RFQ: 36C25221Q0889

PAGE 1 OF

1. REQUISITION NO.

2. CONTRACT NO.

3. AWARD/EFFECTIVE DATE

4. ORDER NO.

5. SOLICITATION NUMBER

6. SOLICITATION ISSUE DATE

a. NAME

b. TELEPHONE NO. (No Collect Calls)

8. OFFER DUE DATE/LOCAL

TIME

9. ISSUED BY

CODE

10. THIS ACQUISITION IS

UNRESTRICTED OR

SET ASIDE:

% FOR:

SMALL BUSINESS

HUBZONE SMALL

BUSINESS

SERVICE-DISABLED

VETERAN-OWNED

SMALL BUSINESS

WOMEN-OWNED SMALL BUSINESS

(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED

SMALL BUSINESS PROGRAM

EDWOSB

8(A)

NAICS:

SIZE STANDARD:

11. DELIVERY FOR FOB DESTINA-

TION UNLESS BLOCK IS

MARKED

SEE SCHEDULE

12. DISCOUNT TERMS

13a. THIS CONTRACT IS A

RATED ORDER UNDER

DPAS (15 CFR 700)

13b. RATING

14. METHOD OF SOLICITATION

RFQ

IFB

RFP

15. DELIVER TO

CODE

16. ADMINISTERED BY

CODE

17a. CONTRACTOR/OFFEROR

CODE

FACILITY CODE

18a. PAYMENT WILL BE MADE BY

CODE

TELEPHONE NO.

DUNS:

DUNS+4:

PHONE:

FAX:

17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER 18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED

SEE ADDENDUM

19.

20.

21.

22.

23.

24.

ITEM NO.

SCHEDULE OF SUPPLIES/SERVICES

QUANTITY

UNIT

UNIT PRICE

AMOUNT

(Use Reverse and/or Attach Additional Sheets as Necessary)

25. ACCOUNTING AND APPROPRIATION DATA

26. TOTAL AWARD AMOUNT (For Govt. Use Only) 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED.

27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED

28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________

29. AWARD OF CONTRACT: REF. ___________________________________ OFFER

COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND

DATED ________________________________. YOUR OFFER ON SOLICITATION

DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY

(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE

ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED

SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:

30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER) 30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED

AUTHORIZED FOR LOCAL REPRODUCTION

(REV. 2/2012)

PREVIOUS EDITION IS NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.212

7. FOR SOLICITATION

INFORMATION CALL:

STANDARD FORM 1449

OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS

607-21-2-6969-0008 36C25221Q0889 07-01-2021

CHESAK, THOMAS

414-844-4813 07-09-2021

11:59 PM

CDT

36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee WI 53214-1476 X 334290 750 Employees N/A X 36C252

DEPARTMENT OF VETERANS AFFAIRS

WILLIAM S. MIDDLETON MVH

2500 OVERLOOK TERRACE

MADISON WI 53705-2286

36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee WI 53214-1476

Department of Veterans Affairs Financial Services Center PO Box 149971 Austin TX 78714-9971 877-353-9791 512-460-5540 See CONTINUATION Page

NURSE CALL SYSTEM FOR THE WILLIAM S. MIDDLETON MVH LOCATED

IN MADISON, WISCONSIN.

BRAND NAME ONLY.

SEE CONTINUATION PAGES

See CONTINUATION Page

607-3610162-6969-850100-2660-A1XXXX 010044158

X X

ONE

THOMAS H. CHESAK

VA-VHA-SAOC-2016-69A44B8A

Table of Contents

SECTION AError! Bookmark not defined.
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMSError! Bookmark not defined.
SECTION B - CONTINUATION OF SF 1449 BLOCKS4
B.1 CONTRACT ADMINISTRATION DATA4
B.2 STATEMENT OF WORK5
I. Background:5
II. Scope:5
III. Specific Tasks:7
IV. General:8
V. Equipment Cabinets:9
VI. Wiring Practice:9
VII. Cable Installation:11
VIII. Labeling:11
IX. Fireproofing:12
X. Grounding12
XI. Management Controls:12
XII. Contract Management:15
XIII. Basis of design is Ascom Telligence Nurse Call System:16
XIV. Deliverables:18
A. Contract Management Plan.18
XV. Performance Monitoring:18
XVI. Security Requirements:18
XVII. Packaging, Packing and Shipping Instructions:18
XVIII. Inspection and Acceptance Criteria:18
XIX. Risk Control:19
XX. Place of Performance:19
XXI. Terms of Warranty:19
XXII. Basis of Award:19
B.1 PRICE/COST SCHEDULE20
ITEM INFORMATIONError! Bookmark not defined.
B.2 DELIVERY SCHEDULE26
SECTION C - CONTRACT CLAUSES27
C.1 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL ITEMS (OCT 2018)27
C.2 VAAR 852.212-70 PROVISIONS AND CLAUSES APPLICABLE TO VA ACQUISITION OF COMMERCIAL ITEMS (APR 2020)32
C.3 VAAR 852.247-73 PACKING FOR DOMESTIC SHIPMENT (OCT 2018)34
C.4 52.204-13 SYSTEM FOR AWARD MANAGEMENT MAINTENANCE (OCT 2018)34
C.5 52.204-18 COMMERCIAL AND GOVERNMENT ENTITY CODE MAINTENANCE (AUG 2020)36
C.6 52.204-16 COMMERCIAL AND GOVERNMENT ENTITY CODE REPORTING (AUG 2020)37
C.7 52.232-40 PROVIDING ACCELERATED PAYMENTS TO SMALL BUSINESS SUBCONTRACTORS (DEC 2013)38
C.8 VAAR 852.212-71 GRAY MARKET ITEMS (APR 2020)38
C.9 52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR EXECUTIVE ORDERS—COMMERCIAL ITEMS (JAN 2021) (JUL 2020) (DEVIATION)39
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS47
SECTION E - SOLICITATION PROVISIONS48
E.1 52.212-1 INSTRUCTIONS TO OFFERORS—COMMERCIAL ITEMS (JUN 2020)48
E.2 52.204-7 SYSTEM FOR AWARD MANAGEMENT (OCT 2018)52
E.3 52.212-3 OFFEROR REPRESENTATIONS AND CERTIFICATIONS—COMMERCIAL ITEMS (FEB 2021) (JUL 2020) (DEVIATION)53

