This is a fire extinguisher inspection record for the Veterans Affairs Northern Indiana Health Care System (NIHCS) Marion campus. The spreadsheet documents 279 active fire extinguishers across multiple buildings, including exterior and interior facilities. The inspection follows NFPA Code 10.7.2.1.2 standards and records critical information for each extinguisher: assigned location, manufacturer (primarily Amerex), model numbers (primarily B456-ABC with some Purple K and Class K variants), serial numbers, and hydrostatic test dates. The majority of extinguishers are scheduled for 6 and 12-year hydrostatic testing in 2031 and 2037 respectively, with annual inspections due in August. All extinguishers currently show "FALSE" for the annual pass status column, indicating the inspection cycle is pending or in progress.

The inventory spans diverse building types across the Marion campus, including medical buildings (Buildings 138, 172, 174, 185), operational facilities (boiler plant, shops, warehouses), administrative structures (transportation, engineering), and specialized areas (chapel, gymnasium, greenhouse). Notable facilities include Building 138 with 49 extinguishers (basement through penthouse), Building 172 with 59 extinguishers (basement through 2nd floor), and Building 55 with 11 extinguishers. Several buildings note recent fire incidents requiring extinguisher replacement (October 28-29, 2025), and some areas under construction or renovation are excluded from current inventory. The inventory also references satellite facilities (Muncie and Peru CBOCs) owned and inspected by their respective building owners, with 51 additional extinguishers listed under Building 5 basement noted to reference a separate inventory list.

View the file

Other files for this federal contract opportunity

Other files attached to H212--NIHCS Fire Alarm & Suppression Testing, newest first.
File Type Posted
36C25026Q0088 0005.docx DOCX document
36C25026Q0088 0004.docx DOCX document
Updated quantities- Marion Ft Wayne.xlsx XLSX spreadsheet
36C25026Q0088 0003.docx DOCX document
HOOD INFORMATION FORT WAYNE.docx DOCX document
Fire ext new fort wayne.xlsx XLSX spreadsheet
Fire Dampers Test Marion.pdf PDF
36C25026Q0088 0002.docx DOCX document
36C25026Q0088 0001.docx DOCX document
36C25026Q0088.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

V.A. NORTHERN INDIANA HEALTH CARE SYSTEM

Fire Extinguisher inspection Inspector:_______________
NFPA Code: 10.7.2.1.2 Date:_______________
Building- Floor-EXT Exterior Buildings - Marion
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or NoComments
BUILDING-1301-CemeteryTOTAL=5
B1301-EXT-1Ext- South East of Bldg# 1301AMEREXB456-ABCI-7010649320312037AugustFALSEFALSE
B1301-1-1B1301-G-S, South GarageAMEREXB456-ABCI-7010567020312037AugustFALSEFALSE
B1301-1-2B1301-BkRm North wall breakroomAMEREXB456-ABCI-7010089020312037AugustFALSEFALSE
B1301-1-3Room 100 OfficeAMEREXB456-ABCI-7004399720312037AugustFALSEFALSE
B1301-1-4B1301-G-E, East GarageAMEREXB456-ABCI-7010088920312037AugustFALSEFALSE
BUILDING-3004-CemeteryTOTAL=3
EXT-B3004-1PUMPEXT 1301/3004 AGST Fuel PumpAmerex415-Purple KI-7024782720302035AugustFALSEFALSE
EXT-B3004-1-1Ext-South East of Bldg 3004Amerex415-Purple KI-7024785620302035AugustFALSEFALSE
B3004-1-2Inside North side of bldg # 3004Amerex415-Purple KI-7024783520302035AugustFALSEFALSE
Building -69 Horse BarnTOTAL=1FALSEFALSE
B69-1-1East wall of buildingAmerexB456I-7009890120312037AugustFALSEFALSE
BUILDING-8-GymTOTAL=4
B8-B-1B8- Bowling Alley South End of lanesAMEREXB456-ABCI-7009889820312037AugustFALSEFALSE
B8-B-2B8-002 Inside OfficeAMEREXB456-ABCI-7010649620312037AugustFALSEFALSE
B8-B-3B8- Bowling Alley behind lanesAMEREXB456-ABCI-7004399820312037AugustFALSEFALSE
