This is a Sources Sought notice from the Aleda E. Lutz VA Medical Center seeking contractors capable of providing Uninterruptible Power Supply (UPS) preventative maintenance and emergency services for the period of February 5, 2025 - February 4, 2026. The contractor must provide APC factory-certified technicians to perform annual maintenance on 2 APC Galaxy 4000 UPS, 11 APC Smart-UPS X, 9 APC Smart-UPS On-line, and 2 Eaton 9PX UPS systems, including battery cabinets and power distribution units. Responses are due by January 13, 2025 at 3:00 PM ET.

The scope includes inspection of power and control wire termination points, system components, power capacitors, inverter and rectifier snubbers, fuses, and performance of operational tests. The contractor must provide their own tools, equipment, and facilities, though the VA will provide basic utilities. Responses must include business information, SAM UEI, NAICS code (541519), business size, and socioeconomic status. This notice may be used to determine potential set-asides. The point of contact is Contracting Officer Alexis Alexander. The contractor must provide 10 business days notice before scheduled maintenance and immediately report any conditions that could jeopardize equipment operation.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sources Sought Notice Sources Sought Notice

SUBJECT*
Uninterruptible Power Supply Preventative and Emergency Services Aleda E. Lutz VA Medical Center

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
48105
SOLICITATION NUMBER*
36C25025Q0218
RESPONSE DATE/TIME/ZONE
01-13-2025 15:00 EASTERN TIME, NEW YORK, USA
ARCHIVE
60 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N

SET-ASIDE

PRODUCT SERVICE CODE*
J061
NAICS CODE*
541519
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Ann Arbor Healthcare System Network Contracting Office 10 2215 Fuller Road Ann Arbor MI 48105

POINT OF CONTACT*

Contracting Officer Alexis S. Alexander Alexis.Alexander1@va.gov 734-222-7169

PLACE OF PERFORMANCE

ADDRESS
Aleda E. Lutz VA Medical Center

1500 Weiss St.

Saginaw MI

POSTAL CODE
48602
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL
https://www.va.gov/saginaw-health-care/
URL DESCRIPTION
Aleda E. Lutz VA Medical Center
AGENCY CONTACT’S EMAIL ADDRESS
Alexis.Alexander1@va.gov
EMAIL DESCRIPTION
Alexis S. Alexander

DESCRIPTION

This Sources Sought/Market Survey Notice is being conducted by Aleda E. Lutz VA Medical Center, 1500 Weiss St., Saginaw, MI 48602 to identify all sources that are capable of providing Uninterruptible Power Supply Preventative and Emergency Services for the period of February 05, 2025 – February 04, 2026, at the discretion of the Government in strict accordance with all schedules, specifications, terms, conditions and provisions of this contract.

General Intention The intention of this statement of work (SOW) is to obtain on-site maintenance, inspection, testing, battery replacement, technical support and repair for the facilities Uninterruptible Power Supply (UPS) systems at the Aleda E. Lutz VA Medical Center.

General Requirements Contractor shall maintain equipment operation as originally specified by the equipment manufacturer.

Contractor shall obtain all licenses, permits, and insurance required to perform all requirements of this Contract without additional expense to the Government. Contractor shall comply with all applicable federal, state, and local laws. Evidence of insurance, licenses, and permits shall be provided to the Contracting Officer before work commences.

Codes and Standards VHA Directive 1028 – Facility Electrical Power Systems OSHA 1910.269 – Electric Power Generation, Transmission, and Distribution, https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=standards&p_id=9868 NFPA 70 – National Electrical Code NFPA70E – Standard for Electrical Safety in the Workplace NFPA 99 – Standard for Healthcare Facilities NFPA 101 – Life Safety Code NFPA 110 – Emergency and Standby Power Systems Joint Commission Accreditation of Healthcare Organizations (Joint Commission) EC.7.40.1 and EC.7.40.7 Government Furnished Property, Materials and Services ALEDA E. LUTZ VA MEDICAL CENTER will not provide office space or operational facilities to the Contractor. The Contractor shall secure and maintain the necessary office space and other facilities required for the performance of this Contract at his/her own expense.

ALEDA E. LUTZ VA MEDICAL CENTER will not provide supplies, materials, tools or equipment to the Contractor. The Contractor shall furnish all supplies, materials, tools and equipment required for the performance of this Contract.

ALEDA E. LUTZ VA MEDICAL CENTER will furnish the following services at existing outlets, for use in those facilities provided by the ALEDA E. LUTZ VA MEDICAL CENTER and as required for the work to be performed under this Contract: electricity, fresh water, sewage service, and non- hazardous refuse collection (from existing collection points).

Contractor Requirements Contractor shall provide mechanics/technicians factory certified through APC. Certificates shall be submitted to the COR.

