_515-21-108 - Drawings - 100_Part7.pdf
PDF 44 MB Posted
- Solicitation number
- 36C25022B0069
About this file
This document provides details on a federal contract opportunity for waterproofing basements at various buildings. The solicitation number is 36C25022B0069 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 for its Z1DA--515-21-108 Waterproof Basements, Various Buildings opportunity. The pre-solicitation notice seeks to waterproof basements at multiple agency facilities but provides no further information on response dates, award timing, pricing requirements, or set-asides.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
B138-A B138-B.1 B138-B.8 B138-D B138-E.2B138-B B138-C B138-E B138-E.9 B138-F B138-G
B138-9
B138-8
B138-7
B138-6
B138-5
B138-4
B138-3
B138-2
B138-1
002E
ELECTRICAL
" 5
1 2
PAINT ENTIRE WALL TO
MATCH EXITING
CORNER TO CORNER
FLOOR PLAN LEGEND
EXISTING NON-FIRE RATED WALL
BENTONITE INJECTION
AREAS - SOFT
SURFACE/EARTH
BENTONITE INJECTION
AREAS - HARD
SURFACE/CONCRETE
3 HUMIDITY/MOISTURE OBSERVED ON FOUNDATION
WALL. CLEAN AND DRY SURFACE. REMOVE ANY
DAMAGED AND DETERIORATED FINSHES. PATCH AND
REPAIR FINISHES TO MATCH ADJACENT SURFACE.
2 REMOVE DAMAGED AND DETERIORATED FINISHES.
INSPECT SURFACE FOR ANY CRACKING IN
FOUNDATION WALLS AND FILL AND SEAL CRACK
WITH HYRDOPHOBIC POLYURETHANE GROUT WHERE
CRACK IS OBSERVED. PATCH AND REPAIR FINSHES
TO MATCH ADJACENT SURFACE.
1 REMOVE DAMAGED AND DETERIORATED FINISHES
AROUND FOUNDATION CRACK WHERE OBSERVED.
FILL AND SEAL CRACK WITH HYRDOPHOBIC
POLYURETHANE GROUT. PATCH AND REPAIR
FINSHES TO MATCH ADJACENT SURFACE
KEYNOTE LEGEND
4 DAMAGED/LEAKING PIPE PENETRATION. REMOVE
EXSTING PIPE SEAL. FIELD VERIFY OPENING WIDTH.
APPLY PIPE SEAL AROUND EXISTING PIPE. FILL
PENETRATION WITH HYDROPHOBIC POLYURETHANE
GROUT TO SEAL OPENING. APPLY NEW PIPE SEAL
AROUND EXISTING PIPE. PATCH AND REPAIR
FINISHES TO MATCH ADJACENT SURFACES AS
REQUIRED. REFER TO DETAIL 01/AE200.
5 INJECT BETOGROUT REMEDIAL WATERPROOFING IN
INDICATED AREA DOWN TO FOUNDATION FOOTING.
REFER TO FOOTING DEPTH SCHEDULE AND DETAIL
02/AE200.
6 DRILL INTO CONCRETE PAD/SIDEWALK AND INJECT
BETOGROUT REMEDIAL WATERPROOFING INTO
CONCRETE AT INDICATED AREA DOWN TO
FOUNDATION FOOTING. PATCH AND REPAIR
CONCRETE AS NEEDED. REFER TO FOOTING DEPTH
SCHEDULE AND DETAIL 02/AE200.
7 REMOVE DAMNGED VINYL FLOORING, CLEAN AND
PREP SURFACE FOR NEW FLOORING INSTALLATION.
REPLACE WITH VCT TO MATCH EXISTING
8 REMOVE EXISTING GUTTER AND DOWNSPOUT.
PATCH AND REPAIR SURFACES AS NEED TO
PREPARE FOR NEW WORK. INSTALL NEW 6"x6"
GUTTER AND DOWNSPOUT AND CONNECT TO
EXISTING PVC STORM WATER SYSTEM.
