36C25227Q0062.docx
DOCX document 32 KB Posted
- Solicitation number
- 36C25227Q0062
About this file
This is a Special Notice of Intent to Sole Source issued by the Department of Veterans Affairs Great Lakes Acquisition Center for fire alarm system monitoring and programming services at the Captain James A. Lovell Federal Health Care Center in North Chicago, Illinois. The VA intends to negotiate a sole source contract with Johnson Controls Fire Protection under the authority of 41 U.S.C. § 1901 (Simplified Acquisition Procedures), determining that only one responsible source can satisfy agency requirements. The contract will be structured as a firm fixed price agreement with a one-year base period plus four one-year option periods exercised at government discretion. The solicitation number is 36C25227Q0062, and the NAICS code is 561621. Responses to this notice must be submitted by email to Contract Specialist Lori Eastmead (lori.eastmead@va.gov) by 9:00 AM Central Time on October 28, 2026. Any interested firms must provide capability statements with supporting evidence demonstrating ability to meet requirements, product and service information, and customer references.
The scope requires 24/7/365 monitoring of fire alarm and fire suppression systems across multiple facility buildings, with twice-monthly technician visits scheduled for the 2nd Thursday and last Thursday of each month during normal working hours (7:00 AM to 3:30 PM Monday through Friday, excluding federal holidays). The contractor must furnish all labor, materials, tools, equipment, supervision, transportation, and expertise to perform fire and smoke alarm testing and fire suppression system services in accordance with NFPA codes, The Joint Commission standards, OSHA requirements, VA standards, and ISO 9000. Technicians must hold a minimum NICET Level II certification and possess proprietary programming access for Simplex Grinnell systems. The monitoring contractor must be UL 827 or FM-approved central station service provider and issue Certificates of Alarm Service. Documentation must be provided after each visit to the Contracting Officer Representative for recordkeeping and Joint Commission compliance. The facility includes 40+ buildings across medical, long-term care, and general categories with various wet systems, dry systems, and fire pumps requiring continuous monitoring and maintenance.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Special Notice Special Notice
| SUBJECT* |
| Fire Alarm System Monitoring and Programming INTENT TO SOLE SOURCE |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 53214-1476 |
| SOLICITATION NUMBER* |
| 36C25227Q0062 |
| RESPONSE DATE/TIME/ZONE |
| 10-28-2026 9:00AM CENTRAL TIME, CHICAGO, USA |
| ARCHIVE |
| 99 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| PRODUCT SERVICE CODE* |
| J042 |
| NAICS CODE* |
| 561621 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
36C252 115 South 84th Street, Suite 101
Milwaukee WI 53214-1476
POINT OF CONTACT*
Contract Specialist Lori Eastmead lori.eastmead@va.gov 414-844-4840
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
Under Statutory Authority 41 U.S.C. § 1901 the VA Great Lakes Acquisition Center (GLAC) intends to negotiate a sole source contract with Johnson Controls Fire Protection. The contractor shall furnish all labor, material, tools, equipment, supervision, transportation, and expertise to perform Fire/smoke alarm testing and fire suppression systems in accordance with all current regulations to perform service to all fire alarm devices and equipment located at the Captain James A. Lovell Federal Health Care Center.
This acquisition is conducted under the authority of 41 U.S.C. § 1901 Simplified acquisition procedures as implemented in RFO 12.102 only one responsible source and no other supplies or services will satisfy agency requirements. This will be a firm fixed price contract for a base plus (4) four option year contract. The NAICS Code is 561621.
This Notice of Intent is not a request for competitive quotes. No solicitation documents are available, and telephone requests will not be honored. However, if a firm believes it can meet the requirements it must furnish information about its products and services, as well as references from other customers who are using these products and services to the Contracting Officer by 9:00AM LOCAL TIME 10/28/2026. Supporting evidence must be furnished in sufficient detail to demonstrate the ability to comply with the above requirements. Responses received will be evaluated. However, a determination by the Government not to compete the proposed procurement based upon responses to this notice is solely within the discretion of the Government. If no responses are received, the Contracting Officer will proceed with the sole source negotiation with the Johnson Controls Fire Protection.