B8-1-1B8-GYMAMEREXB456-ABCI-7010088520312037AugustFALSEFALSE
BUILDING-9TOTAL=6
B9-1-1B9-109Print Shop North East exitAMEREXB456-ABCI-7009890220312037AugustFALSEFALSE
B9-1-2B9-109print shopAMEREXB456-ABCI-7010088420312037AugustFALSEFALSE
B9-1-3B9-104Across from OfficeAMEREXB456-ABCI-7004399920312037AugustFALSEFALSE
B9-2-1B9-2nd floorRM 201AMEREXB456-ABCI-7010616320312037AugustFALSEFALSE
B9-2-2B9-2nd floorCenteral HallAMEREXB456-ABCI-7010566920312037AugustFALSEFALSE
B9-2-3B9-2nd floorRM 205AMEREXB456-ABCI-7010782020312037AugustFALSEFALSE
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or NoComments
BUILDING-55- Logistics WHTOTAL=11
EXT-B55-1South West corner ext across from fuel pumpAMEREX415-Purple KI-7024785520302035AugustFALSEFALSE
B55-1-1B55 South Loading dockAMEREXB456-ABCI-700649520312037AugustFALSEFALSE
B55-1-2B55-Outside RM 106 HAC/ RestroomAMEREXB456-ABCI-7009890920312037AugustFALSEFALSE
B55-1-3B55-103 BreakroomAMEREXB456-ABCI-7009890520312037AugustFALSEFALSE
B55-1-4B55-North loading dock by entrance door.AMEREXB456-ABCI-7009891220312037AugustFALSEFALSE
B55-1-5B55-100 by prosthtics shipmentAMEREXB456-ABCI-7009890620312037AugustFALSEFALSE
B55-1-6B55- West Loading DockAMEREXB456-ABCI-7010782420312037AugustFALSEFALSE
B55-B-1B55- 004 Basement Elevator RoomAMEREXB456-ABCI-7010607820312037AugustFALSEFALSE
B55-B-2B55-001 Basment center postAMEREXB456-ABCI-7004394220312037AugustFALSEFALSE
B55-B-3B55-002 Basement North end on post.AMEREXB456-ABCI-7010642220312037AugustFALSEFALSE
B55C-1-1B55C- Mail RoomAMEREXB456-ABCI-7010784120312037AugustFALSEFALSE
BUILDING-153-PavilionTOTAL=1
B153-1-1B153-102KitchenAMEREXB456-ABCI-7010622420312037AugustFALSEFALSE
BUILDING-54 Metal ShopTOTAL=1
B54-1-1B54-100 west entranceAMEREXB456-ABCI-7010089920312037AugustFALSEFALSE
BUILDING-137-TransportationTOTAL=1
B137-1-1B137-100/101 By south entranceAMEREXB456-ABCI-7004401320312037AugustFALSEFALSE
BUILDING-504- Fab ShopTOTAL=1
B504-1-1B504-100 By North sideAMEREXB456-ABCI-7004391320312037AugustFALSEFALSE
BUILDING-516- Auto ShopTOTAL=1
B516-1-1B516-100 By east entranceAMEREXB456-ABCI-7010561220312037AugustFALSEFALSE
BUILDING-97-Paint ShopTOTAL=1
B97-1-1B97-100 North Side by entranceAMEREXB456-ABCI-7010090020312037AugustFALSEFALSE
BUILDING-41- TransportantionTOTAL=2
B41-1-1B41-102 GarageAMEREXB456-ABCI-7010079020312037AugustFALSEFALSE
B41-1-2B41-104 BathroomAMEREXB456-ABCI-7010781320312037AugustFALSEFALSE
BUILDING-49- LibaryTOTAL=0 Still under construction
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or N0Comments
BUILDING-51- ENG electrical, plumbing, carpentryTOTAL=10
B51-1-1C104-051Near EntryAMEREXB456-ABCI-7010082220312037AugustFALSEFALSE
B51-1-2115-051-MHVAC/Plumb ShopAMEREXB456-ABCI-7004400020312037AugustFALSEFALSE
B51-1-3118-051-MElectric ShopAMEREXB456-ABCI-7005807720312037AugustFALSEFALSE
B51-1-4119-051-MKitchen/ BreakroomAMEREX260-Class KI-7000091720302035AugustFALSEFALSE
B51-1-5C122-051MNear slop sinkAMEREXB456-ABCI-7005809020312037AugustFALSEFALSE
B51-1-6126-051-MCarpentry ShopAMEREXB456-ABCI-7005809120312037AugustFALSEFALSE
B51-1-7126-051-MCarpentry ShopAMEREXB456-ABCI-7005808920312037AugustFALSEFALSE
B51-B-1B51-bsmt-2Basement roomAMEREXB456-ABCI-7005807520312037AugustFALSEFALSE
B51-B-2B51-bsmt-1By cage 1AMEREXB456-ABCI-7005808720312037AugustFALSEFALSE
B51-B-3B51-bsmt-16By Cage 16AMEREXB456-ABCI-7005808820312037AugustFALSEFALSE
BUILDING-52- Eng OfficeTOTAL=2
B52-1-1B52- Beside RM103 restroomAMEREXB456-ABCI-7005807620312037AugustFALSEFALSE
B52-2-1B52-Top of stairs outside RM 203AMEREXB456-ABCI-7005807820312037AugustFALSEFALSE
BUILDING-53- EngTOTAL=4
B53-1-1M53-102middle hallAMEREXB456-ABCI-17004394120312037AugustFALSEFALSE
