Attachment A - Damper Repairs and Installation

Building Floor Room Tag# FD# Description of Work Needed

1st 480 Label FD as Decommissioned 1st 1145 472 Damper is fire caulked – remove fire caulk 1st 1145 473 No Retaining Angle and Damper is fire caulked- install RA and remove caulk 1st 1145 474 No Retaining Angle and Damper is fire caulked- install RA and remove caulk 1st 1145 475 No Retaining Angle and Damper is fire caulked- install RA and remove caulk 1st 1145 476 No Retaining Angle and Damper is fire caulked- install RA and remove caulk & patch/paint drywall hole 1st 1145 479 Need 8’ Round access door, test damper, install retaining angle 1st 480 FD401-1-009 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

2nd 2189 Need FD401-2-004 Need Fire Damper, Access Panel, and access door installed. Test, tag, and document update.

2nd 2105a Need FD401-2-029 Need Fire Damper, Access Panel, and Access Door installed. Test, tag, and document update.

2nd 2100 Need FD401-2-030 Access Panel to shaft needed. Test, tag, and document update.

2nd 2124a Need FD401-2-027 Install Access Door and Access Panel. Test, tag, and document update.

2nd 2113 466 Install Access Door and Access Panel. Test, tag, and document update.

2nd 1c22b Need FD 401-2-025 Install Access Door and Access Panel. Test, tag, and document update.

2nd 2100 Need FD 401-2-028 Install Access Door and Access Panel. Test, tag, and document update.

2nd FD 401-2-005 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

2nd FD 401-2-006 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

2nd FD 401-2-007 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

2nd FD 401-2-008 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

2nd FD 401-2-009 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, 3rd 3124 454 Need Fire Damper, Access Panel, and access door installed. Test, tag, and document update.

3rd 3139 458 Need Fire Damper, Access Panel, and access door installed. Test, tag, and document update.

3rd 435 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

3rd 436 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

3rd 441 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

3rd 3219 488 Add T Bar to 2x4 Ceiling Grid to gain access, Install Access Door. Test, tag, and document update.

3rd 3229 492 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

3rd 3229 493 Install 12x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

3rd 3239a 495 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

3rd 3251 496 Install 12x12 Access Door, Install Retaining Angle, Test, tag, and document update.

3rd 3257 497 Install 12x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

3rd 3255a 498 Install 12x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

3rd 3277 500 Remove and relocate light fixture to gain access, Install 8x8 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update

3rd 3276 501 Install 12x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

3rd 3278a 502 Install 10x10 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

3rd 3264 504 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

3rd 3264 505 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2274a 506 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2c28 507 Install 12x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2269a 508 Install 14x14 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2292 509 Install 16x16 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2292a 510 Install 10x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2297 511 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2261 512 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2242 514 Install 12x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

2nd 2205a 530 Remove Ceiling grid, Test, tag, and document update, Create new access point.

1st 538 FD 402-1-007 Tag Damper as “Damper Decommissioned” and Current Date 1st None FD 402-1-016 Tag Damper as “Damper Decommissioned” and Current Date 1st 542 FD 402-1-011 Tag Damper as “Damper Decommissioned” and Current Date 1st 543 FD 402-1-012 Tag Damper as “Damper Decommissioned” and Current Date 1st 1251 534 FD 402-1-003 Replace Access Door with 12x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st 1229 535 Install 10x10 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st` 1265 536 Remove T bar, Install 12x12 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st 1264 537 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st 1274 539 Install 14x14 Access Door, R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st 1280 540 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st 1280 541 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st 1223 544 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st 1223 545 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

1st 1223 546 R&R retaining angle. Damper is fire caulked – remove fire caulk, Test, tag, and document update.

Attic 567 Fire Smoke Damper does not close, Actuator Functions, Clear obstructions, Replace

U bolt on shaft, Test, tag, and document update.

Attic 571 Fire Smoke Damper does not close, Actuator Functions, Clear obstructions, Replace

U bolt on shaft, Test, tag, and document update.

1st 5151 628 Fire Damper Caulked. Remove caulk, Test, tag, and document update.

1st 1540 FD 405 -1-007 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, and document update.

1st 1538 FD 405 -1-008 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag, 406 2nd Diagnose and repair up to10 faulty dampers and air supply line, test all associated dampers related to air handler 4.

408 2nd Diagnose and repair up to 6 dampers that are stuck in closed position associated with air handler 4.

3rd 3860 095 Install 12x12 Access Door. Install new Damper, Install new Access Panel. Test, tag,