND

PHASING PLAN

FCA - REPLACE MEHCANICAL

SYSTEMS BLDG 18 & 60

MVP SD

Drawing # 6 of 77

1/8" = 1'-0"

OVERALL FLOOR PLAN - BUILDING 60 - FLOOR 01

CODE ANALYSIS - BUILDING 60

NOTE: THE CONSTRUCTION TYPE WAS DETERMINED FROM REVIEW OF THE ORIGINAL CONSTRUCTION DOCUMENTS DATED 9-07-1950. SPRINKLER DRAWINGS ARE DATED 9-07-1962 AND REVISED IN APRIL 1969.

PROJECT DESCRIPTION: REPLACEMENT OF MECHANICAL SYSTEM

BUILDING USE: COMMERCIAL KITCHEN

BUILDING CONSTRUCTION TYPE: TYPE V

BUILDING OCCUPANCY: F-2 COMMERCIAL KITCHEN

OCCUPANCY SEPARATION: NOT REQUIRED

FIRE RESISTANCE: PER IBC 2018, TABLE 601

RATING REQUIREMENTS: TYPE V-B

STRUCTURAL FRAME 0 HR

BEARING WALLS

EXTERIOR 0 HR

INTERIOR 0HR

NON-BEARING WALLS

EXTERIOR <5'-0" 1 HR

5'-0" TO 10'-0" 1 HR

10'-0" TO 30'-0" 0 HR

> 30'-0" 0 HR

INTERIOR 0 HR

FLOOR CONSTRUCTION 0 HR

ROOF CONSTRUCTION 0 HR

RATED CORRIDORS: NOT REQUIRED

PLUMBING FIXTURE COUNT: THE HISTORIC NUMBER OF FIXTURES WILL BE MAINTAINED. NO ADDITIONS

OR DELETIONS.

APPLICABLE CURRENT CODES

2018 INTERNATIONAL BUILDING CODE (IBC)

2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC)

2018 INTERNATIONAL MECHANICAL CODE (IMC)

2018 INTERNATIONAL PLUMBING CODE (IPC)

NATIONAL FIRE PROTECTION ASSOCIATION STANDARDS (NFPA)

2020 NATIONAL ELECTRICAL CODE (NEC)

2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

2013 ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS

2005 ASME A17.3 SAFETY CODE FOR ELEVATORS AND ESCALATORS

2017 ICC / ANSI A117.1

2018 NFPA 101 LIFE SAFETY CODE

Plan North

True North

KEYNOTES:

PROVIDE ICRA BARRIER FOR DUST CONTROL.

KITCHEN EXHAUST SYSTEM TO BE REMOVED AND REPLACED.

IISLM - MAINTAIN THE ACCESS/EXITT POINTS FOR ANY OCCUPIED SPACE.

10' - 9"

7' - 10"

9' - 6"

7' - 11"

7' - 11"

10' - 9"

8' - 0"

8' - 0"

7' - 11" 8' - 0"

8' - 0"

7' - 8"

9' - 1"

9' - 0"8' - 0"

9' - 8" 9' - 8"

9' - 0"

9' - 6"

9' - 6" 8' - 0"

8' - 0"

9' - 4" 9' - 4"

9' - 4"9' - 4"

10' - 9"

10' - 9"

PIPE CHASE

Z001

MECH. RM.

CORRIDOR

H001

CORRIDOR

H002

ELEVATOR

MACHINE RM.

STAIRWELL NO. 2

S002

TOILET, UNISEX

TOILET, FEMALE

HAC

BREAK RM.

OFFICE

OFFICE, CHIEF

OFFICE

OFFICE

VENDING

H003

OFFICE

MECH. RM.

003AMECH. RM.

OI&T

003B

ELEVATOR LOBBY

CHASE

CH-1-B

CHASE

CH-2-B

CHASE

CH-3-B

CHASE

CH-4-B

ELEVATOR

E1

Plan North True North KEYPLAN th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:3 :5

P

M

18-AD-101

ARCHITECTURAL DEMOLITION

REFLECTED CEILING PLAN - FLOOR 00

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

MVP SD Drawing # 7 of 77

1/8" = 1'-0"

ARCHITECTURAL DEMOLITION REFLECTED CEILING PLAN - BUILDING 18 - FLOOR 00

Plan North True North

DEMOLITION KEY NOTES:

REMOVE CEILING TILE GRID, DEVICES AND EQUIPMENT IN THIS AREA TO

INSTALL MECHANICAL DUCT WORK AND RELATED DIFFUSERS. REPLACE TILE

CEILING, TILE GRID AND ALL DEVICES. REPLACE ANY DAMAGED TILE GRID, OR

LIGHT FIXTURES WITH LIKE KIND IF DAMAGED.