SECTION B - CONTINUATION OF SF 1449 BLOCKS

B.1 CONTRACT ADMINISTRATION DATA

(Continuation from Standard Form 1449, block 18A.)

1. Contract Administration: All contract administration matters will be handled by the following individuals:

A. CONTRACTOR:
(Contractor’s Name)

(Address) (City-State-Zip)

(Point of Contact / Title)

(Phone Number)
(E-Mail Address)

(DUNS Number) (Federal Tax ID)

B. GOVERNMENT:THOMAS CHESAK / CONTRACTING OFFICER
GREAT LAKES ACQUISITION CENTER
115 S. 84TH STREET, SUITE 101
MILWAUKEE, WI 53295

(414) 844-4813

THOMAS.CHESAK@VA.GOV

The Contracting Officer is the only person authorized to approve changes or modify any of the requirements under this contract. The Contractor shall communicate with the Contracting Officer on all matters pertaining to contract administration. Only the Contracting Officer is authorized to make commitment or issue changes that will affect price, quantity or quality of performance of this contract. In the event the Contractor effects any such change at the direction of any person other than the Contracting Officer, the change shall be considered to have been made without authority and no adjustment will be made in the contract price to cover any increase in cost incurred thereof.

2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:

[X] 52.232-33, Payment by Electronic Funds Transfer – System for Award Management.

3. INVOICES: Invoices shall be submitted in arrears in accordance with:

1. 852.232-72 ELECTRONIC SUBMISSION OF PAYMENT REQUESTS (NOV 2012).

1. UPON ACCEPTANCE OF ITEMS.

1. Reference PO IFCAP: 607-A1xxxx on all invoices to avoid delay in payment.

4. GOVERNMENT INVOICE ADDRESS: All invoices from the contractor shall be submitted electronically in accordance with 852.232-72 ELECTRONIC SUBMISSION OF PAYMENT REQUESTS (NOV 2012).

FACSIMILE, E-MAIL, AND SCANNED DOCUMENTS ARE NOT ACCEPTABLE FORMS OF SUBMISSION FOR PAYMENT REQUESTS

For assistance setting up e-Invoice, the below information is provided:

* Vendors must register online at http://www.tungsten-network.com/veteransaffairs/

* Tungsten Network Setup Information: 1-866-340-4980

* Tungsten Network email: VA.Registration@tungsten-network.com

* FSC Vendor Support Section Contact: 1-877-353-9791

* FSC Vendor Support Section email: vafsccshd@va.gov Vendors can inquire on the status of payments by accessing the Vendor Inquiry System (VIS) at: https://www.vis.fsc.va.gov/login.aspx?ReturnUrl=%2fDefault.aspx

B.2 STATEMENT OF WORK

I. Background:

The Nurse Call System at the William S. Middleton Memorial Veterans Hospital (Madison VA) in Madison, Wisconsin is a vital communication method in patient care areas. The previous Executone system in this area is no longer supported for service or parts. All cabling and equipment shall be removed in this project. There will be additional procedure and recovery rooms available when expansion is complete.

II. Scope:

A. The contractor shall:

1. Provide design, engineer, furnish, install, connect complete, test, certify and guarantee the new Code Blue/nurse call system for the 4A Medical Unit located on the 4th floor of A-wing. This contractor shall remove the existing nurse call devices, cabling, and headend equipment that was used for this system.

2. This project will include a new patient/staff signaling devices for 20 patient bed locations within the 4A area and required head-end equipment to operate these and future devices in this wing.

3. Provide materials and equipment to install a complete nurse system that seamlessly ties into our existing ASCOM Telligence Nurse Call System. This system currently exists on the 8th floor (ICU), 7B and 6A with head-end software which resides in the 9th floor rack. Code blue signals from this system are displayed/annunciated at the Switchboard that is in Building 2.

4. Utilize all existing pull and back boxes from the previous existing installation where possible. If existing raceways will not be adequate, install cables free air in j-hook cable supports.

B. Contractor qualifications include:

1. The Original Equipment Manufacturer (OEM) shall have had experience with three (3) or more installations of Nurse Call systems of comparable size and interfacing complexity with regards to type and design as specified herein. Each of these installations shall have performed satisfactorily for at least one (1) year after final acceptance by the user.

**Include the names, locations and point of contact for these installations as a part of the submittal

2. The Contractor shall submit certified documentation that they have been an authorized distributor and service organization for the Original Equipment Manufacturer (OEM) for a minimum of three (3) years. The Contractor shall be authorized by the OEM to pass thru the OEM’s warranty of the installed equipment to VA. In addition, the OEM and Contractor shall accept complete responsibility for the design, installation, certification, operation, and physical support for the System.

**This documentation, along with the System Contractor and OEM certifications must be provided in writing as part of the Contractor’s Technical submittal.

3. The Contractor’s Communications Technicians assigned to the System shall be fully trained, qualified, and certified by the OEM on the engineering, installation, operation, and testing of the System. The Contractor shall provide a Lead OEM certified Technician that shall lead/train other in house technicians.

