John Cochran VA
| Medical Gas Equipment Inventory | |
| John Cochran VA |
MASTER ALARM PANELS ZONE VALVE BOXES
| LOCATION: 1 | PLB SHOP | ||
| LOCATION: 2 | C106 | TOTAL NUMBER OF BOXES | 63 |
| SWITCHES: | VALVES | ||
| OXYGEN | 12 | OXYGEN | 67 |
| MEDICAL AIR | 24 | MEDICAL AIR | 59 |
| MED VACUUM | 12 | MED VACUUM | 62 |
| EVACUATION | 0 | EVACUATION | 6 |
| NITROUS OXIDE | 6 | NITROUS OXIDE | 17 |
| NITROGEN | 6 | NITROGEN | 17 |
| CARBON DIOXIDE | 6 | CARBON DIOXIDE | 4 |
| HELIUM | 0 | HELIUM | 0 |
TOTAL SWITCHES 66 TOTAL VALVES 232
AREA ALARM PANELS PATIENT TERMINALS
TOTAL NUMBER OF PANELS 70 MEDICAL GAS TERMINALS
| ALARM POINTS: | GASES: | ||
| OXYGEN | 54 | OXYGEN | 573 |
| MEDICAL AIR | 48 | MEDICAL AIR | 291 |
| MED VACUUM | 52 | MED VACUUM | 572 |
| EVACUATION | 1 | EVACUATION | 7 |
| NITROUS OXIDE | 16 | NITROUS OXIDE | 41 |
| NITROGEN | 10 | NITROGEN | 12 |
| CARBON DIOXIDE | 1 | CARBON DIOXIDE | 3 |
| HELIUM | 0 | HELIUM | 0 |
TOTAL ALARM POINTS 182 TOTAL TERMINAL COUNT 1499
John Cochran VA equipment
| Liquid Cryogenic Oxygen Evaluation Inspection Record | ||||||
| Oxygen Tanks outside by Bell Street | ||||||
| January 10, 2020 | ||||||
| Manifold Type | Liq x Liq | Liq x Cry | Liq x HP | Liq x Liq w HP | Liq x Cry w HP |
Manufacturer: LINDE Location: REAR OF FACILITY
Main Tank Liq: 100 Main Tank PSI: 120 Secondary Tank Liq: 92 Secondary Tank PSI: 140
| Main Line Pressure: | 52 | Cyl x Cyl: | N/A | |||
| High Pressure Manifold Evaluation Inspection Record | ||||||
| N2O Room A445 | ||||||
| Manifold Gas: | Oxy | Med Air | N2O | NG | CO2 |
Manifold Type: HP X HP CRY X CRY CRY X HP CRY x CRY w HP
Manufacturer: OHIO Location: A445
Left Bank: 713 Right Bank: 292 Line Pressure 50 Reserve Header: N/A
Main Line Pressure: 152 Cyl x Cyl: 6X6
| High Pressure Manifold Evaluation Inspection Record | ||||||
| CO2 Room A445 | ||||||
| Manifold Gas: | Oxy | Med Air | N2O | NG | CO2 |
Manifold Type: HP X HP CRY X CRY CRY X HP CRY x CRY w HP
Manufacturer: OHIO Location: A445
Left Bank: 819 Right Bank: 942 Line Pressure 43 Reserve Header: N/A
Main Line Pressure: 44 Cyl x Cyl: 6X6
| High Pressure Manifold Evaluation Inspection Record | ||||||
| Nitrogen room A455 | ||||||
| Manifold Gas: | Oxy | Med Air | N2O | NG | CO2 |
Manifold Type: HP X HP CRY X CRY CRY X HP CRY x CRY w HP
Manufacturer: OHIO Location: A445
Left Bank: 924 Right Bank: 2269 Line Pressure 151 Reserve Header: N/A
| Main Line Pressure: | 151 | Cyl x Cyl: | 6X6 | |||
| Medical Air Compressor Evaluation Inspection Record | ||||||
| MAC-1 Pipe Basement | ||||||
| Configuration: | Simplex | Duplex | Triplex | Quadruplex | Other |
Compressor Type: Scroll Liquid Ring Reciprocating
Compressor Mount: Base Tank Frame
Manufacturer: POWEREX Model: MPD150425
Location: B018
| Unit: | HP | Hour Meter | Comp Serial # | Manufacturer | ||||
| 1 | 15 | 3561 | N/A | HITACHI | ||||
| 2 | 15 | 3538 | N/A | HITACHI | ||||
| Medical Air Compressor Evaluation Inspection Record | ||||||||
| MAC-2 room D302 | ||||||||
| Configuration: | Simplex | Duplex | Triplex | Quadruplex | Other |
Compressor Type: Scroll Liquid Ring Reciprocating
Compressor Mount: Base Tank Frame
Manufacturer: POWEREX Model: MPD150445
