36C25219B0055-0002000.docx
DOCX document 22 KB Posted
- Attached to
- 676-19-116 Repair Campus Life Safety
- Solicitation number
- 36C25219B0055
About this file
36C25219B0055 0002 36C25219B0055 0002.docx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25219B0055-0005001.pdf | ||
| 36C25219B0055-0005000.docx | DOCX document | |
| 36C25219B0055-0004000.docx | DOCX document | |
| 36C25219B0055-0003000.docx | DOCX document | |
| 36C25219B0055-0002001.pdf | ||
| 36C25219B0055-0001000.docx | DOCX document | |
| 36C25219B0055-003.pdf | ||
| 36C25219B0055-004.pdf | ||
| 36C25219B0055-002.pdf | ||
| 36C25219B0055-001.docx | DOCX document | |
| 36C25219B0055-000.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 07-25-2019 676-19-3-6985-0051 676-19-116 36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee
WI
53214-1476 36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee
WI
53214-1476 To all Offerors/Bidders
36C25219B0055 07-25-2019
X X X
X
Project: 676-19-116 Repair Campus Life Safety Findings
This Amendment is to include Q_A documents for IFB (36C25219B0055) and a revised SOW.
See Continuation Page(s) for Q_A and attachment for the SOW.
Note: This is Amendment 0002 for Solicitation 36C25219B0055. The SOW document is noted as Amendment 1, specifically for the SOW document, not the Solicitation.
676-19-116 Repair Campus Life Safety RFI- 7/24/2019
1. B400
1. Reattach falling escutcheon; vestibule to the north of Room 1080A 1st floor
0. Question: Does this item get removed from the scope per the bid walk conversations?
0. Answer: Item gets deleted from project.
1. Relocate the smoke detectors at least 3' away from a HVAC supply grill outside room 3069 3rd floor
· Question: Do these need to be hard piped?
· Answer: The VA requirement is Hard Pipe to a Junction box mounted on the hard deck and flexible steel metal tubing to the drop ceiling lox location.
1. Reattach astragal on smoke barrier door by Stair S8-4th floor
0. Question: Does this item get removed from the scope per the bid walk conversations?
0. Answer: Item gets deleted from project.
2. B401
1. Provide a cover plate for the old lock in door. Stair 12 1st floor
0. Question: Does this item get removed from the scope per the bid walk conversations?
0. Answer: Item gets deleted from project.
1. Remove class D interior finish wood paneling or replace with a resistive coating room 1183 1st floor
· Question: Per the bid walk a new 3’-0” door is wanted. Please confirm. Would the VA like the new door to be wood to matching existing or would a hollow metal door be acceptable? Does the new door need a kick plate? What fire rating does the new door need to have? (1-hour, 2 hours?).
· Answer: New door is the preferred choice from the VA, Metal door and does not have a requirement for fire rated.
4. B403
1. Replace door with broken hinges; Cross corridor door outside room 1373 1st floor, Slab Replacement
0. Question: Per the bid walk a new 3’-6” door with light and hardware is wanted. Please confirm. Would the VA like the new door to be wood to matching existing or would a hollow metal door be acceptable? Does the new door need a kick plate? What fire rating does the new door need to have? (1-hour, 2 hours?).
0. Answer: New door is the preferred choice from the VA, Metal door and does not have a requirement for fire rated without kick plate.
1. Repair holes in door; room 1324 1st floor
1. Question: Per the walk through a new 3’-6” door and hardware is wanted. Please confirm. Would the VA like the new door to be wood to matching existing or would a hollow metal door be acceptable? Does the new door need a kick plate? What fire rating does the new door need to have? (1-hour, 2 hours?).
1. Answer: New door is the preferred choice from the VA, Metal door and does not have a requirement for fire rated with kick plate.
1. Maintain 18" clearance from top of storage to sprinkler heads in room 1324 1st floor
2. Question: Does this item get removed from the scope per the bid walk conversations?
2. Answer: Item gets deleted from project.
5. B404
a) Door rating is removed from tag; room 1431 1st floor
2. Question: Per the walk through a new 3’-6” door and hardware is wanted. Please confirm. Would the VA like the new door to be wood to matching existing or would a hollow metal door be acceptable? Does the new door need a kick plate? What fire rating does the new door need to have? (1-hour, 2 hours?).
2. Answer: New door wood to match existing is the preferred choice from the VA and does have a requirement for 1-hour fire barrier rated.
7. B409
1. Sprinkler spray patterns were obstructed by objects mounted on the ceiling less than ten inches away, and extending down between 1.5 inches and seven inches from the sprinkler deflectors: Room 1905
1. Question: Should a 13” x 13” access panel be installed to get to sprinkler head?
1. Answer: The VA would be open to the access panel install in leu of tearing out of a portion of ceiling gypsum board for the sprinkler addition.
8. B410
b) Sprinkler spray patterns were obstructed by objects mounted on the ceiling less than ten inches away, and extending down between 1.5 inches and seven inches from the sprinkler deflectors:
Room 11031
1. Question: Should a 13” x 13” access panel be installed to get to sprinkler head?
1. Answer: The VA would be open to the access panel install in leu of tearing out of a portion of ceiling gypsum board for the sprinkler addition.
See attached document: Att0001 (Rev) SOW 676-19-116 Repair Campus Life Safety 20190718.