4. The Contractor shall display all applicable national, state and local licenses.

5. The Contractor shall submit copy (s) of Certificate of successful completion of OEM’s installation/training school for installing technicians of the System’s Nurse Call and/or Code Blue equipment being proposed.

C. The installation shall comply fully with all governing authorities, laws and ordinances, regulations, codes, and standards, including, but not limited to:

1. United States Federal Law:

a. Departments of:

1) Commerce, Consolidated Federal Regulations (CFR), Title 15 – Under the Information Technology Management Reform Act (Public Law 104-106), the Secretary of Commerce approves standards and guidelines that are developed by the:

a) Chapter II, National Institute of Standards Technology (NIST – formerly the National Bureau of Standards). Under Section 5131 of the Information Technology Management Reform Act of 1996 and the Federal Information Security Management Act of 2002 (Public Law 107-347), NIST develops

– Federal Information Processing Standards Publication (FIPS) 140-2—Security Requirements for Cryptographic Modules.

b) Chapter XXIII, National Telecommunications and Information Administration (NTIA – aka ‘Red Book’) Chapter 7.8 / 9; CFR, Title 47 Federal communications Commission (FCC) Part 15, Radio Frequency Restriction of Use and Compliance in “Safety of Life” Functions & Locations.

2) Health, (Public Law 96-88), CFR, Title 42, Chapter IV Health & Human Services, CFR, Title 46, Subpart 1395(a)(b) JCAHO “a hospital that meets JCAHO accreditation is deemed to meet the Medicare conditions of Participation by meeting Federal Directives:”

a) All guidelines for Life, Personal and Public Safety; and, Essential and Emergency Communications.

3) Labor, CFR, Title 29, Part 1910, Chapter XVII - Occupational Safety and Health Administration (OSHA), Occupational Safety and Health Standard:

a) Subpart 7 - Definition and requirements (for a NRTL – 15 Laboratory’s, for complete list, contact (http://www.osha.gov/dts/otpca/nrtl/faq_nrtl.html):

1) UL:

a) 65 – Standard for Wired Cabinets.

b) 83-03 – Standard for Thermoplastic-Insulated Wires and Cables.

c) 467-01 – Standard for Electrical Grounding and Bonding Equipment

d) 468 – Standard for Grounding and Bonding Equipment.

e) 486A-01 – Standard for Wire Connectors and Soldering Lugs for Use with Copper Conductors

f) 486C-02 – Standard for Splicing Wire Connectors.

g) 514B-02 – Standard for Fittings for Cable and Conduit.

h) 1069 – Hospital Signaling and Nurse Call Equipment.

i) 1449 – Standard for Transient Voltage Surge Suppressors.

j) 1479-03 – Standard for Fire Tests of Through- Penetration Fire Stops.

k) 1666 – Standard for Wire/Cable Vertical (Riser) Tray Flame Tests.

l) 1863 – Standard for Safety, Communications Circuits Accessories.

m) 60950-1/2 – Information Technology Equipment – Safety.

2) Canadian Standards Association (CSA): same tests as for UL.

3) Communications Certifications Labatory (CCL): same tests as for UL.

4) Intertek Testing Services NA, Inc. (ITSNA formerly Edison Testing Labatory [ETL]): same tests as for UL.

b) Subpart 35 – Compliance with NFPA 101 – Life Safety Code.

c) Subpart 36 - Design and construction requirements for exit routes.

d) Subpart 268 - Telecommunications.

e) Subpart 305 - Wiring methods, components, and equipment for general use.

4) Veterans Affairs (Public Law No. 100-527), CFR, Title 38, Volumes I & II:

a) Office of Telecommunications:

1) Handbook 6100 – Telecommunications.

a) Spectrum Management FCC & NTIA Radio Frequency Compliance and Licensing Program.

b) Special Communications Proof of Performance Testing, VACO Compliance and Life Safety Certification(s).

c) Office of Cyber and Information Security (OCIS):

1) Handbook 6500 - Information Security Program.

2) Wireless and Handheld Device Security Guideline Version 3.2, August 15, 2005.

a) VA’s National Center for Patient Safety – Veterans Health Administration Warning System, Failure of Medical Alarm Systems using Paging Technology to Notify Clinical Staff, July 2004.

2. National Codes:

a. American Institute of Architects (AIA): Guidelines for Healthcare Facilities.

b. American National Standards Institute/Electronic Industries Association/Telecommunications Industry Association (ANSI/EIA/TIA):

1) 568-B - Commercial Building Telecommunications Wiring Standards:

a) B-1 – General Requirements.

b) B-2 – Balanced twisted-pair cable systems.

c) B-3 - Fiber optic cable systems.

2) 569 - Commercial Building Standard for Telecommunications Pathways and Spaces.

3) 606 – Administration Standard for the Telecommunications Infrastructure of Communications Buildings.

4) 607 – Commercial Building Grounding and Bonding Requirements for Telecommunications.

5) REC 127-49 – Power Supplies.

6) RS 270 – Tools, Crimping, Solderless Wiring Devices, Recommended Procedures for User Certification.

c. American Society of Mechanical Engineers (ASME):

1) Standard 17.4 – Guide for Emergency Personnel.

2) Standard 17.5 – Elevator & Escalator Equipment (prohibition of installing non-elevator equipment in Elevator Equipment Room / Mechanical Penthouse).

d. American Society of Testing Material (ASTM):

1) D2301-04 - Standard Specification for Vinyl Chloride Plastic Pressure Sensitive Electrical Insulating Tape.

e. Building Industries Communications Services Installation (BICSI):

1) All standards for smart building wiring, connections and devices for commercial and medical facilities.