8' - 10" 8' - 10"

8' - 10"

7' - 6" 7' - 9"

10' - 7"

8' - 11"

7' - 9"

8' - 10"8' - 10"8' - 10"

7' - 8 3/4"

8' - 2"

8' - 0"

7' - 7" 9' - 0" 9' - 0" 7' - 10"

9' - 0"

9' - 0"

9' - 0" 9' - 0"

9' - 0" 9' - 0"

7' - 11"

9' - 0" 9' - 0" 9' - 0"

8' - 9"

7' - 2"

7' - 8"

8' - 10"

8' - 10"

8' - 10"

10' - 4"

9' - 0"

10' - 3"

7' - 11"

9' - 0"

7' - 11"

9' - 0"

7' - 11"

9' - 0"

7' - 11"

8' - 9"

9' - 0"

9' - 0"

7' - 11"7' - 11"

9' - 0"

9' - 0"

9' - 0"

8' - 8"

7' - 6"

7' - 2"

7' - 11"

7' - 1" 7' - 6"

9' - 0" 9' - 0"

9' - 0"

9' - 0"

8' - 0"

9' - 2"

8' - 0"

9' - 2"

8' - 0"

9' - 2"

8' - 0"

7' - 10"

8' - 10"

7' - 10"

8' - 10" 8' - 10"

7' - 10" 7' - 10"

8' - 10"

7' - 10"

8' - 10" 8' - 6"

8' - 0"

8' - 11"

7' - 5"

7' - 4"

8' - 6"

8' - 6"

7' - 11"7' - 11"

8' - 9"

7' - 11"

8' - 9"

7' - 11"

8' - 9"

7' - 11"

8' - 9" 8' - 9"

7' - 11"

AP

7' - 2"7' - 5"

10' - 4"

9' - 8"

9' - 8"

10' - 3" 9' - 8"

8' - 8" 8' - 8"

10' - 8"

8' - 0"

OFFICE

OFFICE

OFFICE

FILE RM.

OFFICE

OFFICE

WORK RM.

STORAGE

TOILET, MALE

ELEVATOR LOBBY

TOILET, FEMALE

STAIRWELL NO. 2

S102

CORRIDOR

H102

CORRIDOR

H103

OI&T

OFFICE

CORRIDOR

H101

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

LIBRARY

CORRIDOR

H104

CONFERENCE RM.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

114A

OFFICE

BREAK RM.

115A

OFFICE, OPEN

OFFICE

OFFICE, CHIEF

113A

OFFICE

OFFICE

OFFICE

CORRIDOR

H105

CLOSET

115C

CLOSET

115B

ELEVATOR

E1

CHASE

CH-1-1

CHASE

STAIRWELL NO. 3

S103

RECEPTION

STAIRWELL NO. 1

S101

Plan North True North KEYPLAN th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:3 :0

P

M

18-AD-111

ARCHITECTURAL DEMOLITION

REFLECTED CEILING PLAN - FLOOR 01

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

MVP SD Drawing # 8 of 77

1/8" = 1'-0"

ARCHITECTURAL DEMOLITION REFLECTED CEILING PLAN - BUILDING 18 - FLOOR 01

1 Plan North

True North

DEMOLITION KEY NOTES:

REMOVE CEILING TILE GRID, DEVICES AND EQUIPMENT IN THIS AREA TO

INSTALL MECHANICAL DUCT WORK AND RELATED DIFFUSERS. REPLACE TILE

CEILING, TILE GRID AND ALL DEVICES. REPLACE ANY DAMAGED TILE GRID, OR

LIGHT FIXTURES WITH LIKE KIND IF DAMAGED.

