36C25224Q0337_2.docx
DOCX document 192 KB Posted
- Attached to
- H265--MEDICAL GAS TESTING BASE + 4OYS
- Solicitation number
- 36C25224Q0337
About this file
This document is a Request for Quote (RFQ) solicitation issued by the Department of Veterans Affairs (VA) for medical gas system testing and inspection services at the Clement J. Zablocki VA Medical Center in Milwaukee, Wisconsin.
The key details are:
- This is a 100% set-aside for small businesses, with a NAICS code of 811210 (Electronic and Precision Equipment Repair and Maintenance).
- The contract includes a base year from June 1, 2024 to May 31, 2025, with four option years.
- The contractor shall provide labor, materials, supervision, tools, and equipment to perform preventive maintenance, inspections, and testing on medical air dryers, master/area alarm panels, dental air compressor systems, medical gas pressure outlets, manifold systems, zone valve boxes, and other medical gas equipment.
- Specific service requirements include semi-annual, annual, and quarterly testing and maintenance activities.
- Quotes are due by April 25, 2024 at 10:00 am CDT.
- The VA points of contact are Contracting Officer Susan Pasholk and Contracting Officer's Representative Perry Scott.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAGE 1 OF
1. REQUISITION NO.
2. CONTRACT NO.
3. AWARD/EFFECTIVE DATE
4. ORDER NO.
5. SOLICITATION NUMBER
6. SOLICITATION ISSUE DATE
a. NAME
b. TELEPHONE NO. (No Collect Calls)
8. OFFER DUE
DATE/LOCAL
TIME
9. ISSUED BY
CODE
10. THIS ACQUISITION IS
UNRESTRICTED OR
SET ASIDE:
% FOR:
SMALL BUSINESS
HUBZONE SMALL
BUSINESS
SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
WOMEN-OWNED SMALL BUSINESS
(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
8(A)
NAICS:
SIZE STANDARD:
11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
12. DISCOUNT TERMS
13a. THIS CONTRACT IS A
RATED ORDER UNDER
DPAS (15 CFR 700)
13b. RATING
14. METHOD OF SOLICITATION
RFQ
IFB
RFP
15. DELIVER TO
CODE
16. ADMINISTERED BY
CODE
17a. CONTRACTOR/OFFEROR
CODE
FACILITY CODE
18a.
PAYMENT WILL BE MADE BY
CODE
TELEPHONE NO.
UEI:
EFT:
PHONE:
FAX:
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER 18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED
SEE
ADDENDUM
19.
20.
21.
22.
23.
24.
ITEM NO.
SCHEDULE OF SUPPLIES/SERVICES
QUANTITY
UNIT
UNIT PRICE
AMOUNT
(Use Reverse and/or Attach Additional Sheets as Necessary)
25. ACCOUNTING AND APPROPRIATION DATA
26.
TOTAL AWARD AMOUNT (For Govt. Use Only) 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA
ARE
ARE NOT ATTACHED.
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212
-4. FAR 52.212-5 IS ATTACHED. ADDENDA
ARE
ARE NOT ATTACHED
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________
29. AWARD OF CONTRACT: REF. ___________________________________ OFFER
COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND
DATED ________________________________. YOUR OFFER ON SOLICITATION
DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY
(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE
ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED
SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:
30a. SIGNAT
URE OF OFFEROR/CONTRACTOR
31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER) 30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED
AUTHORIZED FOR LOCAL REPRODUCTION
(REV. NOV 2021)
PREVIOUS EDITION IS NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.212
7. FOR SOLICITATION
INFORMATION CALL:
STANDARD FORM 1449
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL
PRODUCTS AND COMMERCIAL SERVICES
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30
None 695-24-3-6093-0045 36C25224Q0337 04-10-2024 Pasholk,Susan 414-844-4846 04-25-2024 10:00
CDT
36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee WI 53214-1476 X X 811210 $34 Million N/A X 36C252
CLEMENT J. ZABLOCKI VA MEDICAL CENTER
Department of Veterans Affairs
5000 WEST NATIONAL AVENUE
MILWAUKEE WI 53295
36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee WI 53214-1476
Department of Veterans Affairs Financial Services Center PO Box 149971 Austin TX 78714-9971 877-353-9791 512-460-5540 See CONTINUATION Page
MEDICAL GAS SYSTEM TESTING AND INSPECTION
PER THE STATEMENT OF WORK
THIS REQUIREMENT IS 100% SET-ASIDE FOR SMALL BUSINESS
VA POC: PERRY SCOTT 414-384-2000 X43931
CO: SUSAN PASHOLK
414-844-4846
BASE YEAR JUNE 1, 2024 - MAY 31, 2025
OPTION YEAR 1 JUNE 1, 2025 - MAY 31, 2026
OPTION YEAR 2 JUNE 1, 2026 - MAY 31, 2027
OPTION YEAR 3 JUNE 1, 2027 - MAY 31, 2028
OPTION YEAR 4 JUNE 1, 2028 - MAY 31, 2029
See CONTINUATION Page 695-3640162-6093-854100-2543 010050190 X X
SUSAN PASHOLK
CONTRACTING OFFICER
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA (continuation from Standard Form 1449)
OFFERORS MUST COMPLETE AND RETURN ALL INFORMATION DESIGNATED HEREIN PRIOR TO THE TIME SPECIFIED IN BLOCK 8 OF SF 1449 IN ORDER TO BE CONSIDERED FOR AWARD.
ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:
| AMENDMENT NO | DATE | |
| ______________________________ | __________________________ | |
| ______________________________ | __________________________ | |
| ______________________________ | __________________________ |
1. CONTRACT ADMINISTRATION: All contract administration matters will be handled by the following individuals:
a. CONTRACTOR:
CONTRACTOR NAME _____________________________________
ADDRESS _____________________________________
CITY-STATE-ZIP _____________________________________
POINT OF CONTACT/TITLE _____________________________________
| PHONE NUMBER | _____________________________________ |
| E-MAIL ADDRESS | _____________________________________ |
UNIQUE ENTITY INDENTIFIER _____________________________________
b. GOVERNMENT: SUSAN PASHOLK, CONTRACTING OFFICER
CONTRACTING OFFICE CODE: 36C252
| DEPARTMENT OF VETERANS AFFAIRS |
| GREAT LAKES ACQUISITION CENTER |
| 115 S. 84TH ST., STE 100 |
MILWAUKEE WI 53214
2. ACQUISITION OF COMMERCIAL ITEMS: This Request for Quote (RFQ) solicitation is issued under the authority of FAR Part 13.5 Simplified Procedures for Certain Commercial Items in which simplified acquisition procedures in FAR Part 13 will be used. FAR Part 14 and 15 will not be used. From this RFQ, the Government intends to award a firm fixed price contract where the contractor provides a price that is not subject to any adjustment on the basis of the contractor’s cost experience in performing the contract. (Note: The terms “offeror” and “quoter” are both used in this Solicitation. For the purposes of this Solicitation, these terms are interchangeable; there is no difference in meaning between the two.)
3. SET-ASIDE (If any): See box 10 of STANDARD FORM 1449
4. SOLICITATION TIMELINE SUMMARY:
1. SITE VISIT:
It is strongly suggested and expected that the offeror inspect the campus to be serviced to fully understand the nature of the work and the conditions under which the work is to be performed. In no case shall failure to inspect the campus constitute grounds for a claim after contract award.
SITE VISIT IS SCHEDULED FOR TUESDAY APRIL 16, 2024 AT 9:30 AM LOCAL TIME. ALL INTERESTED PARTIES TO MEET COR PERRY SCOTT (414-629-1213) AT EAST ENTRANCE OF BUILDING 111.
1. RFQ QUESTIONS:
In order to maintain integrity of this solicitation and subsequent award date, all offerors are advised that any question and answer requests must be submitted in a written form via e-mail to the Contracting Officer susan.pasholk@va.gov no later than WEDNESDAY APRIL 17, 2024 AT NOON LOCAL TIME. Contracting will issue a consolidated response via solicitation amendment to https://sam.gov Contract Opportunities within 2 business days to all parties
1. SOLICITATION CLOSES/QUOTES DUE:
See box 8 of STANDARD FORM 1449 or most recent Amendment.
1. SUBMISSION OF QUOTE:
See 52.212-1 Instructions to Offerors—Commercial Products and Commercial Services and addendum for specific instructions to offerors.
5. CONTRACTING OFFICER AUTHORITY:
The Contracting Officer is the only person authorized to approve changes or modify any of the requirements under this contract. The Contractor shall communicate with the Contracting Officer on all matters pertaining to contract administration. Only the Contracting Officer is authorized to make commitment or issue changes that will affect price, quantity or quality of performance of this contract. In the event the Contractor effects any such change at the direction of any person other than the Contracting Officer, the change shall be considered to have been made without authority and no adjustment will be made in the contract price to cover any increase in cost incurred thereof.
6. INVOICES:
1. All payments by the Government to the contractor will be made in accordance with: FAR 52.232-33 PAYMENT BY ELECTRONIC FUNDS TRANSFER – SYSTEM FOR AWARD MANAGEMENT (OCT 2018)
1. Invoices shall be submitted quarterly in arrears in accordance with: 852.232-72 ELECTRONIC SUBMISSION OF PAYMENT REQUESTS (NOV 2018)
1. Payments shall be made in arrears upon receipt of a properly prepared invoice
1. Facsimile, e-mail, and scanned documents are not acceptable forms of submission for payment requests.
1. The VA has mandated electronic invoice submission to the Veterans Affairs Financial Services Center (VAFSC). VAFSC has partnered with Tungsten Network e-Invoicing network, for submissions of all electronic invoices to VA. Tungsten Network electronic invoicing is free to all VA vendors. In order to submit electronic invoices, all VA vendors must register with Tungsten Network by submitting an email to VA.Registration@Tungsten-Network.com or calling 1-877-489-6135 for Enrollment.
1. Contractor shall submit an electronic invoice by the tenth (10th) of the following month services were performed to the Veterans Affairs Financial Services Center (VAFSC) e-Invoice through the website at https://portal.Tungsten-Network.com/Login.aspx. For questions regarding the submission of VA electronic invoices, Tungsten Network customer service may be contacted at 1-877-489-6135.
1. All invoices shall reference the vendor name and address, customer name, contract number, appropriate obligation/funding order number, description of services provided, quantity, unit price, and total invoice amount (any additional info). Invoices shall also include any payment discount terms.