2) Structured Building Cable Topologies.

3) In consort with ANSI/EIA/TIA.

f. Institute of Electrical and Electronics Engineers (IEEE):

1) C62.41 – Surge Voltages in Low-Voltage AC Power Circuits.

g. NFPA:

1) 70 - National Electrical Code (current date of issue) – Articles 517, 645 & 800.

2) 77 – Recommended Practice on Static Electricity.

3) 99 - Healthcare Facilities.

4) 101 - Life Safety Code.

5. Accreditation Organization(s):

a. Joint Commission on Accreditation of Hospitals Organization (JCAHO) – Section VI, Part 3a – Operating Features.

III. Specific Tasks:

A. Codes and Permits:

1. Provide all necessary permits and schedule all inspections as identified in the contract’s milestone chart, so that the system is proof of performance tested, certified and approved by VA and ready for operation on a date directed by the Madison VA..

2. The contractor is responsible to adhere to all codes described herein and associated contractual, state, and local codes.

B. Scheduling:

1. After the award of contract, the Contractor shall prepare a detailed schedule (aka milestone chart) using “Microsoft Project” software or equivalent. The Contractor Project Schedule (CPS) shall indicate detailed activities for the projected life of the project. The CPS shall consist of detailed activities and their restraining relationships. It will also detail manpower usage throughout the project.

2. It is the responsibility of the Contractor to coordinate all work with the other trades for scheduling, rough-in, and finishing all work specified. The Madison VA will not be liable for any additional costs due to missed dates or poor coordination of the supplying contractor with other trades.

C. Review of contract drawings and equipment data submittals (aka technical submittals):

(Note: The Contractor is encouraged, but not required, to submit separate technical submittal(s) outlining alternate technical approach(s) to the system requirements stated here-in as long as each alternate technical document(s) is complete, separate, and submitted in precisely the same manner as outlined herein. VA will review and rate each received alternate submittal, which follows this requirement, in exactly the same procedure as outlined herein. Partial, add-on, or addenda type alternates will not be accepted or reviewed.)

1. Submit at one time within 21 days of contract awarding, drawings and product data on all proposed equipment and system. Check for compliance with contract documents and certify compliance with Contractor's "APPROVED" stamp and signature.

2. Support all submittals with descriptive materials, i.e., catalog sheets, product data sheets, diagrams, and charts published by the manufacturer. These materials shall show conformance to specification and drawing requirements.

3. Where multiple products are listed on a single cut-sheet, circle or highlight the one that you propose to use. Provide a complete and through equipment list of equipment expected to be installed in the system, with spares, as a part of the submittal. Special Communications (TVE-005OP3B) will not review any submittal that does not have this list.

4. Provide four (4) copies to the VA Project Manager for technical review. The VA Project Manager will provide a copy to the offices identified in Paragraph 1.3.C, at a minimum for compliance review as described herein where each responsible individual(s) shall respond to the VA Project Manager within 10 days of receipt of their acceptance or rejection of the submittal(s).

5. Surveys Required as a Part of The Technical Submittal:

a. The Contractor shall provide the following System surveys that depict various system features and capacities required in addition to the on-site survey requirements described herein. Each survey shall be in writing and contain the following information (the formats are suggestions and may be used for the initial Technical Submittal Survey requirements), as a minimum:

i. Nurse Call Cable System Design Plan:

An OEM and contractor designed functioning Nurse Call System cable plan to populate the entire empty conduit/pathway distribution systems provided as a part of Specification 27 11 00 shall be provided as a part of the technical proposal. A specific functioning Nurse Call: cable, interfaces, J-boxes and back boxes shall coincide with the total growth items as described herein. It is the Contractor’s responsibility to provide the Systems’ entire Nurse Call cable and accessory requirements and engineer a functioning Nurse Call distribution system and equipment requirement plan for the devices and stations indicated on the drawings.

6. Installation - Install new Nurse Call system within current conduit raceways. Utilize all existing pull and back boxes from the previous existing installation where possible.

IV. General:

A. Execute work in accordance with National, State, and local codes, regulations, and ordinances.

B. Install work neatly, plumb, and square and in a manner consistent with standard industry practice. Carefully protect work from dust, paint and moisture as dictated by site conditions. The Contractor will be fully responsible for protection of his work during the construction phase up until final acceptance by the Madison VA.

C. Install equipment according to OEM’s recommendations. Provide any hardware, adaptors, brackets, rack mount kits or other accessories recommended by OEM for correct assembly and installation.

D. Secure equipment firmly in place, including receptacles, speakers, equipment racks, system cables, etc.

1. All supports, mounts, fasteners, attachments, and attachment points shall support their loads with a safety factor of at least 5:1.

2. Do not impose the weight of equipment or fixtures on supports provided for other trades or systems.

3. Any suspended equipment or associated hardware must be certified by the OEM for overhead suspension.

4. The Contractor is responsible for means and methods in the design, fabrication, installation and certification of any supports, mounts, fasteners, and attachments.

E. Finishes for any exposed work such as plates, racks, panels, speakers, etc. shall be approved by the Architect, Madison VA and TVE 005OP3B.

F. Coordinate cover plates with field conditions. Size and install cover plates as necessary to hide joints between back boxes and surrounding wall. Where cover plates are not fitted with connectors, provide grommeted holes in size and quantity required. Do not allow cable to leave or enter boxes without cover plates installed.

G. Active electronic component equipment shall consist of solid-state components, be rated for continuous duty service, comply with the requirements of FCC standards for telephone and data equipment, systems, and service.