GENERAL NOTES
1. PRIOR TO COMMENCING EACH NEW PHASE OF WORK
CONTRACTORS ARE TO VERIFY EXISTING FIELD CONDITIONS
AND DIMENSIONS. IMMEDIATELY NOTIFY THE COR OF ALL
DISCREPANCIES OR CONCERNS A MINIMUM OF (10) TEN
WORKING DAYS IN ADVANCE OF THE WORK
2. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS,
EQUIPMENT, TESTING, AND ALL APPURTENANCES TO
COMPLETE THE PROJECT.
3. ALL CONSTRUCTION AREAS ARE TO BE PROPERLY
IDENTIFIED, CLEANED AND MAINTAINED BY THE
CONTRACTOR ON A DAILY BASIS. NO CONSTRUCTION
DEBRIS IS TO REMAIN ON SITE AT PROJECT COMPLETION
4. CONTRACTOR TO VERIFY CONSTRUCTION WASTE
DUMPSTER LOCATIONS WITH THE COR PRIOR TO
BEGINNING ANY DEMOLITION AT EACH BUILDING
5. ALL CONTRACTORS ARE TO PROTECT EXISTING EQUIPMENT,
FINISHES AND BUILDING COMPONENTS FROM
CONSTRUCTION ACTIVITIES.
6. CONTRACTORS SHALL BE RESPONSIBLE FOR ANY/ALL
DAMAGE CAUSED DURING CONSTRUCTION OPERATIONS
INCLUDING BUT NOT LIMITED TO SIDEWALK, CURBS,
BUILDINGS, IRRIGATION, PRIVATE PROPERTY, LAWN
RESTORATION, ETC. THE CONTRACTOR SHALL NOTIFY THE
COR IMMEDIATELY IF ANY DAMAGE OCCURS AS A RESULT
OF WORK ACTIVITIES.
7. CONTRACTOR IS TO TAKE PRECAUTIONARY MEASURES TO
PROTECT ALL TURF, TREES AND PLANTS THAT ARE IN THE
VICINITY OF CONSTRUCTION AREAS AND BE RESPONSIBLE
TO REPAIR/REPLACE ANY DAMAGED VEGETATION AND/OR
PERFORM ANY LAWN RESTORATION AS A RESULT.
8. CONTRACTOR SHALL NOT BLOCK AREAS OF
INGRESS/EGRESS FOR VEHICLE TRAFFIC OR PATIENT/STAFF
ACCESS DURING CONSTRUCTION ACTIVITIES. IF THIS
CANNOT BE AVOIDED, WRITTEN PERMISSION MUST BE
OBTAINED FROM THE COR PRIOR. PROVIDE TRAFFIC CONES
OR BARRICADES AND/OR PROVIDE A PERSON AT THE
SUBJECT AREA TO ALERT PEDESTRIANS DURING WORK.
9. SEE SPECIFICATION FOR HAZARDOUS MATERIAL LEGACY
REPORTS AVAILABILITY. LEAD BASED PAINT WILL LIKELY BE
ENCOUNTERED IN THIS WORK SCOPE. CONTRACTOR SHALL
INCLUDE ABATEMENT OF ALL MATERIAL AFFECTED BY THE
WORK SCOPE AND REFERENCED IN THE LEGACY REPORTS
THAT HAS TESTED OR INDICATED AS ASSUMED POSITIVE. IF
SUSPECTED HAZARDOUS MATERIALS ARE ENCOUNTERED
BEYOND THOSE IN THE OWNER PROVIDED LEGACY
REPORTS, DO NOT DISTURB AND IMMEDIATELY NOTIFY THE
CONTRACTING OFFICER REPRESENTATIVE FOR DIRECTION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PRELIM
IN
A
RY
N O
T FO
R C
O N
STRUC
TIO
N DWG. ___ OF XX