1. VA’s Electronic Invoice Presentment and Payment System – The Veterans Affairs Financial Services Center (VAFSC) uses a third-party contractor, Tungsten Network e-Invoice, to transition vendors from paper to electronic invoice submission. Please go to this website: http://www.tungsten-network.com/customer-campaigns/veteransaffairs/ to begin submitting electronic invoices, free of charge.
1. As of July 1, 2020, the VA10091 form has been eliminated and the VAFSC is requiring our vendors to update and add their information in the Customer Engagement Portal (CEP) at https://www.cep.fsc.va.gov/. This is for new vendors being added to FMS only.
1. For assistance setting up e-Invoice, the below information is provided:
* Tungsten Network e-Invoice Setup Information: 1-877-489-6135
* Tungsten Network e-Invoice email: VA.Registration@Tungsten-Network.com
* FSC e-Invoice Contact Information: 1-877-353-9791
* FSC e-invoice email: vafsccshd@va.gov
7. FACILITY REQUIREMENTS: In addition to any other requirements set forth in this Contract, the Contractor, including its employees, agents, and subcontractors (collectively “the Contractor”), shall comply with the following facility requirements. Failure to comply with these requirements shall be considered a material breach of this Contract and may be a violation of Federal law resulting in charges answerable in the United States District Court.
1. Contractor is responsible to follow all on site facility policies
1. All VA property is considered Federal property and all Federal laws are applicable.
1. It is the responsibility of the Contractor to park in the appropriate designated parking areas. Information on parking is available from the VA Police Section. The VA will not invalidate or make reimbursement for parking violations of the Contractor under any conditions.
1. All VA facilities are drug free. Possession of drugs, to include Marijuana and all Marijuana bi-products are prohibited. Enclosed containers, including tool kits, shall be subject to search. Violations of VA regulations may result in citation answerable in the United States (Federal) District Court, not a local district, state, or municipal court.
1. All contractor personnel are required to adhere to all VA rules and regulations.
1. Smoking is prohibited on the entire campus, both inside and outside the VA Facility
1. Possession of weapons is prohibited. Enclosed containers, including tool kits, shall be subject to search. Violations of VA regulations may result in citation answerable in the United States (Federal) District Court, not a local district, state, or municipal court.
1. VHA DIRECTIVE 1192: This Veterans Health Administration (VHA) directive establishes policy and provides guidance for the prevention of seasonal influenza in VHA facilities through the vaccination or masking of health care personnel (HCP). AUTHORITY: Title 38 United States Code (U.S.C.) 7301(b), 7318(b). Contractor is responsible in ensuring that all aspects of this directive are implemented, including providing face masks and influenza vaccines for all employees working at a VA facility.
8. SECURITY & PRIVACY CONTROL:
The Authorization & Accreditation (A&A) requirements of VHA Handbook 6500.6 do not apply to this requirement, therefore, a Security Accreditation Package is not required. No A&A or MOU/ISA is required. Sensitive information exposure as part of this contract involves applicable security controls within the facility as part of the VA Information Security If there are any questions related to privacy, please have a member of your staff contact the VA Privacy Service at (202) 461-6309. If there are any questions related to the information security, please have a member of your staff contact the Office of Cyber Security at (304) 262-7733.
Visitor Passes:
Issuance of visitor passes is the responsibility and at the discretion of each Facility Director. Visitor passes may be issued to individuals requiring short-term access to a VA facility for a period not to exceed 15 days in a 365-day period. Visitor passes are issued on a daily basis and expire at the end of the day of issuance. Visitor passes are issued following, at a minimum, review of one valid and current State or Federal government issued photo ID. Visitors must be escorted in areas restricted to the general public.
9. FACILITY CHECK IN/OUT PROCEDURES:
Sign in/out is MANDATORY:
Contractor and/or their technicians are required to check in at Graphics Center, Bldg. 113 upon arrival to VAMC, and check out upon departure.
VA contact Person(s): Perry Scott Location (Building/Room Number): Building 70; Room 70-1067 Telephone Number & Extension(s): 414-384-2000, ext. 43931 Contractor -- Provide telephone number(s) to call for your Service Department: ___________ Provide name(s) of authorized contact person(s): __________________
A.1 PRICE/COST SCHEDULE
ITEM INFORMATION
| ITEM # |
| DESCRIPTION OF SERVICES |
| QTY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1.00 |
| YR |
Contractor shall provide all L,T,E & M to inspect, functionality test, and perform Preventative Maintenance on the Medical Air Dryer and associated alarm panels to include required documentation per Statement of Work.
Contract Period: Base POP Begin: 06-01-2024 POP End: 05-31-2025 PRINCIPAL NAICS CODE: 811210 - Electronic and Precision Equipment Repair and Maintenance PRODUCT/SERVICE CODE: H265 - Equipment and Materials Testing - Medical, Dental, and Veterinary Equipment and Supplies
0001AA
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Dryer function testing per manufacturer recommendation: Semi-Annually in Nov and May
0001AB
| 1.00 |
| JB |
Calibrate carbon monoxide monitor: Annually in May
0001AC
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Test/check dewpoint monitor with portable instrumentation; Semi Annually in Nov and May
0001AD
| 1.00 |
| JB |
Replace all filter element, purge muffler and dew point monitor sensor: Annually in May
0001AE
| 1.00 |
| JB |
Test dew point and carbon monoxide master panel signal; Annually in May
| 1.00 |
| YR |
Test and evaluate medical gas system Master Alarm Panels to include required documentation per Statement of Work
0002AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test alarm functions and settings in accordance with manufacturer’s specifications. Place each master in actual alarm conditions and recalibrate. Include check of all lamps and audible alarms for sound at Master Alarm Panels; Annually in May
0002AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Master Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly in Nov, Feb, May and August
| 1.00 |
| YR |
Test and evaluate medical gas system Area Alarm Panels; (Facility Wide). Contractor to provide complete documentation for facility records after each PM visit.