Capability statements shall be submitted by email only as a MS Word or Adobe PDF attachment to Lori Eastmead at Lori Eastmead@va.gov. TELEPHONIC INQUIRIES WILL NOT BE ACCEPTED.
STATEMENT OF WORK (SOW)
Fire Alarm System Monitoring/ Programming
1. GENERAL
Captain James A. Lovell Federal Health Care Center (FHCC), located at 3001 Green Bay Road, North Chicago, IL 60064 requires 24/7 365 Monitoring of Fire alarm and suppression systems. Including, tech labor for programming with monthly visits twice per month.
2. SCOPE
The contractor shall furnish all labor, material, tools, equipment, supervision, transportation, and expertise to perform Fire/smoke alarm testing and fire suppression systems in accordance with all current National Fire Protection Agency (NFPA) / The Joint Commission regulations and perform service to all fire alarm devices and equipment to include all devices located at the Captain James A. Lovell Federal Health Care Center.
Contractor shall provide service personnel which are certified on a Simplex Grinnell system to include access to proprietary programing to perform service to all Station Fire Systems.
3. PERIOD OF PERFORMANCE
The anticipated period of performance, (POP) will include a one (1) year base period, plus four (4) one-year option periods; that are to be exercised at the Government’s discretion.
4. CONFORMANCE STANDARDS
Contractors shall ensure that the equipment functions in conformance with The Joint Commission Elements of Performance EC.02.03.05, the latest published edition of National Fire Protection Association (NFPA) Codes, Occupational Safety and Health Administration (OSHA), Veterans Administration (VA) standards, International Organization of Standard (ISO) 9000, and manufacturer/industry standards. Must comply with records management guidelines outlined in the following web link https://www.archives.gov/records-mgmt/policy/records-mgmt-language .
5. QUALIFICATIONS
Contractor shall provide qualified technicians that shall have at minimum National Institute for Certification in Engineering Technologies (NICET) level II or higher. Contractor shall provide service and monitoring of all fire alarm systems and fire suppression systems on station. The monitoring Contractor must be listed for central station service (UL 827 or FM-approved) and issue a Certificate of Alarm Service to the protected premises.
6. SERVICES TO BE PROVIDED
1. Contractors must provide 24 hours per day, seven (7) days per week monitoring with designated fire department notification upon all alarms.
2. Covers Tech Labor during normal working hours. Contractor shall provide 2 technician scheduled visits a month at facility to provide ongoing service. These visits shall be scheduled to occur on the 2nd Thursday of the month and the last Thursday of the month. This is to ensure even number of visits are spread out to maximize effectiveness.
7. HOURS OF SERVICES
A schedule of Technician visits shall be established to be completed during the working hours, Monday through Friday, 7:00 AM Local Time until 3:30 PM Local Local Time to the extent possible. National and Federal Holidays shall be exempt. The service schedule shall be confirmed between the Contractor and Contracting Officer Representative (COR) prior to the first working day of the month.
National and Federal Holidays that shall be exempt:
| New Years' Day | Labor Day | ||
| Martin Luther King, Jr Birthday | Columbus Day | ||
| President’s Day | Veterans Day | ||
| Memorial Day | Thanksgiving Day | ||
| Juneteenth Day | Christmas Day |
Independence Day
Any other day specifically declared by the President of the United States to be a National or Federal Holiday.
When a holiday falls on a Sunday, the following Monday shall be observed as a National or Federal Holiday by U.S. Government agencies. When a holiday falls on a Saturday, the preceding Friday shall be observed as a National or Federal Holiday.
8. DOCUMENTATION
The contractor shall provide documentation records upon request in regard to monitoring. Contractor shall provide documentation after every visit to the COR to properly document repairs and history for recordkeeping and Joint commission requirements.
9. PERFORMANCE MONITORING
COR shall monitor all documentation to ensure compliance with all regulations and proposals. Any regulation changes or requirements shall be provided to Contractor via email by Contracting Officer Representative or their designee.
10. SECURITY REQUIREMENTS
Test and maintenance personnel shall be required to obtain FHCC issued Contractor Identification badges from Building 135 PIV Office. Contractor shall be responsible for keeping the credentials renewed as required. The identification shall be always worn visible while on FHCC property.