B53-1-2M53-105NNorth in roomAMEREXB456-ABCI-7010078420312037AugustFALSEFALSE
B53-1-3M53-Carpwest exit carpentryAMEREXB456-ABCI-7010559820312037AugustFALSEFALSE
B53-B-1M53-Bsmtbottom of stairsAMEREXB456-ABCI-7010560420312037AugustFALSEFALSE
B53-B-2M53-BasementBehind Fire DoorAMEREXB456-ABCI-7010561820312037AugustFALSEFALSE
BUILDING-165-Eqpt Pole BarnTOTAL=2
B165-1-1B165- West beside slid doorAMEREXB456-ABCI-7005805020312037AugustFALSEFALSE
B165-1-2B165- Beside doorAMEREXB456-ABCI-7005804920312037AugustFALSEFALSE
BUILDING-191 AGSTTOTAL=2
191-1Mount on fenceAmerex415- Purple KI-7024783420302035AugustFALSEFALSE
191-2Mounted by tankAmerex415- Purple KI-7024783720302035AugustFALSEFALSE
BUILDING-192 AGSTTOTAL=2
192-1Mount on fenceAmerex415-Purple KI-7024782820302035AugustFALSEFALSE
192-2Mounted by TankAmerex415-Purple KI-7024785220302035AugustFALSEFALSE
BUILDING-145 GENTOTAL=1
B76-GenGenerator outside Bldg # 76AMEREXB456-ABCI-7009891320312037AugustFALSEFALSE
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or NoComments
BUILDING-76-Boiler PlantTOTAL=8
B76-1-1B76-Low-ContIn lower control rmAMEREXB456-ABCI-7005804720312037AugustFALSEFALSE
B76-1-2B76-PanelBy fire alarm panelAMEREXB456-ABCI-7005804620312037AugustFALSEFALSE
B76-1-3B76-restroomEast by restroomAMEREXB456-ABCI-7005804020312037AugustFALSEFALSE
B76-1-4B76-NwallNorth Wall centerAMEREXB456-ABCI-70005803920312037AugustFALSEFALSE
B76-1-5B76-Up-WUpper deck Wst endAMEREXB456-ABCI-7005805820312037AugustFALSEFALSE
B76-2-1B76-Up-ContBy upper control rmAMEREXB456-ABCI-7005804120312037AugustFALSEFALSE
B76-EXT-1B76-Ext-West side of bldgAmerex415- Purple KI-7024783820302035AugustFALSEFALSE
B76-EXT-2B76-EXT- East side of bldgAmerex415- Purple KI-7024784120302035AugustFALSEFALSE
Underground Storage TanksTOTAL=2FALSEFALSE
U.G. Storage-W-1West EndPole outside boiler plantAMEREXA411-ABCI-5765302820312037AugustFALSEFALSE
U.G. Storage-W-2East EndPole outside boiler plantAMEREXA411-ABCI-5765302720312037AugustFALSEFALSE
BUILDING-58-Temp PSTOTAL=2
B58-1-1B58-100Room 100AMEREXB456-ABCI-5765302820312037AugustFALSEFALSE
B58-1-2B58Room 101AMEREXB456-ABCI-5765302720312037AugustFALSEFALSE
BUILDING-79 (EAST)-CFUTOTAL=5
B79-1-1EB79-EastAMEREXB456-ABCI-7010567320312037AugustFALSEFALSE
B79-1-2EBy grinding roomAMEREXB456-ABCI-7010567320312037AugustFALSEFALSE
B79-1-3ECenter PoleAMEREXB456-ABCI-7009800820312037AugustFALSEFALSE
B79-1-4EAir Compressor RoomAMEREXB456-ABCI-7010782520312037AugustFALSEFALSE
B79-1-5EDock AreaAMEREXB456-ABCI-7010784220312037AugustFALSEFALSE
BUILDING-79 (West)-WarehouseTOTAL=3
B79-1-1B79-W North WallAMEREXB456-ABCI-7010090120312037AugustFALSEFALSE
B79-1-2B79-W Middle of BuildingAMEREXB456-ABCI-7010617120312037AugustFALSEFALSE
B79-1-3B79-WNext to South ExitAMEREXB456-ABCI-700981420312037AugustFALSEFALSE
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or NoComments
BUILDING-173-GreenhouseTOTAL=3
B173-1-1B173-100Greenhouse entranceAMEREXB456-ABCI-7010560520312037AugustFALSEFALSE
B173-1-2B173-107In roomAMEREXB456-ABCI-7010616920312037AugustFALSEFALSE
B173-1-3B173-104SW door, garageAMEREXB456-ABCI-7010090320312037AugustFALSEFALSE
BUILDING-5TOTAL=4
B5-B-1B5-001Basement Elevator RoomAMEREXB456-ABCI-7009891120312037AugustFALSEFALSE
B5-1-1B5-1011st Floor by ElevatorAMEREXB456-ABCI-7004392620312037AugustFALSEFALSE
B5-2-1B5-2092nd Floor by ElevatorAMEREXB456-ABCI-7010567620312037AugustFALSEFALSE
B5-GEN.BLDB5-GenBldgenerator buildingAMEREXB456-ABCI-7010617220312037AugustFALSEFALSE
BUILDING-6TOTAL=3
B6-B-1B6-101Basement Elevator RoomAMEREXB456-ABCI-7010617020312037AugustFALSEFALSE
B6-1-1B6-0011st Floor by ElevatorAMEREXB456-ABCI-7010567520312037AugustFALSEFALSE
B6-1-2B6-2-2042nd Floor by ElevatorAMEREXB456-ABCI-7010090220312037AugustFALSEFALSE