0003AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test alarm functions and settings in accordance with manufacturer’s specifications. Place each panel in actual alarm conditions and recalibrate. Include check of all lamps and audible alarms for sound at Area Alarm Panels; Annually in May
0003AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Area Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly (At the conclusion of each panel tested, the Service technician is to provide an immediate Reorientation of panel function and operation to the VA area supervisor. Reorientation training shall be documented on the medical gas panel Test and Inspection report (to include date, time and Supervisor(s) name(s) ); Due in Nov, Feb, May and Aug and Supplies
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to inspect, functionally test and perform preventive maintenance on the dental air compressor system per manufacturer’s and National Fire Protection Agency (NFPA) 99 standards. Contractor to provide complete documentation for facility records after each PM visit.
0004AA
| 2.00 |
| JB |
| $__________________ |
| $_________________ |
Replacement of all filter elements and recalibrations of the dew point and carbon monoxide monitors shall also be done Semi-annually; Due in Nov and May
0004AB
| 1.00 |
| JB |
Perform laboratory particulate and purity annual testing on the dental air system. Lab results must be included in preventative maintenance Report; Due in May
0004AC
| 1.00 |
| JB |
Inspect, functionally test, and perform annual preventative maintenance on the Dental vacuum system per manufacturer’s and NFPA 99 standards; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to perform testing on all medical gas pressure outlets:
0005AA
| 1.00 |
| JB |
Perform annual performance testing for all Medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during normal work hours; Annually in Feb
0005AB
| 1.00 |
| JB |
Perform annual performance testing for all medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during premium work hours; Annually in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection, testing and calibration of all medical gas manifold systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually provide purity and Particulate testing on oxygen, medical air and nitrous Oxide gas systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection and testing on all zone valve boxes throughout Medical Center for proper location, valve type, label accuracy, and presence/function of gauges per NFPA Standards. Contractor to provide complete documentation of testing and results for facility records; Due in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually perform inspection and leak testing of source valves (Oxygen, Medical Air, and Vacuum – total of 3). Contractor will provide and install CGA/NFPA 99 approved valve tags properly identifying the area(s) being served. Contractor will install proper NFPA 99 pipe labels on the distribution piping adjacent to source valves. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary to inspect, functionally test, and perform preventive maintenance on the Surgery Instrument Air Compressor package and dryer system. Provide complete documentation for facility records after each PM visit.
0010AA
| 1.00 |
| JB |
Replace all compressor filter elements and belts. Properly lubricate as required. Replace all dryer elements, purge mufflers and dew point sensor; Due in August
0010AB
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Perform semi-annually, thorough inspection, testing and recalibration of the instrument Air Compressor and dryer; Due in August and February
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to provide initial inventory and perform testing and evaluation of each Medical Gas vacuum inlet for proper identification, - function, flow, latching, cleanliness, and vacuum pressure per NFPA 99s standards: Due in March
| 1.00 |
| JB |
Provide a medical gas awareness training program for each applicable department throughout the facility. Provide two (2) focused awareness programs for the Police staff.
| 1.00 |
| JB |
All L,T,M,E necessary to perform Flexible Outlet/Inlet Hose assembly testing; Due in August
| 12.00 |
| MO |
| $_____________ |
| $_______________ |
Emergency Service/Maintenance performed outside normal hours of coverage.
BASE YEAR TOTAL $_____________________
| 1.00 |
| YR |
Contractor shall provide all L,T,E & M to inspect, functionality test, and perform Preventative Maintenance on the Medical Air Dryer and associated alarm panels to include required documentation per Statement of Work.
Contract Period: Option 1 POP Begin: 06-01-2025 POP End: 05-31-2026
PRODUCT/SERVICE CODE: H265 - Equipment and Materials Testing - Medical, Dental, and Veterinary Equipment and Supplies
1001AA
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Dryer function testing per manufacturer recommendation: Semi-Annually in Nov and May
1001AB
| 1.00 |
| JB |
Calibrate carbon monoxide monitor: Annually in May
1001AC
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Test/check dewpoint monitor with portable instrumentation; Semi Annually in Nov and May
1001AD
| 1.00 |
| JB |
Replace all filter element, purge muffler and dew point monitor sensor: Annually in May
1001AE
| 1.00 |
| JB |
Test dew point and carbon monoxide master panel signal; Annually in May
| 1.00 |
| YR |
Test and evaluate medical gas system Master Alarm Panels to include required documentation per Statement of Work
1002AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test manufacturer’s specifications. Place each master in actual alarm conditions and recalibrate. Include
1002AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Master Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly in Nov, Feb, May and August
| 1.00 |
| YR |
Test and evaluate medical gas system Area Alarm Panels; (Facility Wide). Contractor to provide complete documentation for facility records after each PM visit.