11. CHECK-IN/CHECK-OUT
The contractor shall check-in with Captain James A. Lovell Federal Health Care Center Controls personnel in Building 188. Contractor shall check-out with Captain James A. Lovell Federal Health Care Center Controls personnel in Building 188 upon completion of services or at the duration of the day, whichever shall be completed first.
12. GOVERNMENT-FURNISHED EQUIPMENT (GFE)/GOVERNMENT-FURNISHED INFORMATION (GFI)
No GFE or GFI will be furnished.
13. Key Personnel The contractor shall provide a contract manager who shall be responsible for the performance of work. The name of the designated manager and an alternate who shall act for the contractor when the manager is absent shall be designated in writing to the contracting officer. The contract manager shall have full authority relating to the daily operation of this contract. The contract manager shall be available between 7:00am and 3:30pm Local Time Monday through Friday except for Federal holidays.
14. SERVICE TABLE
| Service |
| Frequency |
| Number of Inspections per POP |
| Service Month(s) |
| Monitoring for Partitions |
| Monthly |
| Continuous |
(24/7/365) April, May, June, July, August, September
| Service Visits Tech Labor |
| Twice a month |
| 2nd Thursday and Last Thursday of the Month |
| April, May, June, July, August, September |
15. TABLE 2 INVENTORY OF BUILDINGS
a. Medical Buildings
| Building # |
| Wet System |
| Dry System |
| Fire Pump |
| 131 |
| X |
X
| 133 |
| X |
| X |
| X |
| 133CA |
| X |
| X (quantity of 2) |
| X |
| 133EF |
| X |
| 7 |
| X |
| X |
| 11 |
| X |
| X |
| 66 |
| X |
| X |
b. Long-Term Care Buildings
| Building # |
| Wet System |
| Dry System |
| Fire Pump |
X
X
X
X
| 134 |
| X |
| X |
| X |
c. General Buildings
| Building # |
| Wet System |
| Dry System |
| Fire Pump |
| Notes |
| 1 |
| X |
| X |
Vacant/construction
| 3 |
| X |
| X |
| 4 |
| X |
| X |
| 5 |
| X |
| X |
| Under construction |
| 6 |
| X |
| X |
| 9 |
| X |
| X |
| 32 |
| X |
| 37 |
| X |
| 46 |
| X |
| X |
Vacant/construction
| 92(new fire panel will be installed) |
| X |
Installation in progress
| 135 |
| X |
X
| 138 |
| X |
| 139 |
| X |
| 140 |
| X |
| 188 |
| X |
| Co-Gen |
| X |
| Fisher House |
| X |
16. SYSTEM MONITORING
All buildings listed in tables 2 (a, b, c) require monitoring 24 hours per day, 7 days per week, 365 days per year of all fire systems. The buildings that are under construction are highlighted in red. Building 1 is unoccupied but still needs to maintain life/safety as well as building 48. Building 5 is currently close to completion and will be active in the future. The partition for Building 5 has already been created and will need to be maintained in the monitoring agreement and eventually requires testing once released to FHCC ownership.
17. TYPICAL DISPATCH SCENARIOS FOR ANY ALARM RECEIVED
a. Fire Dispatch fire department and notify facility
b. Supervisory/Trouble Alarms Notify Facility- do not dispatch Fire Dept. (currently fire dept will be dispatched for supervisory alarms and even some trouble alarms. This is not necessary and common industry standards are notification only.)
c. Placing systems on bypass/test A list of approved FHCC staff will be provided and maintained at the COR discretion that will be authorized to call into monitoring. This is to prevent anyone with the password to place a system on test/bypass without FHCC’s knowledge and to accurately track the outages and maintain security and safety of the facility.
18. BILLING
All invoices submitted shall be detailed in description of work and match the contract line-item totals so that the approval process is straightforward. Services shall be billed as follows:
1. Monitoring shall be billed monthly matching the line items in the contract for schedule of services. It shall list all partitions and buildings covered in one invoice.
2. Labor/service shall be billed monthly and consist of a clear description of services provided and cost matching the contract schedule of line items amounts exactly. This will provide quicker processing of invoices.
*Invoices will be rejected if they do not meet the minimum requirements listed.
Fire Alarm System Monitoring/ Programming