H. Color code all distribution wiring to conform to the Nurse Call Industry Standard, EIA/TIA, and this document, whichever is the more stringent. At a minimum, all equipment, enclosures, wiring, terminals, and cables shall be clearly and permanently labeled according to and using the provided record drawings, to facilitate installation and maintenance.

I. Connect the System’s primary input AC power to the Facility’ Critical Branch of the Emergency AC power distribution system as shown on the plans or if not shown on the plans consult with VA Project Manager regarding a suitable circuit location prior to bidding.

V. Equipment Cabinets:

A. Provide security covers for all devices not requiring routine operator control.

B. Provide vent panels and cooling fans as required for the operation of equipment within the OEM' specified temperature limits. Provide adequate ventilation space between equipment for cooling. Follow manufacturer’s recommendations regarding ventilation space between amplifiers.

C. Ensure a minimum of 36 inches in front of each cabinet to comply with OSHA Safety Standards.

D. Install Nurse Call head-end equipment in Data Closet B4110A; utilizing existing data racks.

VI. Wiring Practice:

In addition to the MANDATORY infrastructure requirements outlined in VA Construction Specifications 27 10 00 – TIP Structured Communications Cabling, 27 11 00, the following additional practices shall be adhered too:

A. Execute all wiring in strict adherence to the National Electrical Code, applicable local building codes and standard industry practices.

B. Do not splice wiring anywhere along the entire length of the run. Make sure cables are fully insulated and shielded from each other and from the raceway for the entire length of the run.

C. Do not pull wire through any enclosure where a change of raceway alignment or direction occurs. Do not bend wires to less than radius recommended by manufacturer.

D. Replace the entire length of the run of any wire or cable that is damaged or a braided during installation. There are no acceptable methods of repairing damaged or a braided wiring.

E. Use wire pulling lubricants and pulling tensions as recommended by the OEM.

F. Use grommets around cut-outs and knock outs where conduit or chase nipples are not installed.

G. Do not use tape-based or glue-based cable anchors.

H. Field wiring entering equipment cabinets shall be terminated as follows:

1. Provide OEM directed service loops at harness break outs and at plates, panels, and equipment. Loops should be sufficient to allow plates, panels, and equipment to be removed for service and inspection.

2. Line level and speaker level wiring may be terminated inside the equipment rack using specified terminal blocks (see “Products.”) Provide 15% spare terminals inside each rack. Microphone level wiring may only be terminated at the equipment served.

3. Employ permanent strain relief for any cable with an outside diameter of 1” or greater.

I. Make all connections as follows:

1. For crimp-type connections, use only tools that are specified by the manufacturer for the application.

2. Use only insulated spade lugs on screw terminals. Spade lugs shall be sized to fit the wire gauge. Do not exceed two lugs per terminal.

3. Wire nuts, electrical tape or “Scotch Lock” connections are not acceptable for any application.

J. Noise filters and surge protectors shall be provided for each equipment interface cabinet, switch equipment cabinet, control console, local, and remote active equipment locations to ensure protection from input primary AC power surges and noise glitches are not induced into low Voltage data circuits.

I. Wires or cables to be installed outside of conduit, cable trays, wireways, cable duct, etc:

1. Only when specifically authorized as described herein, will wires or cables be identified and approved to be installed outside of conduit. The wire or cable runs shall be OEM CMR rated.

2. Wires and cables shall be hidden, protected, fastened and tied at 1200 mm (48 in.) intervals, maximum, as described herein to building structure and where accessibility allows.

3. Closer wire or cable fastening intervals may be required to prevents sagging, maintain clearance above suspended ceilings, remove unsightly wiring and cabling from view and discourage tampering and vandalism. Wire or cable runs, not provided in conduit that penetrate outside building walls, supporting walls, and two hour fire barriers shall be sleeved and sealed with an approved fire retardant sealant.

4. Wire or cable runs to system components installed in walls (i.e.: volume attenuators, circuit controllers, signal, or data outlets, etc.) may, when specifically authorized by the RE, be fished through hollow spaces in walls.

5. Completely test all of the cables after installation and replace any defective cables.

6. Wires or cables that are installed outside of buildings shall be in conduit, secured to solid building structures. If specifically approved, on a case by case basis, to be run outside of conduit, the wires or cables shall be installed, as described herein. The bundled wires or cables must: Be tied at not less than 460 mm (18 in.) intervals to a solid building structure; have ultra violet protection and be totally waterproof (including all connections). The laying of wires or cables directly on roof tops, ladders, drooping down walls, walkways, floors, etc. is not allowed and will not be approved.

VII. Cable Installation:

Cable Installation - In addition to the mandatory infrastructure requirements outlined in VA Construction Specifications 27 10 00 – Structured Cabling, the following additional practices shall be adhered to:

A. Support cable on maximum 4’-0” centers. Acceptable means of cable support are cable tray, j-hooks, and bridal rings. Velcro wrap cable bundles loosely to the means of support with plenum rated Velcro straps. Plastic tie wraps are not acceptable as a means to bundle cables.

B. Run cables parallel to walls.

C. Install maximum of 40 cables in a single row of J-hooks. Provide necessary rows of J-hooks as required by the number of cables.

D. Do not lay cables on top of light fixtures, ceiling tiles, mechanical equipment, or ductwork. Maintain at least 2’-0” clearance from all shielded electrical apparatus where accessibility allows.

E. All cables shall be tested after the total installation is fully complete. All test results are to be documented. All cables shall pass acceptable test requirements and levels. Contractor shall remedy any cabling problems or defects in order to pass or comply with testing. This includes the re-pull of new cable as required at no additional cost to the Madison VA.