1003AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test alarm functions and settings in accordance with manufacturer’s specifications. Place each panel in actual alarm conditions and recalibrate. Include check of all lamps and audible alarms for sound at Area Alarm Panels; Annually in May
1003AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Area Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly (At the conclusion of each panel tested, the Service technician is to provide an immediate Reorientation of panel function and operation to the VA area supervisor. Reorientation training shall be documented on the medical gas panel Test and Inspection report (to include date, time and Supervisor(s) name(s) ); Due in Nov, Feb, May and Aug
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to inspect, functionally test and perform preventive maintenance on the dental air compressor system per manufacturer’s and NFPA 99 standards. Contractor to provide complete documentation for facility records after each PM visit.
1004AA
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Replacement of all filter elements and recalibrations of the dew point and carbon monoxide monitors shall also be done Semi-annually; Due in Nov and May
1004AB
| 1.00 |
| JB |
Perform laboratory particulate and purity annual testing on the dental air system. Lab results must be included in preventative maintenance Report; Due in May
1004AC
| 1.00 |
| JB |
Inspect, functionally test, and perform annual preventative maintenance on the Dental vacuum system per manufacturer’s and NFPA 99 standards; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to perform testing on all medical gas pressure outlets:
1005AA
| 1.00 |
| JB |
Perform annual performance testing for all Medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during normal work hours; Annually in Feb
1005AB
| 1.00 |
| JB |
Perform annual performance testing for all medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during premium work hours; Annually in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection, testing and calibration of all medical gas manifold systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually provide purity and Particulate testing on oxygen, medical air and nitrous Oxide gas systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection and testing on all zone valve boxes throughout Medical Center for proper location, valve type, label accuracy, and presence/function of gauges per NFPA Standards. Contractor to provide complete documentation of testing and results for facility records; Due in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually perform inspection and leak testing of source valves (Oxygen, Medical Air, and Vacuum – total of 3). Contractor will provide and install CGA/NFPA 99 approved valve tags properly identifying the area(s) being served. Contractor will install proper NFPA 99 pipe labels on the distribution piping adjacent to source valves. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary to inspect, functionally test, and perform preventive maintenance on the Surgery Instrument Air Compressor package and dryer system. Provide complete documentation for facility records after each PM visit., and
1010AA
| 1.00 |
| JB |
Replace all compressor filter elements and belts. Properly lubricate as required. Replace all dryer elements, purge mufflers and dew point sensor; Due in August
1010AB
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Perform semi-annually, thorough inspection, testing and recalibration of the instrument Air Compressor and dryer; Due in August and February
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to provide initial inventory vacuum inlet for proper identification, - function, flow, latching, cleanliness, and vacuum pressure per NFPA 99s standards; Due in March
| 1.00 |
| JB |
Provide a medical gas awareness training program for each applicable department throughout the facility. Provide two (2) focused awareness programs for the Police staff.
| 1.00 |
| JB |
All L,T,M,E necessary to perform Flexible Outlet/Inlet Hose assembly testing; Due in August
| 12.00 |
| MO |
| $_____________ |
| $_______________ |
Emergency Service/Maintenance performed outside normal hours of coverage.
TOTAL OPTION YEAR 1 $__________________
| 1.00 |
| YR |
Contractor shall provide all L,T,E & M to inspect, functionality test, and perform Preventative Maintenance on the Medical Air Dryer and associated alarm panels to include required documentation per Statement of Work.
Contract Period: Option 2 POP Begin: 06-01-2026 POP End: 05-31-2027
PRODUCT/SERVICE CODE: H265 - Equipment and Materials Testing - Medical, Dental, and Veterinary Equipment and Supplies
2001AA
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Dryer function testing per manufacturer recommendation: Semi-Annually in Nov and May
2001AB
| 1.00 |
| JB |
Calibrate carbon monoxide monitor: Annually in May
2001AC
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Test/check dewpoint monitor with portable instrumentation; Semi Annually in Nov and May
2001AD
| 1.00 |
| JB |
Replace all filter element, purge muffler and dew point monitor sensor: Annually in May
2001AE
| 1.00 |
| JB |
Test dew point and carbon monoxide master panel signal; Annually in May
| 1.00 |
| YR |
Test and evaluate medical gas system Master Alarm Panels to include required documentation per Statement of Work
2002AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test manufacturer’s specifications. Place each master in actual alarm conditions and recalibrate. Include
2002AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Master Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly in Nov, Feb, May and August
| 1.00 |
| YR |
Test and evaluate medical gas system Area Alarm Panels; (Facility Wide). Contractor to provide complete documentation for facility records after each PM visit.
2003AA
| 1.00 |
| JB |
| $_____________ |
| $_______________ |
Inspect for proper pressure switch locations, test alarm functions and settings in accordance with manufacturer’s specifications. Place each panel in actual alarm conditions and recalibrate. Include check of all lamps and audible alarms for sound at Area Alarm Panels; Annually in May
2003AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Area Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly (At the conclusion of each panel tested, the Service technician is to provide an immediate Reorientation of panel function and operation to the VA area supervisor. Reorientation training shall be documented on the medical gas panel Test and Inspection report (to include date, time and Supervisor(s) name(s) ); Due in Nov, Feb, May and Aug
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to inspect, functionally test and perform preventive maintenance on the dental air compressor system per manufacturer’s and NFPA 99 standards. Contractor to provide complete documentation for facility records after each PM visit.
