- J041--Chiller Plant Preventative Maintenance
- Solicitation number
- 36C25026Q0723
About this file
This is a Sources Sought Notice for preventative maintenance services on the chiller plant at the Richard L. Roudebush VA Medical Center in Indianapolis, Indiana. The Department of Veterans Affairs is conducting market research to identify contractors capable of servicing five centrifugal York chillers (four 1,000-ton units and one 500-ton unit), their associated variable frequency drives (VFDs manufactured by Toshiba and York), and monitoring refrigerant leakage. The anticipated contract structure is firm-fixed price with a one-year base period (November 1, 2026 through October 31, 2027) and two optional one-year renewal periods. All work will be performed at the facility located at 1481 W. 10th Street, Indianapolis, IN 46202.
Interested contractors must respond by Friday, July 24, 2026, at 5:00 PM Eastern Time to jeffrey.rozema@va.gov with their business name and address, point of contact information, SAM Unique Entity ID, socio-economic status, and relevant capability information. Required contractor qualifications include York and Toshiba factory certification, NATE certification for large centrifugal chillers and VFD units, Section 608 Universal certification under the Clean Air Act for refrigerant work, and a minimum of three years of verifiable experience with centrifugal chillers and VFDs. The NAICS code is 238220 (Plumbing, Heating, and Air Conditioning Contractors) with a $19.0M business size standard, and the PSC is J041 (Maintenance, Repair, and Rebuilding of Equipment - Refrigeration, Air Conditioning, and Air Circulating Equipment). Contractors must be registered with SAM.gov, and those claiming small business, SDVOSB, or VOSB status must meet corresponding SBA requirements.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sources Sought Notice Sources Sought Notice
| SUBJECT* |
| Chiller Plant Preventative Maintenance |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 49037 |
| SOLICITATION NUMBER* |
| 36C25026Q0723 |
| RESPONSE DATE/TIME/ZONE |
| 07-24-2026 5:00 PM EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 60 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
SET-ASIDE
| PRODUCT SERVICE CODE* |
| J041 |
| NAICS CODE* |
| 238220 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veteran Affairs |
Network Contracting Office 10 Battle Creek VA Medical Center 5500 Armstrong Rd.
Battle Creek MI 49037
POINT OF CONTACT*
Contracting Officer Jeffrey Rozema jeffrey.rozema@va.gov
PLACE OF PERFORMANCE
| ADDRESS |
| Department of Veterans Affairs |
Richard L. Roudebush VA Medical Center
1481 W. 10th Street
Indianapolis IN
| POSTAL CODE |
| 46202 |
| COUNTRY |
| U.S.A. |
ADDITIONAL INFORMATION
| AGENCY’S URL |
| https://www.va.gov |
| URL DESCRIPTION |
| Agency Homepage |
| AGENCY CONTACT’S EMAIL ADDRESS |
| jeffrey.rozema@va.gov |
| EMAIL DESCRIPTION |
| Contracting Officer |
DESCRIPTION
This is a SOURCES SOUGHT request for informational and planning purposes only and shall not be construed as a solicitation or as an obligation or commitment by the Government at this time.
This notice is intended strictly for market research. The purpose of this Sources Sought notice is to determine the interest and capability of businesses to meet the requirements listed below.
The associated North American Industry Classification System (NAICS) Code is 238220 – Plumbing, Heating, and Air Conditioning Contractors, and the Business Size Standard is $19.0M. The associated Product Service Code is J041 – Maintenance, Repair, and Rebuilding of Equipment – Refrigeration, Air Conditioning, and Air Circulating Equipment.
Description of Requirement:
The Richard L Roudebush VA Medical Center has a requirement for preventative maintenance on five centrifugal liquid York chillers, their associated variable frequency drives (VFDs), and monitoring refrigerant leakage from the same chillers. A firm-fixed price service contract with a 1-year base period and two 1-year option periods is anticipated. The base period of performance is anticipated to be November 1, 2026 – October 31, 2027.
All work will occur at the Richard L. Roudebush VA Medical Center (RLRVAMC), 1481 W. 10th Street, Indianapolis, IN 46202. The facility has a primary/secondary chilled water loop to provide cooling medium for the majority of the air handling units (AHUs) and fan- coil units that distribute cool air to the interior of the buildings. The chiller plant is the sole source of cooling for the facility and has four (4) 1,000-ton and one (1) 500-ton chiller located in Building 23. All chillers are manufactured by York. The variable frequency drives associated with these 1,000-ton chillers are manufactured by Toshiba. The VFD for the 500-ton chiller is manufactured by York. The chillers and drives are all of the mid 1990s vintage.