F. Ends of cables shall be properly terminated on both ends per industry and OEM’s recommendations.

G. Provide proper temporary protection of cable after pulling is complete before final dressing and terminations are complete. Do not leave cable lying on floor. Bundle and tie wrap up off of the floor until you are ready to terminate.

H. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at outlets and terminals.

I. Splices, Taps, and Terminations: Arrange on numbered terminal strips in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures. Cables may not be spliced.

J. Bundle, lace, and train conductors to terminal points without exceeding OEM's limitations on bending radii. Install lacing bars and distribution spools.

K. Cold-Weather Installation: Bring cable to room temperature before de-reeling. Heat lamps shall not be used.

L. Cable shall not be run through structural members or be in contact with pipes, ducts, or other potentially damaging items.

VIII. Labeling:

Provide labeling in accordance with ANSI/EIA/TIA-606-A. All lettering for Nurse Call and/or Code Blue circuits shall be stenciled using laser printers.

A. Cable and Wires (Hereinafter referred to as “Cable”): Cables shall be labeled at both ends in accordance with ANSI/EIA/TIA-606-A. Labels shall be permanent in contrasting colors. Cables shall be identified according to the System “Record Wiring Diagrams.”

B. Equipment: System equipment shall be permanently labeled with contrasting plastic laminate or Bakelite material. System equipment shall be labeled on the face of the unit corresponding to its source.

1. Clearly, consistently, logically and permanently mark switches, connectors, jacks, relays, receptacles and electronic and other equipment.

2. Engrave and paint fill all receptacle panels using 1/8” (minimum) high lettering and contrasting paint.

3. For rack-mounted equipment, Label the front and back of all rack-mounted equipment.

C. Where multiple pieces of equipment reside in the same rack group, clearly and logically label each indicating to which room, channel, receptacle location, etc. they correspond.

D. Permanently label cables at each end, including intra-cabinet connections. Labels shall be covered by the same, transparent heat- shrink tubing covering the end of the overall jacket. Alternatively, computer generated labels of the type which include a clear protective wrap may be used.

E. Contractor’s name shall appear no more than once on each continuous set of racks. The Contractor’s name shall not appear on wall plates or portable equipment.

F. Ensure each OEM supplied item of equipment has appropriate UL Labels Marks for the service the equipment is performed permanently attached or marked to a non-removal board in the unit. Equipment installed not bearing these UL marks will not be allowed to be a part of the system. The contractor shall bear all costs required to provide replacement equipment with approved UL marks.

IX. Fireproofing:

A. Where Nurse Call and/or Code Blue wires, cables and conduit penetrate fire rated walls, floors and ceilings, fireproof the opening.

B. Provide conduit sleeves (if not already provided by electrical contractor) for cables that penetrate fire rated walls and Telecommunications Rooms floors and ceilings. After the cabling installation is complete, install fire proofing material in and around all conduit sleeves and openings. Install fire proofing material thoroughly and neatly. Seal all floor and ceiling penetrations.

C. Use only materials and methods that preserve the integrity of the fire stopping system and its rating.

X. Grounding A. Ground Nurse Call and/or Code Blue equipment to eliminate shock hazard and to minimize ground loops, common mode returns, noise pickup, cross talk, and other impairments.

B. Do not use “3rd or 4th” wire internal electrical system conductors for communications signal ground.

C. Do not connect the signal ground to the building’s external lightning protection system.

D. Do Not “mix grounds” of different systems. All 120V power shall be provided for system head-end equipment prior to nurse call system installation.

XI. Management Controls:

A. Integration Management Control Planning:

1. The Contractor shall continually employ interfacing methods that are approved by the OEM and VA. At a minimum, an acceptable interfacing method requires not only a physical and mechanical connection, but also a matching of signal, voltage, and processing levels with regard to signal quality and impedance. The interface point must adhere to all standards described herein for the full separation of Critical Care and Life Safety systems.

2. The System Contractor shall connect the System ensuring that all NFPA and UL Critical Care and Life Safety Circuit and System separation guidelines are satisfied. The System Contractor is not allowed to make any connections to the Telephone System. VA shall arrange for the interconnection between the MATV and Patient Bed Service Walls Systems with the appropriate responsible parties. System hardware shall consist of a nurse call/Code Blue patient communications network comprised of nurse consoles, control stations, staff and duty stations, room and corridor dome lights, pillow speakers/call cords, pull cord and/or emergency push button stations, and wiring. The system shall be provided with the hardware and software for staff locator devices. All necessary equipment required to meet the intent of these specifications, whether or not enumerated within these specifications, shall be supplied and installed to provide a complete and operating nurse call/Code Blue patient communications network. It is not acceptable to utilize the telephone cable system for the control and distribution of nurse call (code Blue) signals and equipment.

3. The System is defined as Critical Service and the Code Blue functions is defined as Life Safety/Support by NFPA (re Part 1.1.A) and so evaluated by JCAHCO.

B. Intermediate Testing:

1. After completion of 30 – 40% of the installation of a head end cabinet(s) and equipment, one master stations, local and remote stations, and prior to any further work, this portion of the system must be pretested, inspected, and 1certified. Each item of installed equipment shall be checked to ensure appropriate UL Listing and Certification Labels are affixed as required by NFPA - Life Safety Code 101-3.2 (a) & (b), UL Nurse Call Standard 1069 and JCAHCO evaluation guidelines, and proper installation practices are followed. The intermediate test shall include a full operational test.

2. All inspections and tests shall be conducted by an OEM-certified contractor representative and witnessed by TVE-005OP3B if there is no local Government Representative that processes OEM and VA approved Credentials to inspect and certify the system. The results of the inspection will be officially recorded by the Government Representative and maintained on file by the Point of Contact (PoC)/COR, until completion of the entire project. The results will be compared to the Acceptance Test results. An identical inspection may be conducted between the 65 - 75% of the system construction phase, at the direction of the Point of Contact (PoC)/COR.