2004AA
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Replacement of all filter elements and recalibrations of the dew point and carbon monoxide monitors shall also be done Semi-annually; Due in Nov and May
2004AB
| 1.00 |
| JB |
Perform laboratory particulate and purity annual testing on the dental air system. Lab results must be included in preventative maintenance Report; Due in May
2004AC
| 1.00 |
| JB |
Inspect, functionally test, and perform annual preventative maintenance on the Dental vacuum system per manufacturer’s and NFPA 99 standards; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to perform testing on all medical gas pressure outlets:
2005AA
| 1.00 |
| JB |
Perform annual performance testing for all Medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during normal work hours; Annually in Feb
2005AB
| 1.00 |
| JB |
Perform annual performance testing for all medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during premium work hours; Annually in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection, testing and calibration of all medical gas manifold systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually provide purity and Particulate testing on oxygen, medical air and nitrous Oxide gas systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection and testing on all zone valve boxes throughout Medical Center for proper location, valve type, label accuracy, and presence/function of gauges per NFPA Standards. Contractor to provide complete documentation of testing and results for facility records; Due in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually perform inspection and leak testing of source valves (Oxygen, Medical Air, and Vacuum – total of 3). Contractor will provide and install CGA/NFPA 99 approved valve tags properly identifying the area(s) being served. Contractor will install proper NFPA 99 pipe labels on the distribution piping adjacent to source valves. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary to inspect, functionally test, and perform preventive maintenance on the Surgery Instrument Air Compressor package and dryer system. Provide complete documentation for facility records after each PM visit.
2010AA
| 1.00 |
| JB |
Replace all compressor filter elements and belts. Properly lubricate as required. Replace all dryer elements, purge mufflers and dew point sensor; Due in August
2010AB
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Perform semi-annually, thorough inspection, testing and recalibration of the instrument Air Compressor and dryer; Due in August and February
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to provide initial inventory vacuum inlet for proper identification, - function, flow, standards; Due in March
| 1.00 |
| JB |
Provide a medical gas awareness training program for each applicable department throughout the facility. Provide two (2) focused awareness programs for the Police staff.
| 1.00 |
| JB |
All L,T,M,E necessary to perform Flexible Outlet/Inlet Hose assembly testing; Due in August
| 12.00 |
| MO |
| $_____________ |
| $_______________ |
Emergency Service/Maintenance performed outside normal hours of coverage.
TOTAL OPTION YEAR 2 $_____________________
| 1.00 |
| YR |
Contractor shall provide all L,T,E & M to inspect, functionality test, and perform Preventative Maintenance on the Medical Air Dryer and associated alarm panels to include required documentation per Statement of Work.
Contract Period: Option 3 POP Begin: 06-01-2027 POP End: 05-31-2028
PRODUCT/SERVICE CODE: H265 - Equipment and Materials Testing - Medical, Dental, and Veterinary Equipment and Supplies
3001AA
| 2.00 |
| JB |
| $__________________ |
| $__________________ |
Dryer function testing per manufacturer recommendation: Semi-Annually in Nov and May
3001AB
| 1.00 |
| JB |
Calibrate carbon monoxide monitor: Annually in May
3001AC
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Test/check dewpoint monitor with portable instrumentation; Semi Annually in Nov and May
3001AD
| 1.00 |
| JB |
Replace all filter element, purge muffler and dew point monitor sensor: Annually in May
3001AE
| 1.00 |
| JB |
Test dew point and carbon monoxide master panel signal; Annually in May
| 1.00 |
| YR |
Test and evaluate medical gas system Master Alarm Panels to include required documentation per Statement of Work
3002AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test manufacturer’s specifications. Place each master in actual alarm conditions and recalibrate. Include
3002AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Master Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly in Nov, Feb, May and August
| 1.00 |
| YR |
Test and evaluate medical gas system Area Alarm Panels; (Facility Wide). Contractor to provide complete documentation for facility records after each PM visit.
3003AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test alarm functions and settings in accordance with manufacturer’s specifications. Place each panel in actual alarm conditions and recalibrate. Include check of all lamps and audible alarms for sound at Area Alarm Panels; Annually in May
3003AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Area Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly (At the conclusion of each panel tested, the Service technician is to provide an immediate Reorientation of panel function and operation to the VA area supervisor. Reorientation training shall be documented on the medical gas panel Test and Inspection report (to include date, time and Supervisor(s) name(s) ); Due in Nov, Feb, May and Aug
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to inspect, functionally test and perform preventive maintenance on the dental air compressor system per manufacturer’s and NFPA 99 standards. Contractor to provide complete documentation for facility records after each PM visit.
3004AA
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Replacement of all filter elements and recalibrations of the dew point and carbon monoxide monitors shall also be done Semi-annually; Due in Nov and May
3004AB
| 1.00 |
| JB |
Perform laboratory particulate and purity annual testing on the dental air system. Lab results must be included in preventative maintenance Report; Due in May
3004AC
| 1.00 |
| JB |
Inspect, functionally test, and perform annual preventative maintenance on the Dental vacuum system per manufacturer’s and NFPA 99 standards; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to perform testing on all medical gas pressure outlets:
3005AA
| 1.00 |
| JB |
Perform annual performance testing for all Medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during normal work hours; Annually in Feb
3005AB
| 1.00 |
| JB |
Perform annual performance testing for all medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during premium work hours; Annually in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection, testing and calibration of all medical gas manifold systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually provide purity and Particulate testing on oxygen, medical air and nitrous Oxide gas systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection and testing on all zone valve boxes throughout Medical Center for proper location, valve type, label accuracy, and presence/function of gauges per NFPA Standards. Contractor to provide complete documentation of testing and results for facility records; Due in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually perform inspection and leak testing of source valves (Oxygen, Medical Air, and Vacuum – total of 3). Contractor will provide and install CGA/NFPA 99 approved valve tags properly identifying the area(s) being served. Contractor will install proper NFPA 99 pipe labels on the distribution piping adjacent to source valves. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary to inspect, functionally test, and perform preventive maintenance on the Surgery Instrument Air Compressor package and dryer system. Provide complete documentation for facility records after each PM visit.