7GAE PROJECT NO.: 220111
Sprinkler:
600 E. Michigan Avenue, Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7GenAE.com
1635 Prince Street
Alexandria, VA 22314
P: 202.617.8485 www.alliance.us.com
100% BID DOCUMENTS
35% SCHEMATIC DESIGN
65% DESIGN DEVELOPMENT
95% CONSTRUCTION DESIGN
12.23.2020
04.29.2021
12.17.2021
100% BID DOCUMENTS 05.02.2022
BUILDING 138 BASEMENT
FLOOR PLAN
WATERPROOF BASEMENTS,
VARIOUS BUILDNGS
5500 ARMSTRONG RD
BATTLE CREEK, MI 49037
515-21-108
PROJECT DIRECTOR
MAY 2, 2022 SCC
100% BID
DOCUMENTS
138.AE100
SCALE: 1/8" = 1'-0"
B138 - BASEMENT FLOOR PLAN INVESTIGATION NOTES
KEY PLAN
PLAN NORTH
BUILDING 138 - IMAGE 1
BUILDING 138 - IMAGE 2
BUILDING 138 - IMAGE 3
Revisions: Date: 8581
JRD
PRELIM
IN
A
RY
N O
T FO
R C
O N
STRUC
TIO
N
BATTLE CREEK
VA MEDICAL
CENTER
W
ID
TH
I N
F
IE
L D
V E R
IF
Y
P E N
E
TR
A
TI
O N
V A
R
IE
S HYDROPHOBIC POLYURETHANE
GROUT TO SEAL
NEW BACKER ROD AND SEALANT
EXISTING PIPE PENETRATING
FOUNDATION WALL. VERIFY PIPE
SIZE IN FIELD
EXISTING CONCRETE FOUNDATION
WALL
/2
EXISTING CONCRETE
FOUNDATION WALL
BENTONITE REMEDIAL
WATERPROOFING LAYER,
INJECTED FROM GRADE
LEVEL DOWN TO
FOOTING; INJECTION
SPACING PER INSTALLERS
STANDARDS
R E F E R
T O
B U
IL
D
IN
G
I M
P R
O V
E M
E N
T S C
H E D
U L E
SEE SHEEET CS-201 FOR
ADJACENT GRADING
REVISIONS WHERE
APPLICABLE
EXSITING BASEMENT FLOOR SLAB.
NOTE: BUILDINGS WITH CRAWL
SPACE HAVE DIRT FLOORS
4"
5" 1' - 0" 5"
4"
EXISTING AREA WELLEXISTING ENG. MACHINERY
001E
/ 4
EXISTING CONCRETE
SLAP SLOPED TO
EXISTING FLOOR DRAIN
CUT BOTTOM OF EXISTING DOOR TO
ALLOW FOR NEW 2" CONCRETE CURB
AND RAMP AND NEW WEATHER STRIP.
PATCH AND REPAIR DOOR AS
NEEDED. PRIME AND PAINT WITH
RUST-INHIBITING PAINT
NEW ALUMINUM THRESHOLD AND
THERMAL BREAK
NEW THERMALLY BROKEN
CONCRETE CURB/RAMP AT EXISTING
DOUBLE DOOR OPENING. SAW-CUT
INTERIOR AND EXTERIOR SLABS TO
CREATE 2" DEEP BY 4" WIDE KEYWAY
HYDROPHILIC WATERSTOP AT BACK
OF EXTERIOR SAW-CUT KEYWAY
EXISTING CONCRETE
FOUNDATION WALL
BENTONITE REMEDIAL
WATERPROOFING LAYER,
INJECTED FROM GRADE
LEVEL DOWN TO
FOOTING; INJECTION
SPACING PER INSTALLERS
STANDARDS
R E F E R
T O
B U
IL
D
IN
G
I M
P R
O V
E M
E N
T S C
H E D
U L E
SEE SHEEET CS-201 FOR
ADJACENT GRADING
REVISIONS WHERE
APPLICABLE
EXSITING BASEMENT FLOOR SLAB.