C. Pretesting:

1. Upon completing installation of the Nurse Call and/or Code Blue System, the Contractor shall align, balance, and completely pretest the entire system under full operating conditions.

2. Pretesting Procedure:

a. During the System Pretest the Contractor shall verify (utilizing approved test equipment) that the System is fully operational and meets all the System performance requirements of this standard.

b. The Contractor shall pretest and verify that all PSM System functions and specification requirements are met and operational, no unwanted aural effects, such as signal distortion, noise pulses, glitches, audio hum, poling noise, etc. are present. At a minimum, each of the following locations shall be fully pretested:

1) Central Control Cabinets.

2) Nurse Control Stations.

a) Master Stations

b) Patient Stations w/ code blue, staff assist, emergency and cancellation buttons.

c) Lavatory pull cord stations

3) Dome Lights.

a) Corridors

4) Electrical Supervision Panels/Functions/locations.

5) All Networked locations.

6) System interface locations (i.e. wireless, PA, telephone, etc.).

7) System trouble reporting.

8) System electrical supervision.

3. The Contractor shall provide four (4) copies of the recorded system pretest measurements and the written certification that the System is ready for the formal acceptance test shall be submitted to the Point of Contact (PoC)/COR.

D. Acceptance Test:

1. After the Nurse Call and/or Code Blue System has been pretested and the Contractor has submitted the pretest results and certification to the Point of Contact (PoC)/COR, then the Contractor shall schedule an acceptance test date and give the VA Project Manager 15 working days written notice prior to the date the acceptance test is expected to begin. The System shall be tested in the presence of a TVE 005OP3B and OEM certified representatives. The System shall be tested utilizing the approved test equipment to certify proof of performance and Life Safety / Critical Service compliance. The tests shall verify that the total System meets all the requirements of this specification. The notification of the acceptance test shall include the expected length (in time) of the test.

2. The acceptance test shall be performed on a "go-no-go" basis. Only those operator adjustments required to show proof of performance shall be allowed. The test shall demonstrate and verify that the installed System does comply with all requirements of this specification under operating conditions. The System shall be rated as either acceptable or unacceptable at the conclusion of the test. Failure of any part of the System that precludes completion of system testing, and which cannot be repaired in four (4) hours, shall be cause for terminating the acceptance test of the System. Repeated failures that result in a cumulative time of eight (8) hours to affect repairs shall cause the entire System to be declared unacceptable.

3. Retesting of the entire System shall be rescheduled at the convenience of the Government and costs borne by the Contractor at the direction of the Point of Contact (PoC)/COR.

E. Acceptance Test Procedure:

1. Physical and Mechanical Inspection:

a. The Nurse Call and Hospital Representative will tour all major areas where the Nurse Call and/or Code Blue System and all sub-systems are completely and properly installed to insure they are operationally ready for proof of performance testing. A system inventory including available spare parts will be taken at this time. Each item of installed equipment shall be checked to ensure appropriate UL certification labels are affixed.

b. The System diagrams, record drawings, equipment manuals, TIP Auto CAD Disks, intermediate, and pretest results shall be formally inventoried and reviewed.

c. Failure of the System to meet the installation requirements of this specification shall be grounds for terminating all testing.

2. Operational Test:

a. After the Physical and Mechanical Inspection, the central terminating and nurse call master control equipment shall be checked to verify that it meets all performance requirements outlined herein. A spectrum analyzer and sound level meter may be utilized to accomplish this requirement.

b. Following the central equipment test, a pillow speaker (or on board speaker) shall be connected to the central terminating and nurse call master control equipment’s output tap to ensure there are no signal distortions such as intermodulation, data noise, popping sounds, erratic system functions, on any function.

c. The distribution system shall be checked at each interface, junction, and distribution point, first, middle, and last intersectional, room, and bed dome light in each leg to verify that the nurse call distribution system meets all system performance standards.

d. Each MATV outlet that is controlled by a nurse call pillow speaker shall be functionally tested at the same time utilizing the Contractor’s approved hospital grade HDTV receiver and TV remote control cable.

e. Additionally, each installed emergency, patient, staff, duty, intersectional, room, and bed dome light, power supply, code one, and remote annunciator panels shall be checked insuring they meet the requirements of this specification.

f. Once these tests have been completed, each installed sub-system function shall be tested as a unified, functioning and fully operating system. The typical functions are: nurse follower, three levels of emergency signaling (i.e. flashing red emergency, flashing white patient emergency, flashing white or combination lights for staff emergency, separate flashing code blue), minimum of 10 minutes of UPS operation, memory saving, minimum of ten station audio paging, canceling emergency calls at each originating station only, and storage and prioritizing of calls.

g. Individual Item Test: The TVE 005OP3B Representative will select individual items of equipment for detailed proof of performance testing until 100% of the System has been tested and found to meet the contents of this specification. Each item shall meet or exceed the minimum requirements of this document.

3. Test Conclusion:

a. At the conclusion of the Acceptance Test, using the generated punch list (or discrepancy list) the VA and the Contractor shall jointly agree to the results of the test, and reschedule testing on deficiencies and shortages with the Point of Contact (PoC)/COR. Any retesting to comply with these specifications will be done at the Contractor's expense.

b. If the System is declared unacceptable without conditions, all rescheduled testing expenses will be borne by the Contractor.

F. Acceptable Test Equipment:

1. The test equipment shall be furnished by the Contractor shall have a calibration tag of an acceptable calibration service dated not more than 12 months prior to the test.