Contractor shall be responsible for removing and ensuring proper disposal of all hazardous or universal waste generated under requirements of this contract in accordance with the Resource Conservation and Recovery Act and all associated state and local regulations. Documentation of the Disposal shall be supplied to the COR.

Contractor shall provide tools, equipment, specialty items and other items that may be necessary to perform the tasks required under this Contract.

UPS Inventory

Building
Location
Manufacturer / Model
Serial Number
1
B200
APC SYMMETRA PXSY40K40F
F.V.
1
B200
APC PDU PD40G6FK1-M
F.V.
1
2300
APC SMX3000RMLV2U
AS211825120
1
2300
APC SMX3000RMLV2U
AS1630160642
1
2300
APC SMX3000RMLV2U
AS2225352575
1
4309
APC SMX3000RMLV2U
AS2225352575
1
4309
APC SMX3000RMLV2U
AS1630160654
1
4309
APC SMX3000RMLV2U
AS2225352574
1
4309
APC SMX3000RMLV2U
AS2225352580
1
PHB
EATON 9PX1500RT
PA18L42V87
1
PHB
EATON 9PX1500RT
PA18L42V60
2
100
APC SRT2200XLA
AS1811195509
3
B102
APC SRT2200XLA
AS1819393191
4
106
APC SRT2200XLA
AS1811195502
6
209
APC SRT2200XLA
SAS2141393199
9
103
APC SRT2200XLA
AS1811195500
21
100
APC SRT2200XLA
AS1811195508
22
B406
APC G4TUPS65#31431263
C11736190002
22
B406
APC G4TUPS65#31431265
C11736190003
22
B702
APC SMX3000RMLV2U
AS1630160641
22
B702
APC SMX3000RMLV2U
AS1630160652
22
B702
APC SMX3000RMLV2U
AS1630160638
22
B702
APC SMX3000RMLV2U
AS2225352579
30
104A
APC SRT2200XLA
AS1811195506
32
101B
APC SRT2200XLA
SAS2141393196
38
105
APC SRT2200XLA
SAS2141192346

Part II: WORK REQUIREMENTES

2.1Service, Inspection and Testing
A.Contractor shall provide annual maintenance on 2 – APC Galaxy 4000 UPS, 11 – APC Smart-UPS X, 9 – APC Smart-UPS On-line, and 2 – Eaton 9PX UPS, all battery cabinet and power distribution units in accordance with manufacturers recommendations. The contractor shall:

· Inspect all power and control wire termination points and system components.

· Loose connections shall be re-tightened to manufacturers torque specifications.

· Any corrosion shall be removed and treated to prevent future reoccurrence.

· Corrections to be performed where heat discoloration indicates damaged or compromised components.

· Check all power capacitors for swelling, cracking or leakage. Vent caps shall be inspected to ensure less than 1/8” extrusion.

· Check the inverter and rectifier snubbers for burned or broken wires.

· Check all fuses on the DC capacitor deck.

· Perform functional verification to include:

· Perform operational test of the system, including unit transfer and battery discharge.

· Verification of battery condition and operation

· Verification of parallel operation performance

· Verify and implement all required field advisories and field modifications.

· Check all circuit board revisions and update as required.

· Measure and Record:

· Harmonic trap filter currents

· Real and apparent power for each phase

· Input voltage, frequency and current values for both phase to phase and phase to ground

· All low voltage power supply levels

· Battery connection resistances in micro-ohms (when applicable)

B.Contractor shall provide advanced notification to the COR no less than 10 business days prior to scheduled maintenance and service activity. Service must not interfere with needs or demands of the hospital. The V.A. reserves the right to defer proposed service dates based upon the needs of the agency.
C.Contractor shall immediately notify the Engineering COR of any equipment or environmental conditions which impair or jeopardize the safe and continuous functioning of the equipment. Any parts that are deemed to be replaced by the Contractors inspection shall be ordered via separate purchase order.

· be verified, and oil added as needed. Check new seal to ensure there is no oil leak.

If this is a service your business can provide, respond to this Sources Sought by Monday, January 13, 2025; 3:00 P.M. Eastern time. Responses should include: (1) Business Name and Address (2) Point of Contact Name, Phone Number, and E-mail Address (3) SAM UEI and NAICS code (4) Business Size SMALL or LARGE (5) Type of Business SERVICE DISABLED VETERAN OWNED, VETERAN OWNED, 8A, HUBZone, WOMEN-OWNED etc. (6) Applicable GSA/FSS Contract Number (if applies). All businesses eligible to provide this service are encouraged to reply as this information may be used to determine potential set-asides for the above noted service. E-mail responses to: Alexis Alexander, at Alexis.Alexander1@va.gov. (Note: This is NOT A REQUEST FOR QUOTE or an announcement of a solicitation.)