8' - 0"

7' - 5"

10' - 3"

7' - 6"

7' - 5"

7' - 6"

7' - 9 1/2"

8' - 0"

8' - 0"

8' - 0"

9' - 9"

7' - 5"

7' - 6"

7' - 6"

8' - 8"

8' - 1 3/8" 8' - 1"

7' - 5"

8' - 1" 8' - 2" 8' - 2"

8' - 2"

8' - 2"

8' - 2"8' - 2"

7' - 6"

7' - 6"

8' - 2"

7' - 6"

8' - 2"

8' - 2"

8' - 1"

8' - 0"

7' - 6"

8' - 3" 8' - 3"

8' - 3"

8' - 3"

8' - 3" 8' - 3" 8' - 3" 8' - 3" 7' - 9 1/2"

7' - 8"

OFFICE

217C

OFFICE

217D

OFFICE

217E

OFFICE, SUPV.

HAC

OFFICE

215A

OFFICE

OFFICE

OFFICE

217A

OFFICE

217B

STAIRWELL NO. 1

S201

OFFICE

OFFICE

OFFICE

OFFICE

OI&T

ELEC. CLOSET

TOILET, MALE

TOILET, FEMALE

STAIRWELL NO. 2

S202

OFFICE

OFFICE

OFFICE, SUPV.

OFFICE, CHIEF

CORRIDOR

H203

CORRIDOR

H202

ELEVATOR LOBBY

CORRIDOR

H204

OFFICE

207A

OFFICE

207B

OFFICE

OFFICE

210B

OFFICE

210A

OFFICE

205A

CORRIDOR

H201

KITCHENETTE

212A

ELEVATOR

E1

CHASE

CH-2-1

STAIRWELL NO. 3

S203

Plan North True North KEYPLAN th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:3 :0

P

M

18-AD-121

ARCHITECTURAL DEMOLITION

REFLECTED CEILING PLAN - FLOOR 02

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

MVP SD Drawing # 9 of 77

Plan North True North1/8" = 1'-0"

ARCHITECTURAL DEMOLITION REFLECTED CEILING PLAN - BUILDING 18 - FLOOR 02

DEMOLITION KEY NOTES:

REMOVE CEILING TILE GRID, DEVICES AND EQUIPMENT IN THIS AREA TO

INSTALL MECHANICAL DUCT WORK AND RELATED DIFFUSERS. REPLACE TILE

CEILING, TILE GRID AND ALL DEVICES. REPLACE ANY DAMAGED TILE GRID, OR

LIGHT FIXTURES WITH LIKE KIND IF DAMAGED.

8' - 0"

7' - 8 1/2"

7' - 9 3/4"

7' - 8 1/4"

10' - 3"

8' - 0"

8' - 0" 7' - 9" 8' - 3"

8' - 0"

8' - 0"

7' - 9"

8' - 0" 9' - 11"

7' - 8 3/4"

8' - 2"

8' - 0"

7' - 5"

8' - 0"

8' - 2"

7' - 9"

7' - 9"

7' - 9"

8' - 0"

8' - 8"

9' - 1"

8' - 1"

7' - 10"

8' - 6"8' - 6"8' - 6"

8' - 2"

7' - 8"

7' - 9"

8' - 6"

7' - 9"

8' - 2"

7' - 10"

8' - 6"

9' - 11"

ROOF

HATCH

8' - 0"

8' - 0"

7' - 6"

8' - 6"

7' - 7 1/4"

STAIRWELL NO. 1

S301

CREDENTIALS

SUPERVISOR

CREDENTIALS

OFFICE

TELEHEALTH

SUPERVISOR

KITCHEN

HAC

CORRIDOR

H302

CORRIDOR

H303

TOILET, MALE

ELEVATOR LOBBY

TOILET, FEMALE

STAIRWELL NO. 2

S302

OI&T

ELEC. CLOSET

CORRIDOR

H304

OFFICE

305A

OFFICE

CONFERENCE RM.

OFFICE

OFFICE

306A

OFFICE

OFFICE

BREAK RM.

OFFICE

OFFICE

311A

OFFICE

311E

OFFICE

OFFICE

311D

OFFICE

311B

OFFICE

311C

ELEVATOR

E1

CHASE

CH-3-1

VESTIBULE

H304A

STAIRWELL NO. 3

S303

TELEHEALTH

SUPPLIES

TELEHEALTH

WORKROOM

CORRIDOR

H301A

CORRIDOR

H301

CREDENTIALS

SUPPLIES

Plan North True North KEYPLAN th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:3 :0

P

M

18-AD-131

ARCHITECTURAL DEMOLITION

REFLECTED CEILING PLAN - FLOOR 03

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

MVP SD Drawing # 10 of 77

Plan North True North1/8" = 1'-0"

ARCHITECTURAL DEMOLITION REFLECTED CEILING PLAN - BUILDING 18 - FLOOR 03

DEMOLITION KEY NOTES:

REMOVE CEILING TILE GRID, DEVICES AND EQUIPMENT IN THIS AREA TO

INSTALL MECHANICAL DUCT WORK AND RELATED DIFFUSERS. REPLACE TILE

CEILING, TILE GRID AND ALL DEVICES. REPLACE ANY DAMAGED TILE GRID, OR

LIGHT FIXTURES WITH LIKE KIND IF DAMAGED.