2. All nurse call and Code Blue functions shall be annunciated at nurse stations. Additional annunciation shall be at all duty/staff stations indicated on the contract documents.

3. All calls originated from patient stations, either from the pillow speaker or call button on the station, shall communicate with both nurse stations.

4. The System shall be delivered free of engineering, manufacturing, installation, and functional defects. It shall be designed, engineered, and installed for ease of operation, maintenance, and testing.

5. System firmware shall be the product of a reputable firmware OEM of record with a proven history of product reliability and sole control over all source code.

XII. Contract Management:

A. Throughout progress of the Work, maintain an accurate record of changes in Contract Documents. Vendor shall work with the VA provided electrical contractor to coordinate conduit placement. Upon completion of Work, transfer as-built records and changes to a set of Project Record Documents.

B. The floor plans shall be marked in pen to include the following:

1. Each device specific locations.

2. Conduit locations.

3.Each interface and equipment specific location.

4. Head-end equipment and specific location.

5. Wiring diagram.

6. Labeling and administration documentation.

7. Warranty certificate.

8. System test results.

C. The Contractor shall warrant the installation to be free from defect in material and workmanship for a period of one (1) year from the date of acceptance of the project by the Madison VA. The Contractor shall agree to remedy covered defects within four (4) hours of notification of major failures or within twenty-four (24) hours of notification for individual station related problems.

1. At a minimum, each distribution, interconnection, interface, terminating point and TCO shall be capable of supporting the Facility’s Nurse Call and/or Code Blue System voice and data service as follows:

a. Shall be compliant with and not degrade the operating parameters of the Public Switched Telephone Network (PSTN) and the Federal Telecommunications System (FTS) at each PSTN and FTS interface, interconnection and TCO terminating locations detailed on the contract drawings.

b. The System shall provide the following minimum operational functions:

1) Code Blue calls shall be cancelable at the calling station only. The nurse call master stations that manage Code Blue functions shall not have the ability to cancel Code Blue calls.

2) Calls placed from any Code Blue station shall generate Code Blue emergency type audible and visual signals at each associated nurse control and duty station, respective dome lights and all local and remote annunciator panels. Calls placed from a bedside station shall generate emergency type visual signals at the bedside station and associated corridor light in addition to the previous stated stations and panels.

3) Activating the silencing device at any location, while a Code Blue call or system fault is occurring shall mute the audible signals at the alarm location.

a) The audible alarm shall regenerate at the end of the selected time-out period until the call or fault is corrected.

b) The visual signals shall continue until the call is canceled and/or a fault is corrected. When the fault is corrected, all signals generated by the fault shall automatically cease, returning the System to a standby status.

c) Audible signals shall be regenerated in any local or remote annunciator panel that is in the silence mode, in the event an additional Code Blue call is placed in any Code Blue system.

d) The additional Code Blue call shall also generate visual signals at all annunciators to identify the location of the call.

2. Each System Nurse Call location shall generate a minimum of distinct calls:

a. Routine: white flashing dome lights & master station color and audio tone,

b. Staff Assist/ Bathroom Assist: rapid white flashing dome lights & master station color and audio tone,

c. Emergency: Red flashing dome lights & master station color and audio tone,

d. Code Blue: Blue flashing dome lights and master station color and audio tone,

e. Each generated call shall be cancelable at ONLY the originating location.

D. The Facility’s LAN/WAN is not allowed for Nurses Call/Code Blue main wiring / function that must be a “stand alone primary cable infrastructure” as described herein.

E. Connections to the VA LAN/WAN for functional or operable conditions shall be allowed ONLY when the LAN/WAN system has been demonstrated and NFPA (at a minimum by TVE-005OP3B) Certified meeting Life Safety Standards.

XIII. Basis of design is Ascom Telligence Nurse Call System:

A. Contractor is responsible for pricing all accessories and miscellaneous equipment required to form a complete and operating system. The equipment provided herein shall be as indicated on the drawings except for the indicated spare equipment.

1 HC-PC-DSK2-7 Nurse Station IR Listview PC 1 NGTELL62-S 6.2 base system bridge software 5 NGCISCO8-H head-end IP data switch 1 NGTDSPA-H nurse station staff console 29 NUDL4S-H 4-section LED corridor light 22 NUPSTN-H single patient station 22 NUIAUX2-HU dual Aux station 22 NUBAC37-H 37-pin break-away bed connector cable 22 NUHSDADVEP-H pillow speaker 22 NUDM3-HU customizable 3-button code blue / staff emergency call station 44 NUQIJA-H ¼’’ jack adapter 44 NUPC3-HU pull for help lavatory & shower station 8 NUDUTY-HU smart-enhanced staff / duty station 20 NGWDSP-HU VoIP ColorTouch Staff / Workflow station 1 VER-2037 IR system concentrator plus 1 VER-2407 IR system collector 48 VER-4432 IR system ceiling sensor 1 VER-0005 IR system badge tester 60 VER-1954 IR system badge (30RN & 30 CNA badges)

B. Corridor Dome Lights.

1. Four (4) lamps.

2. Lamp colors available shall be white, green, yellow, blue, and red.

3. Lamp sockets shall be plug-in type connections.

4. Dome shall be easily removable to facilitate lamp replacement.

5. Mount in dual gang back box.

C. Pull-Cord / Emergency Stations.

1. Pull-cord / Emergency Stations. When device is mounted in toilet locations, the enclosed watertight gasket shall be installed. Also included:

a. 10’ nylon cord with solid plastic pendant at the end of the cord. Lamp shall flash when call is registered. Cut cord to desired length.

b. LED light on faceplate.

c. Cancel button on faceplate.

d. Calls initiated in…