BUILDING-2TOTAL=5
B2-B-1B2-001Basement Elevator RoomAMEREXB456-ABCI-7005804420312037AugustFALSEFALSE
B2-1-1B2-1-101near roomAMEREXB456-ABCI-7005804820312037AugustFALSEFALSE
B2-1-2B2-1-120near roomAMEREXB456-ABCI-7005804520312037AugustFALSEFALSE
B2-2-1B2-2-209near roomAMEREXB456-ABCI-7005804320312037AugustFALSEFALSE
B2-2-2B2-2-204near roomAMEREXB456-ABCI-7005806020312037AugustFALSEFALSE
BUILDING-170 PoliceTOTAL=1
B170-1-1B170-104KitchenAMEREXB456-ABCI-7005805520312037AugustFALSEFALSE
BUILDING-175 GeneratorTOTAL=2
B175-1-1B175-southsouth generator roomAMEREXB456-ABCI-7009889920312037AugustFALSEFALSE
B175-1-2B175-northnorth generator roomAMEREXB456-ABCI-7010649120312037AugustFALSEFALSE
BUILDING-65 ChapelTOTAL=5
B65-1-1B65-110by roomAMEREXB456-ABCI-7010089620312037AugustFALSEFALSE
B65-1-2B65-Exit-NExit by alarm panelAMEREXB456-ABCI-7010649220312037AugustFALSEFALSE
B65-1-3B65-ChapelAMEREXB456-ABCI-7010088820312037AugustFALSEFALSE
B65-B-1B65-Bsmt-NNorth basementAMEREXB456-ABCI-7010616420312037AugustFALSEFALSE
B65-B-2B65-Bsmt-SSouth basementAMEREXB456-ABCI-7009890020312037AugustFALSEFALSE
BUILDING-114 TransportationTOTAL=2
B114-1-1B114-101Transportation by front doorAMEREXB456-ABCI-7010649420312037AugustFALSEFALSE
B114-1-2B114-101By I.T. closetAMEREXB456-ABCI-7005806620312037AugustFALSEFALSE
Fire Extinguisher inspection Inspector:_______________
NFPA Code: 10.7.2.1.2 Date:_______________
Interior Buildings - Marion
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or noComments
BUILDING-17TOTAL=5
B17-1-1B17-112Next to RM 112-017AMEREXB456-ABCI-7009890320312037AugustFALSEFALSE
B17-1-2B17-110In Fire Cabinet RM 100-017AMEREXB456-ABCI-7009890420312037AugustFALSEFALSE
B17-2-1B17-200In Fire Cabinet RM 200-017AMEREXB456-ABCI-7010089120312037AugustFALSEFALSE
B17-2-2B17-213Outside RM 208-017AMEREXB456-ABCI-7010616520312037AugustFALSEFALSE
B17-2-3B17-216Outside RM 214-017AMEREXB456-ABCI-7010567220312037AugustFALSEFALSE
BUILDING-16TOTAL=9
B16-B-1Basement Elevator Rm B- 002AMEREXB456-ABCI-7005807220312037AugustFALSEFALSERemoved for renovation
B16-B-2Basement Steamroom By stairwell 1AMEREXB456-ABCI-7005805320312037AugustFALSEFALSERemoved for renovation
B16-1-1B16-111By entrance / exit doorAMEREXB456-ABCI-7005809220312037AugustFALSEFALSERemoved for renovation
B16-1-2B16-103Outside RM 103-016AMEREXB456-ABCI-7005809620312037AugustFALSEFALSERemoved for renovation
B16-1-3B16-130Outside RM 130-016AMEREXB456-ABCI-7005809720312037AugustFALSEFALSERemoved for renovation
B16-2-1B16-207Outside RM 207-016AMEREXB456-ABCI-7005809320312037AugustFALSEFALSERemoved for renovation
B16-2-2B16-201Outside RM 201-016AMEREXB456-ABCI-7005809320312037AugustFALSEFALSERemoved for renovation
B16-3-1B16-318Outside RM 301-016AMEREXB456-ABCI-7005809420312037AugustFALSEFALSERemoved for renovation
B16-3-2B16-307Outside RM 307-016AMEREXB456-ABCI-7005809820312037AugustFALSEFALSERemoved for renovation
BUILDING-15TOTAL=4
B15-1-1B15-100By entrance/ exit doorAMEREXB456-ABCI-7005810720312037AugustFALSEFALSE
B15-1-2B15-120Outside RM 120-015AMEREXB456-ABCI-7005806920312037AugustFALSEFALSE
B15-2-1B15-207Outside RM 207-015AMEREXB456-ABCI-7005805620312037AugustFALSEFALSE
B15-2-2B15-203In cabinet outside RM 203-015AMEREXB456-ABCI-7005805420312037AugustFALSEFALSE
BUILDING-127TOTAL=0
Construction
Construction
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or noComments
BUILDING-124TOTAL=13
B124-1-1B124-1131st floor centerAMEREXB456-ABCI-7005805220312037AugustFALSEFALSE
B124-1-2B124-125Across from room 122AMEREXB456-ABCI-7005806220312037AugustFALSEFALSE
B124-1-3B124-133across from room 120AMEREXB456-ABCI-7005805920312037AugustFALSEFALSE
B124-1-4B124-1-elevBy 1st floor elevatorAMEREXB456-ABCI-7010089820312037AugustFALSEFALSE