Location: D302
| Unit: | HP | Hour Meter | Comp Serial # | Manufacturer | ||||
| 1 | 15 | 5923 | N/A | HITACHI | ||||
| 2 | 15 | 4330 | N/A | HITACHI | ||||
| Medical Vacuum Pump Evaluation Inspection Record | ||||||||
| Medical VAC Pipe Basement | ||||||||
| Configuration: | Simplex | Duplex | Triplex | Quadruplex | Other |
Vacuum Type: Claw Liquid Ring Rotary Vane Oil Free Rotary Vane
Vacuum Mount: Base Tank Frame
Manufacturer: POWETREX Model: VOPD15052INT
Location: B018
| Unit: | HP | Hour Meter | Pump Serial # | Manufacturer | ||||
| 1 | 15 | 18329 | N/A | BECKER | ||||
| 2 | 15 | 18035 | N/A | BECKER | ||||
| 3 | 15 | 18755 | N/A | BECKER | ||||
| Medical Vacuum Pump Evaluation Inspection Record | ||||||||
| Medical Vac D302 | ||||||||
| Configuration: | Simplex | Duplex | Triplex | Quadruplex | Other |
Vacuum Type: Claw Liquid Ring Rotary Vane Oil Free Rotary Vane
Vacuum Mount: Base Tank Frame
Manufacturer: POWEREX Model: CVTD0504B41HTA
Location: D302
| Unit: | HP | Hour Meter | Pump Serial # | Manufacturer | ||||
| 1 | 15 | 15138 | N/A | BECKER | ||||
| 2 | 15 | 19403 | N/A | BECKER | ||||
| 3 | 15 | 3830 | N/A | BECKER | ||||
| 4 | 15 | 16289 | N/A | BECKER | ||||
| Medical Vacuum Pump Evaluation Inspection Record | ||||||||
| Medical Vacuum 10th floor Penthouse | ||||||||
| Configuration: | Simplex | Duplex | Triplex | Quadruplex | Other |
Vacuum Type: Claw Liquid Ring Rotary Vane Oil Free Rotary Vane
Vacuum Mount: Base Tank Frame
Manufacturer: BEACON Model: 4107106815
Location: 10TH FLR MECH ROOM
| Unit: | HP | Hour Meter | Pump Serial # | Manufacturer |
| 1 | 3 | 243 | F1606061370 | BECKER |
| 2 | 3 | 234 | F1606241210 | BECKER |
Jefferson Barracks VA
| Medical Gas Equipment Inventory | |
| Jefferson Barracks VA |
MASTER ALARM PANELS ZONE VALVE BOXES
| LOCATION: 1 | NURS STATION | ||
| LOCATION: 2 | NURS STATION | TOTAL NUMBER OF BOXES | 24 |
| LOCATION : 3 | BOILER PLANT | ||
| SWITCHES: | VALVES | ||
| OXYGEN | 27 | OXYGEN | 15 |
| MEDICAL AIR | 24 | MEDICAL AIR | 14 |
| MED VACUUM | 12 | MED VACUUM | 13 |
| EVACUATION | 0 | EVACUATION | 0 |
| NITROUS OXIDE | 0 | NITROUS OXIDE | 0 |
| NITROGEN | 0 | NITROGEN | 0 |
| CARBON DIOXIDE | 0 | CARBON DIOXIDE | 0 |
| HELIUM | 0 | HELIUM | 0 |
TOTAL SWITCHES 63 TOTAL VALVES 42
AREA ALARM PANELS PATIENT TERMINALS
TOTAL NUMBER OF PANELS 11 MEDICAL GAS TERMINALS
| ALARM POINTS: | GASES: | ||
| OXYGEN | 9 | OXYGEN | 157 |
| MEDICAL AIR | 8 | MEDICAL AIR | 152 |
| MED VACUUM | 8 | MED VACUUM | 150 |
| EVACUATION | 0 | EVACUATION | 0 |
| NITROUS OXIDE | 0 | NITROUS OXIDE | 0 |
| NITROGEN | 0 | NITROGEN | 0 |
| CARBON DIOXIDE | 0 | CARBON DIOXIDE | 0 |
| HELIUM | 0 | HELIUM | 0 |
TOTAL ALARM POINTS 25 TOTAL TERMINAL COUNT 459
Jefferson Barracks VA Equipment
Medical Gas Verification Equipment / Calibration
| Equipment | Description | Model | Qty | Cal Frequency | Prev Cal Date | |||
| Nanuk | Pelican Box- Black | 935 | 1 | N/A | N/A | |||
| Husky | Clear Case | 00908 | 4 | N/A | N/A | |||