Required maintenance tasks are as follows:
Preventative Maintenance / Service Tasks:
Preventative Maintenance Tasks are required both Quarterly and Annually. The Annual inspection includes all Quarterly work items and adds some specific additional tasks as identified below. These tasks as identified below are in addition to any tasks required by the manufacturer.
Quarterly Service Tasks are enumerated below:
– Provide factory specified PM on four, 1,000-ton and one, 500-ton chillers.
– Provide factory specified PM for four Toshiba 4,160-volt VFDs and one York VFD 480 volt.
– Provide the following operational PM on the chillers:
· Check and tighten all electrical connections, and
· Verify operation/settings/calibration of safety controls and shutdown operation, and
· Change oil filters, and
· Change oil dehydrator, and
· Check operation of the oil return systems, and
· Check the oil level (add to oil if oil level is low), and
· Check the oil sump heaters and the thermostat, and
· Check operation of the variable speed drive for the oil pump, and
· Check operation of the oil pump, and
· Check the operation of the oil pump starter, and
· Check for three phase voltage and current balance, and
· Verify condenser and evaporator water flow rates, and
· Verify operation of flow switches, and
· Leak check the refrigerant system and repair leaks.
– Provide the following operational PM on the VFDs:
· Clean and inspect all drives, and
· Blow out drives with an inert gas, and
· Check the components in the drive for heat degradation due to heat or loose connections, and
· Clean or replace filters in drive.
Annual PM tasks are enumerated below:
- Provide the following PM service on chillers and drives:
· Perform an oil analysis on the compressor lube oil, and
· Perform a refrigerant analysis, and
· Replace the coolant on the 480 V drive, and
· All heat exchangers should be cleaned and backwashed, and
· Check the operation of the starter coolant pump, and
· Check the voltage and amp draw on the starter coolant pumps, and
· Perform a vibration analysis on all chillers (this may need to be done at a different time from the annual inspection due to chiller loading requirements.
| Additional Tasks: |
| – Cooling season startup of each chiller includes chillers, drives, controls and associated pumps, and |
| Refrigerant Related Tasks: |
| – Perform refrigerant leak tests during each site visit using certified equipment designed for this purpose, and |
| Complete all required documentation including RLR VAMC Refrigerant Equipment Service Form in compliance with 40 CFR Parts 82 & 84, and |
| Schedule a second visit within 10 business days after scheduled services to provide additional leak testing to verify refrigerant charge integrity. |
| Repairs Outside Scope of this Contract: |
| – Any repairs required beyond the PM activities required by this contract will be ordered separately under a different contracting means. |
Contractor Qualifications:
Required Certifications:
The contractor’s personnel shall be certified and trained by York and Toshiba to work on, adjust, repair, and certify operation of York centrifugal chillers and variable frequency drives specifically of the model and type addressed in this SOW. This training shall include design, operation, maintenance and repair activities for these units. Furthermore, the technician shall be certified by the North American Technical Excellence (NATE) organization as to his/her training and experience involving large centrifugal chillers and VFD units. The technician shall also be trained and certified under Section 608 of the Clean Air Act with a Universal certification for working with refrigerant containing equipment and be proficient with 40 CFR Part 84, Subpart C (AIM Act) and Subpart F requirements.
Experience:
All technicians must have a minimum of three years verifiable experience in working with centrifugal chillers and VFDs of the type and size as identified for this project.
Requested Information:
To aid acquisition planning, contractors that are interested and capable of meeting this requirement are asked to provide a response via the email address listed below. Please provide at minimum the following information in your response:
(1) Business name and address
(2) Point of contact name, phone number and e-mail address
(3) SAM Unique Entity ID (UEI)
(4) Socio-economic status
(5) Any relevant capability information showing ability to meet the requirements listed above.
Additional information:
· All contractors must be registered with the System for Award Management (SAM) at https://sam.gov.
· Any contractor that believes they are capable and desires to claim preference for small business status must be registered with the SBA and meet the requirements of FAR 19.103.
· Any contractor that believes they are capable and desires to claim preference for SDVOSB or VOSB status must be registered with the SBA Veteran Small Business Certification Program.
Responses due to the Contracting Officer, Jeffrey Rozema, by Friday, July 24, 2026, at 5:00 PM Eastern Time. Please e-mail all responses to jeffrey.rozema@va.gov.