B124-2-1B124-2-ElevatorBy ElevatorAMEREXB456-ABCI-7010566820312037AugustFALSEFALSE
B124-2-2B124-213By room 213AMEREXB456-ABCI-7010089520312037AugustFALSEFALSE
B124-2-3B124-222By room 222AMEREXB456-ABCI-7010649720312037AugustFALSEFALSE
B124-3-1B124-3-ElevatorBy ElevatorAMEREXB456-ABCI-7010566820312037AugustFALSEFALSE
B124-3-2B124-3-312By room 312AMEREXB456-ABCI-7010089420312037AugustFALSEFALSE
B124-3-3B124-3-320By room 320AMEREXB456-ABCI-7010089220312037AugustFALSEFALSE
B124-3-4B124-3-326By room 326AMEREXB456-ABCI-7005807020312037AugustFALSEFALSE
B124-3-5B124-3-compIn computer roomAMEREX397I-7130657120302035AugustFALSEFALSE
B124-Courtyard Elec RMB124-pwroff courtyard CAMEREXB456-ABCI-7004399220312037AugustFALSEFALSE
BUILDING-174TOTAL=17
B174-1-1B174-106in hall by roomAMEREXB456-ABCI-7009892320312037AugustFALSEFALSE
B174-1-2B174-108electrical roomAMEREXB456-ABCI-7004400520312037AugustFALSEFALSE
B174-1-3B174-111Cloading dock by roomAMEREXB456-ABCI-7010091820312037AugustFALSEFALSE
B174-1-4B174-112in hall near roomAMEREXB456-ABCI-7010091420312037AugustFALSEFALSE
B174-1-5B174-123outside roomAMEREXB456-ABCI-7004400820312037AugustFALSEFALSE
B174-1-6M174-kt-fryacross from fryersAMEREXB260- Class KI-5165685620302035AugustFALSEFALSE
B174-1-7B174-kt-cabcabinet in kitchenAMEREXB456-ABCI-7003059620312037AugustFALSEFALSE
B174-1-8M174-Kt-Linefront food lineAMEREXB260- Class KI-5165414020302035AugustFALSEFALSE
B174-1-9B174-diningdining room areaAMEREXB456-ABCI-7007667720312037AugustFALSEFALSE
B174-1-10B174-108Electrical RoomAMEREXB456-ABCI-7010568220312037AugustFALSEFALSE
B174-B-1B174-B-100Elevator RoomAMEREXB456-ABCI-7010650520312037AugustFALSEFALSE
B174-B-2B174-B-101Housekeeping storageAMEREXB456-ABCI-7010091820312037AugustFALSEFALSE
B174-B-3B174-B-101HHall across from elevatorAMEREXB456-ABCI-7004400520312037AugustFALSEFALSE
B174-B-4B174-B-106Center postAMEREXB456-ABCI-7009892920312037AugustFALSEFALSE
B174-B-5B172-B2-105A/C Parts roomAMEREXB456-ABCI-7004400720312037AugustFALSEFALSE
B174-B-6B174-B-106Inside Elevator Chiller roomAMEREXB456-ABCI-7010568520312037AugustFALSEFALSE
B174-B-7B174-B-106HHall by sairs 14AMEREXB456-ABCI-7010091520312037AugustFALSEFALSE
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or noComments
BUILDING-138- BasementTOTAL=10
B138-B-1B138-B-ElevatorAcross from West elevatorAMEREXB456-ABCI-7010567820312037AugustFALSEFALSE
B138-B-2B138-010outside roomAMEREXB456-ABCI-7010617320312037AugustFALSEFALSE
B138-B-3B138-B-008In room 008AMEREXB456-ABCI-7010568120312037AugustFALSEFALSE
B138-B-4B138-B-005CIn room 005CAMEREXB456-ABCI-7009891820312037AugustFALSEFALSE
B138-B-5B138-B-003By room 003- Fire EXT ClosetAMEREXB456-ABCI-7010090620312037AugustFALSEFALSE
B138-B-6B138-B-100By room 100- Fire EXT ClosetAMEREXB456-ABCI-7010567920312037AugustFALSEFALSE
B138-B-7B138-B- Stairs 3By Stairs 3- Fire EXT ClosetAMEREXB456-ABCI-7009891920312037AugustFALSEFALSE
B138-B-8B138-B-018In breakroomAMEREXB456-ABCI-7004400120312037AugustFALSEFALSE
B138-B-9B138-B-018By Room 018- Fire EXT closetAMEREXB456-ABCI-7010650620312037AugustFALSEFALSE
B138-B-10B138-B-149In room 149 Mechanical roomAMEREXB456-ABCI-7004400220312037AugustFALSEFALSE
BUILDING-138- 1st floor and PACT areaTOTAL=14
B138-1-1B138-1- ElevatorAcross from West ElevatorAMEREXB456-ABCI-7010650020312037AugustFALSEFALSE
B138-1-2B138-1-114Outside room 114AMEREXB456-ABCI-7009891620312037AugustFALSEFALSE
B138-1-3B138-1-106Closet beside RM 106- VaultAMEREXB456-ABCI-7016049820312037AugustFALSEFALSE
B138-1-4B138-1-100Cabinet beside RM 100AMEREXB456-ABCI-7010649920312037AugustFALSEFALSE
B138-1-5B138-1-stairs 1Closet Stairs1AMEREXB456-ABCI-7009891520312037AugustFALSEFALSE
B138-1-6B138-1-stairs 1Closet by stairs 1AMEREXB456-ABCI-7010617520312037AugustFALSEFALSE