NOTE: BUILDINGS WITH CRAWL
SPACE HAVE DIRT FLOORS
DRILL HOLES INTO EXISTING
CONCRETE PAD/SIDEWALK AT
INSTALLER'S STANDARD
INTERVAL TO ALLOW FOR
BENTONITE INJECTION. PATCH
AND SEAL HOLES UPON
COMPLETEION OF
INJECTIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PRELIM
IN
A
RY
N O
T FO
R C
O N
STRUC
TIO
N DWG. ___ OF XX
7GAE PROJECT NO.: 220111
Sprinkler:
600 E. Michigan Avenue, Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7GenAE.com
1635 Prince Street
Alexandria, VA 22314
P: 202.617.8485 www.alliance.us.com
100% BID DOCUMENTS
35% SCHEMATIC DESIGN
65% DESIGN DEVELOPMENT
95% CONSTRUCTION DESIGN
12.23.2020
04.29.2021
12.17.2021
100% BID DOCUMENTS 05.02.2022
SCHEDULES AND DETAILS WATERPROOF BASEMENTS,
VARIOUS BUILDNGS
5500 ARMSTRONG RD
BATTLE CREEK, MI 49037
515-21-108
N/A
PROJECT DIRECTOR
MAY 2, 2022 SCC
100% BID
DOCUMENTS
AE200
SCALE: 1 1/2" = 1'-0"AE200
PIPE PENETRATION REPAIR DETAIL01
BUILDING IMPROVEMENT TABLE (ALL QUANTITIES ARE APPROXIMATE)
BUILDING NUMBER BASEMENT DEPTH
LINEAL FEET OF
BENTONITE
WATERPROOFING
INJECTION
(EARTH/SOFT
SURFACE)
LINEAL FEET OF
BENTONITE
WATERPROOFING
INJECTION
(PAVEMENT/HARD
SURFACE)
LINEAL FEET OF
CRACKED
CONCRETE
REPAIR
SQUARE FOOTAGE OF FINISH
PAINT REPAIR SQUARE FOOTAGE OF FLOORING REPAIR MISC. REPAIRS
BUILDING 001 11 '- 0" - - - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 002 6' - 6" - - - - REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 003 8' - 0" 76' - 4" 12' - 0" 10' - 0" - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 004 9' - 6" 25' - 1" - 4' - 0" 75 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 005 5' - 0" 38' - 1" - UPON
DISCOVERY
200 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 006 8' - 0" 47' - 4" 74' - 4" - 165 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 007 12' - 0" 56' - 7" 25' - 0" - 620 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 008 9' - 6" 112' - 8" - 20' - 0" 485 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 009 9' - 6" 82' - 4" - - - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 010 9' - 4" 207' - 2" - - - 290 SF VCT (ARMSTRONG COMMERICAL
STANDARD EXCELON - 59236 LINSEED)
-REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 011 9' - 6" 189' - 8" - 15' - 0" - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 012 9' - 7" 152' - 5" - - - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 013 11' - 0" 209' - 8" 10' - 8" - 920 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 014 2' - 6" 196' - 9" 12' - 0" 5' - 0" 1,020 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 019 8' - 8" 17' - 0" - 8' - 0" - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 020 7' - 8" 51' - 0" - 36' - 0" 60 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 021 8' - 0" 9' - 4" - 10' - 0" 70 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 022 9' - 6" 167' - 10" 194' - 9" - - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 024 9' - 0" - 20' - 6" - - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 027 9' - 0" - 32' - 0" 8' - 0" 220 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 030 10' - 3" - 145' - 4" 20' - 0" 620 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 039 11'- 0" 59 ' -0" - - 220 SF 15 SF LVT TO MATCH EXISTING -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 082 9' - 0" 55' - 8" 61' - 11" - 145 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 083 11' - 6" 64' - 2" - - - - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 084 11' - 6" 126' - 2" - - 320 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 127 8' - 6" - 14' - 9" - - - -REGRADING (REFER TO CIVIL DRAWINGS)