| Test Adapter | Oxygen | x | NG MALE | DISS | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Oxygen | x | NG MALE | CH | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Oxygen | x | NG MALE | OHMEDA | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Med Air | x | NG MALE | DISS | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Med Air | x | NG MALE | CH | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Med Air | x | NG MALE | OHMEDA | 1 | ANNUAL | 6-2019 | |
| Test Adapter | N2O | x | NG MALE | DISS | 1 | ANNUAL | 6-2019 | |
| Test Adapter | N2O | x | NG MALE | CH | 1 | ANNUAL | 6-2019 | |
| Test Adapter | N2O | x | NG MALE | OHMEDA | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Vac | x | VAC MALE | CH | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Vac | x | VAC MALE | OHMEDA | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Evac | x | VAC MALE | CH | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Evac | x | VAC MALE | OHMEDA | 1 | ANNUAL | 6-2019 | |
| Test Adapter | Evac | x | VAC MALE | DISS | 1 | ANNUAL | 6-2019 | |
| Bags | 2 x 4 Clear Particulate Bags | Green | 600 | N/A | N/A | |||
| Milipore | Millipore Filter .45 Micron | HAWP02500 | 240 | ANNUAL | 6-2019 | |||
| Milipore | Millipore Adapter | x | NG FEM | Millipore | 1 | ANNUAL | 6-2019 | |
| Tweezer | S/S Tweezers | CVS | 1 | N/A | N/A | |||
| Digital Gauge | Positive | x | 1/4" | DWYER | 1 | ANNUAL | 6-2019 | |
| Digital Gauge | Vacuum | x | 1/4" | DWYER | 1 | ANNUAL | 6-2019 | |
| Oxygen Analyzer | Mactec Handi + | Handi + | 1 | ANNUAL | 6-2019 | |||
| Ultrasonic Leak | Leak Detector | ZORO | 711-202-G1 | 1 | ANNUAL | 6-2019 | ||
| FITTING | Oxygen | x | 1/8" | DISS | 1 | ANNUAL | 6-2019 | |
| FITTING | Oxygen | x | 1/8" | CH | 1 | ANNUAL | 6-2019 | |
| FITTING | Oxygen | x | 1/8" | OHMEDA | 1 | ANNUAL | 6-2019 | |
| FITTING | Med Air | x | 1/8" | DISS | 1 | ANNUAL | 6-2019 | |
| FITTING | Med Air | x | 1/8" | CH | 1 | ANNUAL | 6-2019 | |
| FITTING | Med Air | x | 1/8" | OHMEDA | 1 | ANNUAL | 6-2019 | |
| FITTING | N2O | x | 1/8" | DISS | 1 | ANNUAL | 6-2019 | |
| FITTING | N2O | x | 1/8" | CH | 1 | ANNUAL | 6-2019 | |
| FITTING | N2O | x | 1/8" | OHMEDA | 1 | ANNUAL | 6-2019 | |
| FITTING | Vac | x | 1/8" | DISS | 1 | ANNUAL | 6-2019 | |
| FITTING | Vac | x | 1/8" | CH | 1 | ANNUAL | 6-2019 | |
| FITTING | Vac | x | 1/8" | OHMEDA | 1 | ANNUAL | 6-2019 | |
| FITTING | Evac | x | 1/8" | CH | 1 | ANNUAL | 6-2019 | |
| FITTING | Evac | x | 1/8" | OHMEDA | 1 | ANNUAL | 6-2019 | |
| FITTING | Evac | x | 1/8" | DISS | 1 | ANNUAL | 6-2019 | |
| FITTING | NG | x | 1/8" | DISS | 1 | ANNUAL | 6-2019 | |
| FITTING | CO2 | x | 1/8" | DISS | 1 | ANNUAL | 6-2019 | |
| FITTING | Oxygen | DISS MALE | 1 | ANNUAL | 6-2019 | |||
| FITTING | Med Air | DISS MALE | 1 | ANNUAL | 6-2019 | |||
| FITTING | Vac | DISS MALE | 1 | ANNUAL | 6-2019 | |||
| FITTING | Evac | DISS MALE | 1 | ANNUAL | 6-2019 | |||
| FITTING | NG | DISS MALE | 1 | ANNUAL | 6-2019 | |||
| FITTING | CO2 | DISS MALE | 1 | ANNUAL | 6-2019 | |||
| FITTING | N2O | DISS MALE | 1 | ANNUAL | 6-2019 | |||
| Pres Reg | NG Pressure Regulator | Harris | 1 | ANNUAL | 6-2019 | |||
| Hose | Black Poly Hose 600 PSIG | Tyco | 1 | ANNUAL | 6-2019 | |||
| Test Gauge | NG Test Gauge Rig | NCG | 1 | ANNUAL | 6-2019 | |||
| Tephlon | Tephlon Tape | Baystate | 4 | N/A | N/A | |||
| Flow Meter | Dwyer | RMA-5-SSV | 2 | ANNUAL | 6-2019 |