B138-1-7B138-1- CorridorIn Corridor-C104AMEREXB456-ABCI-7010614720312037AugustFALSEFALSE
B138-1-8B138-1-Stairs 2Closet by Stairs 2AMEREXB456-ABCI-7010650220312037AugustFALSEFALSE
B138-1-9B138-1-103Outside Restrooms in hall-PACTAMEREXB456-ABCI-7009892620312037AugustFALSEFALSE
B138-1-10B138-1-D136PACT by RM D136 in hall- PACTAMEREXB456-ABCI-7010650820312037AugustFALSEFALSE
B138-1-11B138-1-D121Outside RM R121-Hall-PACTAMEREXB456-ABCI-7009892720312037AugustFALSEFALSE
B138-1-12B138-1-D128 HallOutside RM D128-Hall-PACTAMEREXB456-ABCI-7010617920312037AugustFALSEFALSE
B138-1-13B138-1-D117Outside RM D117- Hall- PACTAMEREXB456-ABCI-7004400920312037AugustFALSEFALSE
B138-1-14B138-1- LobbyBy Front Entrance -PACTAMEREXB456-ABCI-7010091620312037AugustFALSEFALSE
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or noComments
Building 138 -2nd FloorTOTAL= 9Y
B138-2-1B138-2-Elevatorcabinet by west elevAmerexB456-ABCI-7010650120312037AugustFALSEFALSEComments
B138-2-2B138-2- 228Inside LabAMEREXB456-ABCI-7010650420312037AugustFALSEFALSE
B138-2-3B138-2- Stairs 3closet Stairs S2 across from RM214AMEREXB456-ABCI-7010563020312037AugustFALSEFALSE
B138-2-4B138-2-201Outside RM 201-016AMEREXB456-ABCI-7010617620312037AugustFALSEFALSE
B138-2-5B138-2-Stairs 1Closet by stairs S1AMEREXB456-ABCI-7010618220312037AugustFALSEFALSE
B138-2-6B138-2-Stairs 3Closet by stairs S3AMEREXB456-ABCI-7010567720312037AugustFALSEFALSE
B138-2-7B138-2-252Ouside RM 252 in hall cabinetAMEREXB456-ABCI-7010090420312037AugustFALSEFALSE
B138-2-8B138-2-248In X-Ray breakroomAMEREXB456-ABCI-7009891720312037AugustFALSEFALSE
B138-2-9B138-2-247In CT roomHalotron397I-7130656620302035AugustFALSEFALSE
Building 138-3rd FloorTOTAL=5FALSE
B138-3-1B138-3-Elevatorcabinet by west elevAMEREXB456-ABCI-7010611920312037AugustFALSEFALSEComments
B138-3-2B138-3-310Closet by Stairs S2AMEREXB456-ABCI-7010563320312037AugustFALSEFALSE
B138-3-3B138-3-371Closet by Stairs S1AMEREXB456-ABCI-7010645920312037AugustFALSEFALSE
B138-3-4B138-3-355Closet by Stairs S3AMEREXB456-ABCI-7010786220312037AugustFALSEFALSE
B138-3-5B138-3-340In RM340AMEREXB456-ABCI-7010084520312037AugustFALSEFALSE
BUILDING-138-4th FloorTOTAL=12
B138-4-1B138-4-welevcabinet by west elevAMEREXB456-ABCI-7004123120312037AugustFALSEFALSE
B138-4-2B138-4-459Dental LABAMEREXB456-ABCI-7003060520312037AugustFALSEFALSE
B138-4-3B138-4-460Cabinet across from dent surgeryAMEREXB456-ABCI-7003060320312037AugustFALSEFALSE
B138-4-4B138-4-Stairs 3Closet by Stairs 3AMEREXB456-ABCI-7010080820312037AugustFALSEFALSE
B138-4-5B138-4- Stairs 1Closet by Stairs 1AMEREXB456-ABCI-7007668820312037AugustFALSEFALSE
B138-4-6B138-4- Stairs 2Closet by Stairs 2AMEREXB456-ABCI-7004489920312037AugustFALSEFALSE
B138-4-7B138-4-415Cabinet by RM 474AMEREXB456-ABCI-7005964320312037AugustFALSEFALSE
B138-4-8B138-4- lobbyLobby by eye glass clinicAMEREXB456-ABCI-7010641220312037AugustFALSEFALSE
B138-Penthouse 1B138-Pths-1top of stairsAMEREXB456-ABCI-7007668420312037AugustFALSEFALSE
B138-Penthouse 2B138-Pths-2new penthouseAMEREXB456-ABCI-7004492220312037AugustFALSEFALSE
B138- Penthouse 3B138-Pths-3New penthouseAMEREXB456-ABCI-7004124420312037AugustFALSEFALSE
B138- Penthouse 4B138-Pths-4new penthouseAMEREXB456-ABCI-7004124420312037AugustFALSEFALSE
BUILDING-185-BasementTOTAL=5
B185-B-1B185-B - CorridorCorridor -02 in hallAMEREXB456-ABCI-7004391620312037AugustFALSEFALSE
B185-B-2B185-B - CorridorOutside RM 007AMEREXB456-ABCI-7010080720312037AugustFALSEFALSE
B185-B-3B185-B- 006Inside Mechianical roomAMEREXB456-ABCI-7010609420312037AugustFALSEFALSE
B185-B-4B185-B-001Inside Mechianical roomAMEREXB456-ABCI-7010782820312037AugustFALSEFALSE
B185-B-5B185-B-002Inside Elevator RoomAMEREXB456-ABCI-7004389320312037AugustFALSEFALSE
