This document is an amendment to a combined solicitation for water treatment services at the Dayton VA Medical Center. The amendment answers vendor questions submitted by November 17, 2023 regarding liquid chemicals, equipment monitoring, installation responsibilities, and permitting requirements. No substitutions will be accepted other than what is specified. The bidder will be responsible for new equipment installation and meeting Ohio EPA requirements. Current secondary disinfection units are permitted but the bidder must update one unit's ventilation. Only SaniPure monochloramine units will be accepted. Alternative bids and value options cannot be submitted; vendors must quote the scope of work as written. The reverse osmosis system will follow the new AAMI standard and require semiannual disinfection. The amendment provides average annual water usage and boiler steam output data in response to vendor questions. Bids are due November 24, 2023 at 3:00 PM Eastern Time for this Department of Veterans Affairs opportunity under solicitation number 36C25024Q0102.

View the file

Other files

File Type Posted
36C25024Q0102 0002.docx DOCX document
36C25024Q0102 0001.docx DOCX document
36C25024Q0102.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
Water Treatment Services Dayton VA Medical Center Amendment 3

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
45219
SOLICITATION NUMBER*
36C25024Q0102
RESPONSE DATE/TIME/ZONE
11-24-2023 15:00 EASTERN TIME, NEW YORK, USA
ARCHIVE
30 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
N/A
PRODUCT SERVICE CODE*
H946
NAICS CODE*
221310

CONTRACTING OFFICE ADDRESS

Department of Veterans Affairs Network Contracting Office (NCO) 10 260 E. University Avenue Cincinnati OH 45219

POINT OF CONTACT*

Contract Specialist Michael P Riordan Michael.Riordan@va.gov

PLACE OF PERFORMANCE

ADDRESS
Department of Veterans Affairs

Dayton VA Medical Center

4100 W. Third Street

Dayton OH

POSTAL CODE
45428
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

COMBINED SYNOPSIS/SOLICITATION FOR COMMERCIAL ITEMS

General Information

Document Type:
Amendment 3 to Combined Solicitation/Synopsis
Solicitation Number:
36C25024Q0102
Posted Date:
November 20, 2023
Original Response Date:
November 24, 2023 @3PM
Current Response Date:
November 24, 2023 @3PM
Product or Service Code:
H946
Set Aside:
N/A

NAICS Code:

Wage Determination:

Revision Number:

Date of Revision:

221310 2015-4731 6/30/2023

Contracting Office Address Department of Veterans Affairs Network Contracting Office 10 Cincinnati VA Medical Center 3200 Vine Street Cincinnati, OH 45220 Description The purpose of the Solicitation Amendment (Amendment 3) is to answer the vendor questions that were due by Friday, November 17, 2023, and to the following VAAR clauses to the Solicitation: 852.233-70 and 852.233-71.

The following questions were submitted by 11/17/23 and the answer to each question is noted in BOLD below.

1. Will the VA accept liquid chemicals in place of solid chemicals? Will the VA accept equipment monitored by a provider other than Ackumen?

No liquid chemicals and no substitutions.

1. Who will be responsible for the installation of the new chemical feed controllers/ system for the boilers/ cooling towers?

The responsibility will be on the bidder.

1. Who will be responsible for installation of the monochloramine systems?

This will be the bidder responsibility.

1. Will the VA accept a rep within a 1 hour radius as required by the Ohio EPA vs. the 25 mile radius as specified.

No.

1. Is the current secondary disinfection units permitted through the EPA? Will any of the Permit in place follow to the new system?

Yes, they are currently permitted. Future permits will be the responsibility of the bidder.

1. Are there engineered drawings for the current secondary disinfection units?

Yes.

1. Have the current units in place been utilizing ventilation per the EPA requirements? If not, who is responsible for the ventilation (VA or others)?

Yes, they are except for 410. Bidder would be responsible for updating 410 ventilation.

1. Will the VA accept other acceptable monochloramine units currently being utilized in the U.S. and Ohio and other VA’s that have been accepted per the EPA and Ohio EPA is place of Sani pure?

No

1. Will the VA accept bids with valued alternates to help alleviate the costs of the VA based on the current SOW? (Secondary disinfection, cooling tower, boiler and others per the SOW?

No, please quote what is in the SOW.

1. Will the SPD RO system be following the new AAMI standard 108? If so how many disinfections per year would you like quoted?

Yes. Disinfections will be required semiannually.

1. I was told the RO system in B330-2b100 is being replaced. Are you able to provide specifications on the new unit? Is the storage tank or any of the pretreatment being replaced?

It will be replaced with the same system that is in place. It hasn’t been purchased yet.

1. How often would the new system in B330-2b100 be disinfected?

Disinfections will be required semiannually

1. What is the annual water usage?

Over the last 5 years the VA has used between 112,260kgal – 115,456kgal per year.

1. What is the total pounds per steam per hour on the boiler?

Depending on the weather and load, it will vary from 8,000 Ibs – 35,000 lbs.

There are no other changes to this Solicitation at this time.