3010AA
| 1.00 |
| JB |
Replace all compressor filter elements and belts. Properly lubricate as required. Replace all dryer elements, purge mufflers and dew point sensor; Due in August
3010AB
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Perform semi-annually, thorough inspection, testing and recalibration of the instrument Air Compressor and dryer; Due in August and February
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to provide initial inventory vacuum inlet for proper identification, - function, flow, standards; Due in March
| 1.00 |
| JB |
Provide a medical gas awareness training program for each applicable department throughout the facility. Provide two (2) focused awareness programs for the Police staff.
| 1.00 |
| JB |
All L,T,M,E necessary to perform Flexible Outlet/Inlet Hose assembly testing; Due in August
| 12.00 |
| MO |
| $_____________ |
| $_______________ |
Emergency Service/Maintenance performed outside normal hours of coverage.
TOTAL OPTION YEAR 3 $__________________
| 1.00 |
| YR |
Contractor shall provide all L,T,E & M to inspect, functionality test, and perform Preventative Maintenance on the Medical Air Dryer and associated alarm panels to include required documentation per Statement of Work.
Contract Period: Option 4 POP Begin: 06-01-2028 POP End: 05-31-2029
PRODUCT/SERVICE CODE: H265 - Equipment and Materials Testing - Medical, Dental, and Veterinary Equipment and Supplies
4001AA
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Dryer function testing per manufacturer recommendation: Semi-Annually in Nov and May
4001AB
| 1.00 |
| JB |
Calibrate carbon monoxide monitor: Annually in May
4001AC
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Test/check dewpoint monitor with portable instrumentation; Semi Annually in Nov and May
4001AD
| 1.00 |
| JB |
Replace all filter element, purge muffler and dew point monitor sensor: Annually in May
4001AE
| 1.00 |
| JB |
Test dew point and carbon monoxide master panel signal; Annually in May
| 1.00 |
| YR |
Test and evaluate medical gas system Master Alarm Panels to include required documentation per Statement of Work
4002AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test manufacturer’s specifications. Place each master in actual alarm conditions and recalibrate. Include
4002AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Master Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly in Nov, Feb, May and August
| 1.00 |
| YR |
Test and evaluate medical gas system Area Alarm Panels; (Facility Wide). Contractor to provide complete documentation for facility records after each PM visit.
4003AA
| 1.00 |
| JB |
Inspect for proper pressure switch locations, test alarm functions and settings in accordance with manufacturer’s specifications. Place each panel in actual alarm conditions and recalibrate. Include check of all lamps and audible alarms for sound at Area Alarm Panels; Annually in May
4003AB
| 4.00 |
| JB |
| $_____________ |
| $_______________ |
Test each Area Alarm Panel for proper audible and visual function, and inspect for Proper labeling; Quarterly (At the conclusion of each panel tested, the Service technician is to provide an immediate Reorientation of panel function and operation to the VA area supervisor. Reorientation training shall be documented on the medical gas panel Test and Inspection report (to include date, time and Supervisor(s) name(s) ); Due in Nov, Feb, May and Aug
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to inspect, functionally test and perform preventive maintenance on the dental air compressor system per manufacturer’s and NFPA 99 standards. Contractor to provide complete documentation for facility records after each PM visit.
4004AA
| 2.00 |
| JB |
| $__________________ |
| $__________________ |
Replacement of all filter elements and recalibrations of the dew point and carbon monoxide monitors shall also be done Semi-annually; Due in Nov and May
4004AB
| 1.00 |
| JB |
Perform laboratory particulate and purity annual testing on the dental air system. Lab results must be included in preventative maintenance Report; Due in May
4004AC
| 1.00 |
| JB |
Inspect, functionally test, and perform annual preventative maintenance on the Dental vacuum system per manufacturer’s and NFPA 99 standards; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary for Contractor to perform testing on all medical gas pressure outlets:
4005AA
| 1.00 |
| JB |
Perform annual performance testing for all Medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during normal work hours; Annually in Feb
4005AB
| 1.00 |
| JB |
Perform annual performance testing for all medical gas pressure outlets (oxygen, medical air, nitrous oxide, nitrogen) – during premium work hours; Annually in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection, testing and calibration of all medical gas manifold systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually provide purity and Particulate testing on oxygen, medical air and nitrous Oxide gas systems in accordance with the requirements of NFPA 99, CGA, USP, and the manufacturer’s instructions/literature. Contractor to provide complete documentation of testing and results for facility records Due in May
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to perform annual Inspection and testing on all zone valve boxes throughout Medical Center for proper location, valve type, label accuracy, and presence/function of gauges per NFPA Standards. Contractor to provide complete documentation of testing and results for facility records; Due in Feb
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to annually perform inspection and leak testing of source valves (Oxygen, Medical Air, and Vacuum – total of 3). Contractor will provide and install CGA/NFPA 99 approved valve tags properly identifying the area(s) being served. Contractor will install proper NFPA 99 pipe labels on the distribution piping adjacent to source valves. Contractor to provide complete documentation of testing and results for facility records; Due in May
| 1.00 |
| YR |
All L,T,M,E necessary to inspect, functionally test, and perform preventive maintenance on the Surgery Instrument Air Compressor package and dryer system. Provide complete documentation for facility records after each PM visit.