-16' - 4" GUTTER AND DOWNSPOUT REPLACEMENT
BUILDING 134 11' - 7" 25' - 9" - - 120 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
BUILDING 138 13' - 10" 14' - 0" - - 150 SF - -REGRADING (REFER TO CIVIL DRAWINGS)
SCALE: 3/4" = 1'-0"AE200
BENTONITE WATERPROOFING DETAIL - THROUGH
SOFTSCAPE02
SCALE: 1 1/2" = 1'-0"AE200
BUILDING 134 - CONCRETE CURB/RAMP DETAIL04
SCALE: 3/4" = 1'-0"AE200
BENTONITE WATERPROOFING DETAIL - THROUGH
CONCRETE PAD/SIDEWALK03
Revisions: Date: 8582
JRD
PRELIM
IN
A
RY
N O
T FO
R C
O N
STRUC
TIO
N
BATTLE CREEK
+/-5 LF MASONRY
CRACK REPAIR
+/-5 LF MASONRY
CRACK REPAIR
+/-10 LF MASONRY
CRACK REPAIR 6
+/-15 LF MASONRY
CRACK REPAIR
+/-10 LF MASONRY
CRACK REPAIR
+/-1 LF OF CONCRETE
FOUNDATION CRACK
REPAIR
+/-15 LF MASONRY
CRACK REPAIR
+/-15 LF OF CONCRETE
FOUNDATION CRACK
REPAIR
160' - 0"
+/-5 LF OF CONCRETE
FOUNDATION CRACK
REPAIR
+/-20 SF OF PAINT
TO MATCH EXISTING
100' - 0"
6 +/-15 LF MASONRY
CRACK REPAIR
' - 0
110' - 0
110' - 0
+/-60 LF OF
CONCRETE
FOUNDATION
CRACK REPAIR
+/-15 LF OF MASONRY
CRACK REPAIR
+/-50 LF OF MASONRY
CRACK REPAIR
+/-30 LF OF MASONRY
CRACK REPAIR
+/-10 LF MASONRY
CRACK REPAIR
AVERAGE
FOUNDATION
DEPTH: 4'-0"
AVERAGE
FOUNDATION
DEPTH: 6'-0"
FLOOR PLAN LEGEND
EXISTING NON-FIRE RATED WALL
BENTONITE INJECTION
AREAS - SOFT
SURFACE/EARTH
BENTONITE INJECTION
AREAS - HARD
SURFACE/CONCRETE
GENERAL NOTES
1. PRIOR TO COMMENCING EACH NEW PHASE OF WORK
CONTRACTORS ARE TO VERIFY EXISTING FIELD CONDITIONS
AND DIMENSIONS. IMMEDIATELY NOTIFY THE COR OF ALL
DISCREPANCIES OR CONCERNS A MINIMUM OF (10) TEN
WORKING DAYS IN ADVANCE OF THE WORK
2. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS,
EQUIPMENT, TESTING, AND ALL APPURTENANCES TO
COMPLETE THE PROJECT.
3. ALL CONSTRUCTION AREAS ARE TO BE PROPERLY
IDENTIFIED, CLEANED AND MAINTAINED BY THE
CONTRACTOR ON A DAILY BASIS. NO CONSTRUCTION
DEBRIS IS TO REMAIN ON SITE AT PROJECT COMPLETION
4. CONTRACTOR TO VERIFY CONSTRUCTION WASTE
DUMPSTER LOCATIONS WITH THE COR PRIOR TO
BEGINNING ANY DEMOLITION AT EACH BUILDING
5. ALL CONTRACTORS ARE TO PROTECT EXISTING EQUIPMENT,
FINISHES AND BUILDING COMPONENTS FROM
CONSTRUCTION ACTIVITIES.
6. CONTRACTORS SHALL BE RESPONSIBLE FOR ANY/ALL
DAMAGE CAUSED DURING CONSTRUCTION OPERATIONS
INCLUDING BUT NOT LIMITED TO SIDEWALK, CURBS,
BUILDINGS, IRRIGATION, PRIVATE PROPERTY, LAWN
RESTORATION, ETC. THE CONTRACTOR SHALL NOTIFY THE
COR IMMEDIATELY IF ANY DAMAGE OCCURS AS A RESULT
OF WORK ACTIVITIES.
7. CONTRACTOR IS TO TAKE PRECAUTIONARY MEASURES TO
PROTECT ALL TURF, TREES AND PLANTS THAT ARE IN THE
VICINITY OF CONSTRUCTION AREAS AND BE RESPONSIBLE
TO REPAIR/REPLACE ANY DAMAGED VEGETATION AND/OR
PERFORM ANY LAWN RESTORATION AS A RESULT.
