36C25220Q0070-003.pdf

PDF 380 KB Posted

Attached to
TEST & BALANCE CRITICAL CARE AREA AIR BASE + 4 OYS
Solicitation number
36C25220Q0070
Issued by

About this file

This document contains test and balance reports for the VA Hospital fifth floor electrophysiology lab air handling unit system. The mechanical contractor Accustar Air Balance performed air distribution testing and balancing to optimize system performance. Testing was conducted in accordance with TABB procedures and included air change and room pressure tests, as well as air distribution terminal flow measurements to verify design air volumes and velocities. The related federal contract opportunity is a solicitation from the Department of Veterans Affairs for test and balance services at the VA Medical Center in Milwaukee, Wisconsin. The contractor will provide all labor, materials, tools and equipment to test and balance critical care area air systems according to the statement of work.

36C25220Q0070 ATTACHMENT A - SAMPLE REPORT.pdf

View the file

Other files

File Type Posted
36C25220Q0070-0001001.pdf PDF
36C25220Q0070-0001000.docx DOCX document
36C25220Q0070-0001000.docx DOCX document
36C25220Q0070-0001001.pdf PDF
36C25220Q0070-002.docx DOCX document
36C25220Q0070-003.pdf PDF
36C25220Q0070-004.pdf PDF
36C25220Q0070-004.pdf PDF
36C25220Q0070-002.docx DOCX document
36C25220Q0070-001.docx DOCX document
36C25220Q0070-001.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T E S T & B A L A N C E R E P O R T

Project Name: VA Hospital – 5th Floor – Electrophysiology Lab Location: Milwaukee, WI Architect: N.A.

Engineer: PSJ Engineering Mechanical Contractor: N.A.

Project Number: 118-332

This is to certify that . has balanced the systems described herein to their optimum performance capabilities. The testing and balancing have been performed in accordance with TABB recommended procedures and principles and the results of these tests are herein recorded.

03/20/19 Dated

Randall Staron Accustar Air Balance, Inc.

TABB Supervisor

BB000051S

March 31, 2021 Printed: 02/18/2019

Date 03/20/19

Project Name: VA Hospital – 5th Floor – Electrophysiology Lab System Name: AHU-1 Floor Number 5th

A I R C H A N G E A N D R O O M P R E S S U R E T E S T S H E E T

Room Use Supply CFM Exhaust CFM Room Air Changes Per Hr Room Number Design Actual Design Actual Volume FT Design Actual Pressure

5535 EP Lab 1750 1874 1500 1156 4850 21.6 23.2 POS

Remarks

Date 03/20/19

Project Name: VA Hospital – 5th Floor – Electrophysiology Lab System Name: AHU-1 Floor Number 5th

A I R D I S T R I B U T I O N T E S T S H E E T

Terminal Room Terminal Factor Design Test - FPM or CFM Final Number Number Type Size FPM CFM Test 1 Test 2 Test 3 FPM CFM

Supply 1750 1874

1 EP Lab SW 48” x 4” 1.0 - - 93 93

2 EP Lab SW 48” x 4” 1.0 - - 119 119

3 EP Lab SW 48” x 4” 1.0 - - 165 165

4 EP Lab SW 48” x 4” 1.0 - - 157 157

5 EP Lab SW 48” x 4” 1.0 - - 174 174

6 EP Lab SW 48” x 4” 1.0 - - 173 173

7 EP Lab CD 36” x 24” 1.0 - - 205 205

8 EP Lab CD 36” x 24” 1.0 - - 200 200

9 EP Lab CD 36” x 24” 1.0 - - 194 194

10 EP Lab CD 36” x 24” 1.0 - - 138 138

11 EP Lab CD 24” x 24” 1.0 - - 160 160

12 EP Lab CD 24” x 24” 1.0 - - 96 96

13 Control Rm CD 24” x 24” 1.0 - - 311 311

Exhaust

1 EP Lab LLE 24” x 12” 1.1 - - 502 552

2 EP Lab LLE 24” x 12” 1.1 - - 549 604

3 Control Rm EG 24” x 24” 1.1 - - 307 338

Remarks

COVER with Logo
pg 01 AIR-CHANGE With Logo
pg 02 AIR-DIS With Logo