This document is a Presolicitation Notice for the repair of a 750 GPM, 75 HP fire pump at the Richard L. Roudebush VA Medical Center in Indianapolis, IN. The fire pump has failed inspection due to excessive leaking from the packing glands. The contractor will be required to replace and test the packing glands, inspect the shaft bearing and provide a recommendation for replacement, and conduct a full monthly run test per NFPA 25 requirements. The government intends to issue a solicitation for this work on or about November 21, 2024. The procurement is set-aside for service-disabled veteran-owned small businesses (SDVOSBC). Responses are due by 12:00 PM Eastern Time on November 21, 2024. The contracting office is the Network Contracting Office (NCO) 10 of the Department of Veterans Affairs Veterans Health Administration.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Presolicitation Notice Presolicitation Notice
| SUBJECT* |
| Repair Fire Pump (750 GPM, 75 HP). |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 45409 |
| SOLICITATION NUMBER* |
| 36C25025Q0112 |
| RESPONSE DATE/TIME/ZONE |
| 11-21-2024 12:00 PM EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 45 DAYS AFTER THE RESPONSE DATE |
| SET-ASIDE |
| SDVOSBC |
| PRODUCT SERVICE CODE* |
| J012 |
| NAICS CODE* |
| 811310 |
| PLACE OF PERFORMANCE |
| Richard L. Roudebush VAMC |
1481 W. 10th St
Indianapolis IN
| POSTAL CODE |
| 46202 |
| COUNTRY |
| USA |
CONTACT INFORMATION
| CONTRACTING OFFICE ADDRESS |
| Network Contracting Office (NCO) 10 |
US Dept of Veterans Affairs
3140 Governors Place Blvd., Suite 210 Kettering OH 45409
POINT OF CONTACT*
Contract Specialist Brian Rosciszewski Brian.Rosciszewski@VA.gov
DESCRIPTION
Introduction. Richard L. Roudebush operates an electric 750 GPM, 75 HP fire pump for the facility fire protection system. Per NFPA 25 8.3 monthly testing is required to occur for ten minutes. The facility fire pump has failed the inspection due to excessive leaking from the packing glands. Pump is exceeding manufacture recommendations of 45-60 drips per minute.
Requirements. The contractor shall accomplish the following:
a. Contractor shall provide all tools, equipment, material, labor, and supervision necessary to replace and test packing glands to assure NFPA 25 8.3.2.9 (1) (c) compliance.
b. Contractor shall provide all tools, equipment, material, labor, and supervision necessary to inspect shaft bearing and provide recommendation for replacement.
c. Upon completion of work, contractor shall complete full monthly run test based on NFPA 25 8.3 recommendations.
Location is 1481 West 10th St. Indianapolis, IN 46202.
** This is not a solicitation. The government intends to issue a solicitation on or about November 21, 2024 **