FALSE
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or NoComments
Building 185- 1st FloorTOTAL=10
B185-1B-1B185-1n-119next to bathroomAMEREXB456-ABCI-7007669120312037AugustFALSEFALSE
B185-1B-2B185-1n-120next to bathroomAMEREXB456-ABCI-7004492720312037AugustFALSEFALSE
B185-1B-3B185-1n-108outside by stair 2AMEREXB456-ABCI-7004493120312037AugustFALSEFALSE
B185-1C-1B185-1s-108outside by stair 5AMEREXB456-ABCI-7008927320312037AugustFALSEFALSE
B185-1C-2B185-1s-120outside bathroomAMEREXB456-ABCI-7004124720312037AugustFALSEFALSE
B185-1C-3B185-1s-125outside by stair 4AMEREXB456-ABCI-7004492820312037AugustFALSEFALSE
B185-1A-1B185-A129in canteen near roomAMEREXB456-ABCI-7004493320312037AugustFALSEFALSE
B185-1A-2B185-canteenbehind food lineAMEREXB260-Class KI-5763923920312037AugustFALSEFALSE
B185-1A-3B185-a119hall across from roomAMEREXB456-ABCI-7007669220312037AugustFALSEFALSE
B185-1A-4B185-a114by room btw unitsAMEREXB456-ABCI-7004125220312037AugustFALSEFALSE
BUILDING-185- 2nd FloorTOTAL=8
B185-2B-1B185-2N-225By Stairs 4AMEREXB456-ABCI-7010559620312037AugustFALSEFALSE
B185-2B-2B185-2N-208By Stairs 2AMEREXB456-ABCI-7004492920312037AugustFALSEFALSE
B185-2B-3B185-2N-220Outside RestroomsAMEREXB456-ABCI-7007669320312037AugustFALSEFALSE
B185-2C-1B185-2S-208By Stairs 5AMEREXB456-ABCI-7004124820312037AugustFALSEFALSE
B185-2C-2B185-2S-220Outside RestroomAMEREXB456-ABCI-7008927420312037AugustFALSEFALSE
B185-2C-3B185-2S-225By Stairs 3AMEREXB456-ABCI-7004492520312037AugustFALSEFALSE
B185-2A-1B185-2fl-hallhall above canteenAMEREXB456-ABCI-7004492620312037AugustFALSEFALSE
B185-2A-2B185-a214by room btw unitsAMEREXB456-ABCI-7003060420312037AugustFALSEFALSE
BUILDING-172 BasementTOTAL= 10
B172-B-1Corner heading to B-185AMEREXB456-ABCI-7003059920312037AugustFALSEFALSE
B172-B-2B172-B- elevatorElevator to BLd 124/ Stairs 12AMEREXB456-ABCI-7004493220312037AugustFALSEFALSE
B172-B-3B175-B-B13Outside RM B013AMEREXB456-ABCI-7010091920312037AugustFALSEFALSE
B172-B-4B172-B-004Inside Storage roomAMEREXB456-ABCI-7004125120312037AugustFALSEFALSE
B172-B-5B172-B-002In hall outside RM B002AMEREXB456-ABCI-7008927020312037AugustFALSEFALSE
B172-B-6B172-B-019Inside Biohazard roomAMEREXB456-ABCI-7004124320312037AugustFALSEFALSE
B172-B-7B172-B-017Inside Elevator RM B017AMEREXB456-ABCI-7004123720312037AugustFALSEFALSE
B172-B-8B172-B-B015Inside Electrical RM B015AMEREXB456-ABCI-7004123520312037AugustFALSEFALSE
B172-B-9B172-B-B020Outside Room B020AMEREXB456-ABCI-7008927220312037AugustFALSEFALSE
B172-B-10B172-B-026Outside RM B026AMEREXB456-ABCI-7007668320312037AugustFALSEFALSE
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or NoComments
BUILDING-172 1st floorTOTAL=26
B172-NE AtriumB172-North East AtriumAMEREXB456-ABCI-7010089320312037AugustFALSEFALSEEXT replaced due to fire on 10/29/2025
B172-SE AtriumB172-South East AtriumAMEREXB456-ABCI-7003059320312037AugustFALSEFALSE
B172-1A-2B172-1A-102 across from stairs 10AMEREXB456-ABCI-7004125020312037AugustFALSEFALSE
B172-1A-3B172-1A-103 kitchen beside ICE makerAMEREXB262- Class kI-5763923820302035AugustFALSEFALSE
B172-1A-4B172-1A-102E, East wallAMEREXB456-ABCI-7004123020312037AugustFALSEFALSE
B172-1A-5B172-1A-102W, West wallAMEREXB456-ABCI-7003059520312037AugustFALSEFALSE
B172-1A-6B172-1A-102 across from stairs 11AMEREXB456-ABCI-7008926820312037AugustFALSEFALSE
B172-1A-7B172-124 Across from ramp heading to bld 124AMEREXB456-ABCI-7003060020312037AugustFALSEFALSE
B172-1B-1B172-1B-106outside roomAMEREXB456-ABCI-7004401120312037AugustFALSEFALSE
B172-1B-2B172-1B-119outside roomAMEREXB456-ABCI-7008506820312037AugustFALSEFALSEEXT replaced due to fire on 10/28/2025
B172-1B-3B172-1B-128across from roomAMEREXB456-ABCI-7010092120312037AugustFALSEFALSE