S M

11' - 3"

9' - 5"

8' - 6"

11' - 10"

8' - 5"

14' - 9"

11' - 10"

9' - 5"

11' - 2"

9' - 5"

11' - 1 1/2"

9' - 6"

7' - 11"

7' - 11"

9' - 4"

9' - 5"

8' - 5"

9' - 6"

7' - 11"

9' - 0"

8' - 5"

7' - 9"

8' - 3"

8' - 3"

9' - 8"

9' - 2"

9' - 6"

8' - 2"

9' - 5"

7' - 4"

8' - 5"

8' - 0" 7' - 10"

9' - 1"

8' - 2"

9' - 8"

11' - 10"

10' - 4" 9' - 6"

9' - 0"

19' - 1 1/4" 16' - 2 1/4"

8' - 0"

7' - 8"

7' - 6"

7' - 6"

7' - 8"

16' - 6" 14' - 1"

11' - 10" 9' - 0 1/4"

8' - 5"

9' - 0"

11' - 1 1/2"

12' - 11 1/4"

Plan North

True North

KEYPLAN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

02/10/2020

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

657-19-103JB

/1

/2

:3 :5

P

M

60-AC-101

ARCHITECTURAL REFLECTED CEILING

PLAN - FLOOR 01

FCA - REPLACE MEHCANICAL

SYSTEMS BLDG 18 & 60

MVP SD

Drawing # 11 of 77

Plan North

True North

1/8" = 1'-0"

OVERALL CEILING PLAN - BUILDING 60 - FLOOR 01

KEYNOTES:

PROVIDE ICRA BARRIER FOR DUST CONTROL.

KITCHEN EXHAUST SYSTEM TO BE REMOVED AND REPLACED.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:1 :5

A

M

00-MG-001

MECHANICAL ABBREVIATIONS AND

GENERAL NOTES

18 & 60

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

DD RT Drawing # 12 of 77

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SV STEAM PRESSURE REDUCING VALVE

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE

TAB TESTING, ADJUSTING, AND BALANCING

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TR TOP REGISTER

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

UCT UNDERCUT

UC UNIT COOLER

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

URV UPBLAST UNIT VENTILATOR

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

W WASTE

WAG WASTE ANESTHESIA GAS

WB WET BULB

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCPU WATER COOLED HEAT PUMPS

WEF WATER COOLED PACKAGED UNIT

WF WATER FILTER

WFCV WATER FLOW CONTROL VALVE

WFM WATER FLOWMETER

WFMD WATER FLOW MEASURING DEVICE

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

YR YEAR

OFM OIL FLOWMETER

OR OPERATING ROOM

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT

PD PRESSURE DROP

PEF PROPELLER TYPE EXHAUST FAN

PF PRE-FILTER

PG PRESSURE GAUGE

PGW PROPYLENE GLYCOL-WATER SOLUTION

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING VALVE STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH, ABSOLUTE

PSIG POUNDS PER SQUARE INCH, GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

RDS ROOM DATA SHEETS

REA RELIEF AIR

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SD-1 SCHEMATIC DESIGN SUBMISSION 1

SD-2 SCHEMATIC DESIGN SUBMISSION 2

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND DISTRIBUTION

SPRV STEAM PRESSURE REDUCING VALVE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

KG KILOGRAM

KG/H KILOGRAMS PER HOUR

KPA KILOPASCAL

KW KILOWATT

KWH KILOWATT HOURS

L LITER

L/H LITERS PER HOUR

L/M LITERS PER MINUTE

L/S LITERS PER SECOND

LAT LEAVING AIR TEMPERATURE

LB/H POUND PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPG LIQUID PROPANE GAS

LPR LOW PRESSURE RETURN (STEAM

CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN (CLEAN)

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M METER

M/S METERS PER SECOND

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN (STEAM

CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MRI MAGNETIC RESONANCE IMAGING UNIT