8. CONTRACTOR SHALL NOT BLOCK AREAS OF
INGRESS/EGRESS FOR VEHICLE TRAFFIC OR PATIENT/STAFF
ACCESS DURING CONSTRUCTION ACTIVITIES. IF THIS
CANNOT BE AVOIDED, WRITTEN PERMISSION MUST BE
OBTAINED FROM THE COR PRIOR. PROVIDE TRAFFIC CONES
OR BARRICADES AND/OR PROVIDE A PERSON AT THE
SUBJECT AREA TO ALERT PEDESTRIANS DURING WORK.
9. SEE SPECIFICATION FOR HAZARDOUS MATERIAL LEGACY
REPORTS AVAILABILITY. LEAD BASED PAINT WILL LIKELY BE
ENCOUNTERED IN THIS WORK SCOPE. CONTRACTOR SHALL
INCLUDE ABATEMENT OF ALL MATERIAL AFFECTED BY THE
WORK SCOPE AND REFERENCED IN THE LEGACY REPORTS
THAT HAS TESTED OR INDICATED AS ASSUMED POSITIVE. IF
SUSPECTED HAZARDOUS MATERIALS ARE ENCOUNTERED
BEYOND THOSE IN THE OWNER PROVIDED LEGACY
REPORTS, DO NOT DISTURB AND IMMEDIATELY NOTIFY THE
CONTRACTING OFFICER REPRESENTATIVE FOR DIRECTION.
KEYNOTE LEGEND
2 REMOVE DAMAGED AND DETERIORATED FINISHES.
INSPECT SURFACE FOR ANY CRACKING IN
FOUNDATION WALLS AND FILL AND SEAL CRACK
WITH HYRDOPHOBIC POLYURETHANE GROUT WHERE
CRACK IS OBSERVED. PATCH AND REPAIR FINSHES
TO MATCH ADJACENT SURFACE.
6 REMOVE DAMAGED AND DETERIORATED FINISHES
AND MORTAR AT MASONRY CRACK BETWEEN FIRST
MASONRY COURSE AND TOP OF CONCRETE
FOUNDATION WALL. PATCH AND SEAL CRACK WITH
NEW MORTAR. PATCH AND REPAIR FINISHES TO
MATCH ADJACENT SURFACES.
1 REMOVE DAMAGED AND DETERIORATED FINISHES
AROUND FOUNDATION CRACK WHERE OBSERVED.
FILL AND SEAL CRACK WITH HYRDOPHOBIC
POLYURETHANE GROUT. PATCH AND REPAIR
FINSHES TO MATCH ADJACENT SURFACE
5 INJECT BETOGROUT REMEDIAL WATERPROOFING IN
INDICATED AREA DOWN TO FOUNDATION FOOTING.
REFER TO FOOTING DEPTH SCHEDULE AND DETAIL
02/AE200.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
DWG. ___ OF XX
7GAE PROJECT NO.: 220111
Sprinkler:
600 E. Michigan Avenue, Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7GenAE.com
1635 Prince Street
Alexandria, VA 22314
P: 202.617.8485 www.alliance.us.com
100% BID DOCUMENTS
35% SCHEMATIC DESIGN
65% DESIGN DEVELOPMENT
95% CONSTRUCTION DESIGN
12.23.2020
04.29.2021
12.17.2021
100% BID DOCUMENTS 05.02.2022
ENCLOSED WALKWAY FLOOR
PLAN - AREA A
WATERPROOF BASEMENTS,
VARIOUS BUILDNGS
5500 ARMSTRONG RD
BATTLE CREEK, MI 49037
515-21-108
PROJECT DIRECTOR
MAY 2, 2022 Checker Author
100% BID
DOCUMENTS
CW-AE100A
Revisions: Date:
SCALE: 1/32" = 1'-0"CW-AE100A
COVERED WALKWAY FLOOR PLAN - AREA A1
KEY PLAN
PLAN NORTH