4010AA
| 1.00 |
| JB |
Replace all compressor filter elements and belts. Properly lubricate as required. Replace all dryer elements, purge mufflers and dew point sensor; Due in August
4010AB
| 2.00 |
| JB |
| $_____________ |
| $_______________ |
Perform semi-annually, thorough inspection, testing and recalibration of the instrument Air Compressor and dryer; Due in August and February
| 1.00 |
| JB |
All L,T,M,E necessary for Contractor to provide initial inventory vacuum inlet for proper identification, - function, flow, standards; Due in March
| 1.00 |
| JB |
Provide a medical gas awareness training program for each applicable department throughout the facility. Provide two (2) focused awareness programs for the Police staff.
| 1.00 |
| JB |
All L,T,M,E necessary to perform Flexible Outlet/Inlet Hose assembly testing; Due in August
| 12.00 |
| MO |
| $_____________ |
| $_______________ |
Emergency Service/Maintenance performed outside normal hours of coverage.
TOTAL OPTION YEAR 4 $___________________
| GRAND TOTAL |
| $_______________ |
MILWAUKEE VA MEDICAL CENTER
MEDICAL GAS SYSTEM TESTING & INSPECTION
STATEMENT OF WORK
The contractor shall provide all labor, materials, supervision, tools and equipment (L,T,M,E)necessary to perform Preventive Maintenance/Inspections/Emergency Service for MEDICAL GAS SYSTEMS as described in this Statement of Work for Clement J. Zablocki VA Medical Center, 5000 W. National Ave, Milwaukee, WI.
1. SCOPE OF WORK
A. Contractor shall perform scheduled preventative maintenance (PM) and inspections in accordance with manufacturer's specifications.
B. Critical Elements:
l) Contractor shall provide complete inventory and initial inspection of each piece of equipment listed herein. Inventory shall be submitted to COR electronically using MS Excel (or other mutually agreed upon format). See Section 2.
2) Based on initial inventory/inspection; Contractor shall establish and provide to the COR, a complete Preventive Maintenance Plan (PMP) to include proposed schedule to ensure requirements of the contract are met. PMP shall be provided within 10 days of completion of initial inventory/inspection. See Sections 6 &11
3) In addition to a PMP, Contractor shall establish a Quality Control Program (QCP) which shall be provided to COR within 10 days of completion of initial inventory/inspection. See Section 19.
4) Contractor shall provide written work reports. See Sections 10 & 13.
5) Contractor response time shall be within 8 hours after call is received for emergency services associated with the medical gas systems. See Section 8.
6) Preventive maintenance shall be scheduled accordingly as defined per system. See Section 4.
7) Requests for extensive repairs shall be submitted in writing to the COR. See Section 16.
8) Documentation for all work performed under this contract shall be submitted electronically using MS Excel (or other mutually agreed upon format). See Sections 2 & 13.
2. TECHNICAL WORK REOUIREMENTS
Upon award of the contract the Contractor shall coordinate with the COR a non-labor intensive plan to inventory and inspect the Medical Gas Systems and provide the COR a written and electronic report of condition to include drawings. The report of condition shall be provided to the COR before work in the specified area starts. Within 10 days of completion of initial inventory/inspection, Contractor shall be required to submit a Preventive Maintenance Plan for all equipment listed herein.
3. CONFORMANCE STANDARDS
A. Contractor shall perform PM and inspections in accordance with manufacturer's specifications. The Contractor shall perform the services in such a manner that does not damage government property. In the event damage occurs to Government property, or any adjacent property by reason of services performed under this contract, the Contractor shall replace or repair the same to the satisfaction of the COR at no cost to the Government. If damage caused by the Contractor has to be repaired or replaced by the Government, the cost of such work shall be deducted from the monies due the Contractor.
B. For any failures found during inspections/testing, the COR and Operations & Maintenance Manager shall be emailed within 24 hours of failure.
C. The Contractor shall secure all permits, licenses, and/or certificates, or any such approvals or plans or specifications as may be required by federal, state and local laws, ordinances, rules, or regulations, for the proper execution and completion of the work under this contract.
D. Chemicals used shall not cause damage to government owned equipment, furniture, exterior building surfaces, etc. Any excess servicing chemicals spilled shall be cleaned-up, the residue neutralized as required, and the surface washed and dried. Spilled clean water shall be cleaned up and the surfaces dried. Contractor shall furnish a listing of proposed chemicals, along with Material Safety Data Sheets (MSDS), to be used for approval by the Government to the COR.
4. PREVENTIVE MAINTENANCE AND INSPECTIONS SHALL INCLUDE
A. All L,T,M,E necessary for Contractor to inspect, functionally test and perform preventive maintenance on the Medical Air Dryer and the Associated Alarm Panels.
This is the start of the file's text. The full file is on GovTribe.