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NG NATURAL GAS

NGFM NATURAL GAS FLOW METER

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OD OUTER DIAMETER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOHX FUEL OIL HEAT EXCHANGER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FR FLOOR REGISTER

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FINNED TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

H HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN (STEAM

CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVD HOISTWAY VENT DAMPER

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING WATER PUMP

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ICU INTENSIVE CARE UNIT

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCHES OF WATER COLUMN

IN WG INCHES OF WATER, GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

CP CONDENSATE PUMP

CR CEILING REGISTER

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CWCC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN (TO COOLING

TOWER)

CWS CONDENSER WATER SUPPLY (FROM COOLING

TOWER)

D DAMPER - AUTOMATIC

D-1 OUTDOOR AIR DAMPER

D-2 RETURN AIR DAMPER

D-3 RELIEF AIR DAMPER

Db DRY BULB TEMPERATURE dB DECIBEL

DD-1 DESIGN DEVELOPMENT SUBMISSION 1

DD-2 DESIGN DEVELOPMENT SUBMISSION 2

DDC DIRECT DIGITAL CONTROLS

DEG DEGREES

DF DIFFUSER

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DP DIFFUSER PLATE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AAV AUTOMATIC AIR VENT

AB AIR BLENDER

ACC AIR COOLED CONDENSER

ACCH AIR COOLED CHILLER

ACCU AIR-COOLED CONDENSING UNIT

ACD AUTOMATIC CONTROL DAMPER, MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER, TWO POSITION

ACFM ACTUAL CUBIC FEET PER MINUTE

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMD AIR FLOW MEASURING DEVICE

AFW AIR FOIL WHEEL (FAN)

AHU AIR HANDLING UNIT

AMP AMPERE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BR BOTTOM REGISTER

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTC BLOWOFF TANK CONTROL VALVE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWT BOILER PLANT WATER TUBE

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION 1)

CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION 2)

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFP CHEMICAL FEED PUMP

CFT CUBIC FEET

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CHW CHILLED WATER

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

BAS BUILDING AUTOMATION SYSTEMS

MECHANICAL ABBREVIATIONS

1. CONTRACTOR SHALL PROVIDE AN INFECTION CONTROL RISK ASSESSMENT BARRIER AROUND

THE PROJECT AREA CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY

THE VA.

SEE SPECIFICATION SECTION 01 00 00 PART 1.2 - F FOR WORK HOURS.

HVAC GENERAL NOTES

MECHANICAL ASCE 7 NONSTRUCTURAL

SEISMIC RESTRAINT AND ANCHORAGE NOTES:

GENERAL NOTES

2.

REFERENCE SPECIFICATION: SECTION 13 05 41

SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS

SEISMIC DESIGN DATA FOR ANALYSIS AND DESIGN

SEISMIC RISK CATEGORY = IV

COMPONENT IMPORTANCE FACTOR IP = 1.50 (ASCE 7-10 TABLE 1.5-2)

MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:

SS=0.447G S1=0.171G

SITE CLASS D (ASSUMED)

DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:

SDS=0.443G SD1=0.241G

SEISMIC DESIGN CATEGORY D BASED UPON SD1 > 0.20G

CLARIFICATION OF ASCE 7 "12 INCH RULE" SUSPENDED SEISMIC BRACING CODE EXCEPTION FOR PIPING

AND HVAC DUCTWORK:

ALL PIPING SUSPENDED BY INDIVIDUAL HANGAR RODS 12" OR LESS AS MEASURED FROM THE TOP OF THE PIPE TO THE BOTTOM OF THE SUPPORT WHERE THE HANGER IS ATTACHED. IF THE 12" LIMIT IS EXCEEDED BY ANY HANGER IN THE RUN, SEISMIC BRACING IS REQUIRED FOR THE RUN. NOTE: A SINGLE SUPPORT LOCATION THAT MEETS THE REQUIREMENT OF THIS EXCEPTION DOES NOT CONSTITUTE A SEISMIC SWAY

BRACE LOCATION.