B172-1B-4B172-1B-130btw rm 129 & 130AMEREXB456-ABCI-7010091720312037AugustFALSEFALSE
B172-1B-5B172-1B-147dining room areaAMEREXB262- Class kI-5165585020302035AugustFALSEFALSE
B172-1B-6B172-1B-105outside roomAMEREXB456-ABCI-7010090420312037AugustFALSEFALSE
B172-1C-1B172-1C-123btw rm 122 & 123AMEREXB456-ABCI-7004401020312037AugustFALSEFALSE
B172-1C-2B172-1C-112outside roomAMEREXB456-ABCI-7010568620312037AugustFALSEFALSE
B172-1C-3B172-1C-121across hallAMEREXB456-ABCI-7010092020312037AugustFALSEFALSE
B172-1D-1B172-1D-112outside nurse stationAMEREXB456-ABCI-7010650920312037AugustFALSEFALSE
B172-1D-2B172-1D-121across fromAMEREXB456-ABCI-7010618320312037AugustFALSEFALSE
B172-1D-3B172-1D-123Beside roomAMEREXB456-ABCI-7010568420312037AugustFALSEFALSE
B172-1E-1B172-1E-147dining room areaAMEREXB262- Class kI-5763923720302035AugustFALSEFALSE
B172-1E-2B172-1E-130outside roomAMEREXB456-ABCI-7010092220312037AugustFALSEFALSE
B172-1E-3B172-1E-128outside roomAMEREXB456-ABCI-7010092420312037AugustFALSEFALSE
B172-1E-4B172-1E-119AMEREXB456-ABCI-7010568720312037AugustFALSEFALSE
B172-1E-5B172-1E-106AMEREXB456-ABCI-7010568820312037AugustFALSEFALSE
B172-1E-6B172-1E-105outside roomAMEREXB456-ABCI-7004401220312037AugustFALSEFALSE
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPass Yes or NoComments
Building 172- 2nd floorTOTAL= 22
B172/174-2 rampB172-124 Ramp-22nd floor near 124AMEREXB456-ABCI-7010618620312037AugustFALSEFALSE
B172-2A-1B172-2A-201by stair 11AMEREXB456-ABCI-7009892820312037AugustFALSEFALSE
B172-2A-PT/OTB172-2A-202in room OT/PTAMEREXB260- Class KI-5763924520302035AugustFALSEFALSE
B172-2B-1B172-2B-206outside roomAMEREXB456-ABCI-7010618520312037AugustFALSEFALSE
B172-2B-2B172-2B-219outside roomAMEREXB456-ABCI-7010568320312037AugustFALSEFALSE
B172-2B-3B172-2B-228across from roomAMEREXB456-ABCI-7010650720312037AugustFALSEFALSE
B172-2B-4B172-2B-230next to roomAMEREXB456-ABCI-7010559420312037AugustFALSEFALSE
B172-2B-5B172-2Bdining room areaAMEREXB262- Class kI-5763924620302035AugustFALSEFALSE
B172-2B-6B172-2B-205outside roomAMEREXB456-ABCI-7010091920312037AugustFALSEFALSE
B172-2C-1B172-2C-223next to roomAMEREXB456-ABCI-7004389220312037AugustFALSEFALSE
B172-2C-2B172-2C-221across from roomAMEREXB456-ABCI-7010559320312037AugustFALSEFALSE
B172-2C-3B172-2C-212outside roomAMEREXB456-ABCI-7010612120312037AugustFALSEFALSE
B172-2D-1B172-2D-212outside roomAMEREXB456-ABCI-7010563120312037AugustFALSEFALSE
B172-2D-2B172-2D-221across fromAMEREXB456-ABCI-7010563220312037AugustFALSEFALSE
B172-2D-3B172-2D-223outside roomAMEREXB456-ABCI-7010645820312037AugustFALSEFALSE
B172-2E-1B172-2E-230outside roomAMEREXB456-ABCI-7010786620312037AugustFALSEFALSE
B172-2E-2B172-2E-228across from roomAMEREXB456-ABCI-7003059720312037AugustFALSEFALSE
B172-2E-3B172-2E-219outside roomAMEREXB456-ABCI-7010608620312037AugustFALSEFALSE
B172-2E-4B172-2E-206outside roomAMEREXB456-ABCI-7010084620312037AugustFALSEFALSE
B172-2E-5B172-2E-outside roomAMEREXB456-ABCI-7004396820312037AugustFALSEFALSE
B172-2E-6B172-2E-200by stair 10AMEREXB456-ABCI-7010786520312037AugustFALSEFALSE
B172-2E-7B172-2E-250across from mech.rmAMEREXB456-ABCI-7004489620312037AugustFALSEFALSE
BUILDING-172- penthouseTOTAL= 1FALSEFALSENNN
B172-PenthouseB172-penthouseAMEREXB456-ABCI-7004489320312037AugustFALSEFALSE
Muncie CBOCTOTAL=3
Owned and Inspected by building owner
PERU CBOCTOTAL=4
Owned and Inspected by building owner
Bldg 5 Basement ExtraTOTAL= 51
Please reference Inventory List
QUARTERSTOTAL= 2
EXTINGUISHER #ASSIGNED LOCATIONMANUFACTURESMODEL #SERIAL #6 & 12 year hydroANNUALPassComments
26ABuilding # 26AAMEREXB456I701008862031 / 2037AugustFALSEFALSE
M239Building # 27AAMEREXB456BV-8489432031 / 2037AugustFALSEFALSE
TOTAL ACTIVE EXTINGUISHERS FOR THE MARION CAMPUS = 279