THE EXCEPTION ALSO APPLIES FOR TRAPEZE SUPPORTED SYSTEMS IF THE DISTANCE AS MEASURED FROM THE POINT OF ATTACHMENT TO THE TRAPEZE TO THE POINT OF ATTACHMENT TO THE STRUCTURE IS LESS THAN 12". NOTE: IF DIRECTIONAL CHANGES OR OFFSETS TO EQUIPMENT CONNECTIONS DO NOT ALLOW FOR FLEXIBILITY OF THE TRAPEZED SYSTEM (E.G. LONG OFFSETS OR FLEXIBLE CONNECTORS) THEN THE SYSTEM MUST BE BRACED REGARDLESS OF PIPE DIAMETER OR DISTANCE TO THE STRUCTURE IF THE

COMBINED WEIGHT PER FOOT (METER) OF ALL ITEMS IS GREATER THAN 10 LBS/FT.

IN ADDITION, TO MEET THE CODE REQUIREMENTS, ALL OF THE FOLLOWING CONDITIONS MUST ALSO BE

SATISFIED:

1. LATERAL MOTION OF PIPING OR DUCTWORK WILL NOT CAUSE DAMAGING IMPACT WITH

SURROUNDING SYSTEMS (E.G. OTHER PIPE, DUCT, EQUIPMENT, SPRINKLER HEADS ETC.) OR CAUSE

LOSS OF SYSTEM VERTICAL SUPPORT.

2. PIPING MUST BE MADE OF DUCTILE MATERIAL WITH DUCTILE CONNECTIONS (E.G. WELDED STEEL

PIPE, BRAZED COPPER PIPE, ETC.)

3. VERTICAL SUPPORT CONNECTIONS CANNOT DEVELOP MOMENTS (E.G. SWIVEL JOINTS, EYE BOLTS, VIBRATION INSULATION HANGERS, ETC.)

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED

IN A FURRED CHASE OR ABOVE THE CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR

INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL

VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS

SHALL BE FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL

SPECIFICATIONS.

4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM,

TERMINAL UNITS, FILTERS, COILS, ETC.

5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE

EQUIPMENT DETAILS.

6. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK

SIZES.

7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE

MADE TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE

INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE FINISHED

FLOOR.

9. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE

10. ALL CONTROL SYSTEM EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING

BUILDING MANAGEMENT SYSTEM CONTROLS. EXTEND EXISTING CONTROL

SYSTEM TO INCLUDE ALL OF THE CONTROLS AND SEQUENCES SHOWN.

11. COORDINATE EXISTING FIRE SPRINKLER HEADS AND LIGHTS WITH DIFFUSERS.

12. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS FOR

ALL NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME AREAS.

DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING UNTIL

COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS: 657-19-103JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.7

100% CONTRACT DOCUMENT SUBMITTAL DRAWINGS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

02/10/2020

/1

/2

:1 :5

A

M

00-MG-002

MECHANICAL SYMBOLS

18 & 60

FCA - REPLACE MECHANICAL

SYSTEMS IN BUILDING 18 & 60

DD BT Drawing # 13 of 77

T

TT

M

MT

PT

TT

FT

IT

CT

SPS

SD

PDT

KR

TSL

HS

ZC

LC

LT

PDS

TSH

EPT

AT

CO2

AT

CO

AT

OC

LTCP

HVAC

ECC

TC

VSMC

PC

SC

FC

PSH

FSH

PSL

26-SF 3

26-TU-I-I

H4

H7

A

BDD

FD

VD

SUPPLY

RETURN45°

45°

N

2 1

1/24

F/S DPR

FE

AV

MV

RH

SCH

SH

TH

PS

RC

WB

CSH

SS

VR

CTPS

CTPD

FWPS

FWPD

CF

FWS

BWS

CBD

BO

TC

A

OFL

HW

SW

CW

FOR

FOS

LPG(I)

G(I)

G

HPS

HPR

MPS

MPR

LPS

LPR

PC

HWS

HWR

GHS

GHR

V

SWS

SWR

CWR

CHR

GCR

RL

RS

RHG

CWS

CHS

GCS

MW

D

GRR

GRS

X

A

PTAC

A TWU

A

FCU

FCU

A

PTACA

MB

KC

FSL

A

M

BAS

DN

DN

UP

UP

D

R

DNUP

FC

10x8

LC

M

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

SUPPLY FAN NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (SUPPLY FAN)

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT SHOWN)

SERVED BY AIR HANDLER UNIT NO. 1

DRAWING NUMBER WHERE DRAWN

BUILDING NO. WHERE EQUIPMENT IS LOCATED

* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY STANDARD PRACTICE SP-58

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

MANUAL AIR VENT

QUICK-COUPLE HOSE CONNECTOR

CONNECT TO EXISTING

LIMIT OF DEMOLITION

AIR SEPERATOR

TERMINAL UNIT WITH REHEAT COIL

DOUBLE DUCT MIXING BOX.

FAN POWERED VARIABLE VOLUME

TERMINAL UNIT WITH HEATING COIL.

EXISTING DUCT TO BE REMOVED

LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL

SECTION.)

FLEXIBLE DUCTWORK (INSULATED)

DUCT WITH SOUND LINING

MANUAL VOLUME DAMPER

FIRE DAMPER

BACK DRAFT DAMPER

COMBINATION FIRE/SMOKE DAMPER

POINT OF CHANGE IN DUCT CONSTRUCTION BY

STATIC PRESSURE CLASS. THE NUMBER ASSIGNS

PRESSURE CLASS (IN. OF WATER) WHICH WILL

ACCOMMODATE MAXIMUM OPERATING PRESSURE

IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES

THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR

ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT

INDICATES NEGATIVE PRESSURE.

AUTOMATIC CONTROL DAMPER MODULATING

AUTOMATIC CONTROL DAMPER TWO POSITION

MANUAL SPLITTER DAMPER

STANDARD BRANCH SUPPLY OR RETURN, NO

SPLITTER (45° TAP)

DUCT MOUNTED COIL (HOT WATER OR STEAM

COIL)

DUCT MOUNTED COIL (ELECTRIC)

CONVECTOR OR RADIATOR (RECESSED)

CONVECTOR OR RADIATOR (WALL HUNG)

FLOOR MOUNTED VERTICAL RECESSED FAN COIL UNIT.

LETTER INDICATES UNITSIZE.

FLOOR MOUNTED VERTICAL CABINET FAN

COIL UNIT. LETTER INDICATES UNIT SIZE.

THRU WALL AIR CONDITIONING UNIT.

LETTER INDICATES UNIT SIZE.

WINDOW TYPE AIR CONDITIONING UNIT.

LETTER INDICATES UNIT SIZE.

FLOOR MOUNTED HEAT PUMP. LETTER

INDICATES UNIT SIZE.

AIR CURTAIN

UNIT HEATER (HORIZONTAL)

UNIT HEATER (VERTICAL)

2'x2' RADIANT CEILING PANEL

2'x4' RADIANT CEILING PANEL

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

RETURN DUCT (UP & DOWN)

ROUND AND SQUARE 4-WAY CEILING DIFFUSERS

SQUARE 3-WAY CEILING DIFFUSERS

SQUARE 2-WAY CEILING DIFFUSERS

SQUARE 1-WAY CEILING DIFFUSERS

LINEAR SLOT DIFFUSER

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING

REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM

REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN REGISTER OR TOP GRILLE

(WALL TYPE)

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

CONNECT NEW DUCT TO EXISTING DUCT

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

LIMIT OF DEMOLITION

FLEXIBLE CONNECTION, EQUIPMENT, VIBRATION,

OR SEISMIC

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS):

WIDTH x DEPTH (RECTANGULAR)

WIDTH / DEPTH (FLAT OVAL)

EXISTING DUCT TO REMAIN

GATE VALVE - THREADED/FLANGED

GLOBE VALVE - THREADED/FLANGED

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE

FLEXIBLE CONNECTION

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

MODULATING CONTROL VALVE

MODULATING CONTROL BUTTERFLY VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

THREE-WAY TWO POSITION CONTROL VALVE

PRESSURE REGULATING VALVE

PRESSURE SAFETY VALVE

AUTOMATIC BALANCING CONTROL VALVE

WATER BALANCE DEVICE

CIRCUIT SETTER VALVE

GATE VALVE WITH GLOBE-VALVED BYPASS

PLUG VALVE

CONTROL VALVE (CV) - FLOAT-OPERATED

PRESSURE REDUCING VALVE (PRV)

WATER LEVEL CONTROLLER

FLOW METER

ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT

ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL

MOUNT

TEMPERATURE TRANSMITTER

TEMPERATURE TRANSMITTER, AVERAGING ELEMENT

MOISTURE (HUMIDITY) TRANSMITTER

PRESSURE TRANSMITTER

STATIC PRESSURE SENSOR

FLOW TRANSMITTER

CURRENT TRANSMITTER

CONDUCTIVITY TRANSMITTER

S…