COVERED WALKWAY - IMAGE 1
COVERED WALKWAY - IMAGE 2
COVERED WALKWAY - IMAGE 3
COVERED WALKWAY - IMAGE 4
COVERED WALKWAY - IMAGE 5
COVERED WALKWAY - IMAGE 6
COVERED WALKWAY - IMAGE 7
COVERED WALKWAY - IMAGE 8
COVERED WALKWAY - IMAGE 9
COVERED WALKWAY - IMAGE 10
COVERED WALKWAY - IMAGE 11
JRD
PRELIM
IN
A
RY
N O
T FO
R C
O N
STRUC
TIO
N
BATTLE CREEK
DN
+/-10 LF OF MASONRY
CRACK REPAIR
+/-10 LF OF MASONRY
CRACK REPAIR
+/-5 LF OF CONCRETE
FOUNDATION CRACK
REPAIR
+/-5 LF OF CONCRETE
FOUNDATION CRACK
REPAIR
+/-5 LF OF MASONRY
CRACK REPAIR
+/-20 LF OF
CONCRETE
FOUNDATION
CRACK REPAIR
+/-10 LF OF MASONRY
CRACK REPAIR
+/-60 SF OF PAINT TO
MATCH EXISTING
+/-40 LF OF
CONCRETE
FOUNDATION
CRACK REPAIR
+/-20 LF OF MASONRY
CRACK REPAIR
6 +/-30 LF OF MASONRY
CRACK REPAIR
6 +/-30 LF OF MASONRY
CRACK REPAIR
100 SF OF PAINT TO
MATCH EXISTING
100 SF OF PAINT TO
MATCH EXISTING
+/-10 LF OF
MASONRY
CRACK
REPAIR 9
+/-5 LF OF
CONCRETE
FOUNDATION
CRACK REPAIR
+/-15 LF OF
CONCRETE
FOUNDATION
CRACK REPAIR
+/-5 LF OF
CONCRETE
FOUNDATION
CRACK REPAIR
100 SF OF PAINT TO
MATCH EXISTING
AVERAGE
FOUNDATION
DEPTH: 6'-0"
FLOOR PLAN LEGEND
EXISTING NON-FIRE RATED WALL
BENTONITE INJECTION
AREAS - SOFT
SURFACE/EARTH
BENTONITE INJECTION
AREAS - HARD
SURFACE/CONCRETE
GENERAL NOTES
1. PRIOR TO COMMENCING EACH NEW PHASE OF WORK
CONTRACTORS ARE TO VERIFY EXISTING FIELD CONDITIONS
AND DIMENSIONS. IMMEDIATELY NOTIFY THE COR OF ALL
DISCREPANCIES OR CONCERNS A MINIMUM OF (10) TEN
WORKING DAYS IN ADVANCE OF THE WORK
2. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS,
EQUIPMENT, TESTING, AND ALL APPURTENANCES TO
COMPLETE THE PROJECT.
3. ALL CONSTRUCTION AREAS ARE TO BE PROPERLY
IDENTIFIED, CLEANED AND MAINTAINED BY THE
CONTRACTOR ON A DAILY BASIS. NO CONSTRUCTION
DEBRIS IS TO REMAIN ON SITE AT PROJECT COMPLETION
4. CONTRACTOR TO VERIFY CONSTRUCTION WASTE
DUMPSTER LOCATIONS WITH THE COR PRIOR TO
BEGINNING ANY DEMOLITION AT EACH BUILDING
5. ALL CONTRACTORS ARE TO PROTECT EXISTING EQUIPMENT,
FINISHES AND BUILDING COMPONENTS FROM
CONSTRUCTION ACTIVITIES.
6. CONTRACTORS SHALL BE RESPONSIBLE FOR ANY/ALL
DAMAGE CAUSED DURING CONSTRUCTION OPERATIONS
INCLUDING BUT NOT LIMITED TO SIDEWALK, CURBS,
BUILDINGS, IRRIGATION, PRIVATE PROPERTY, LAWN
RESTORATION, ETC. THE CONTRACTOR SHALL NOTIFY THE
COR IMMEDIATELY IF ANY DAMAGE OCCURS AS A RESULT
OF WORK ACTIVITIES.
7. CONTRACTOR IS TO TAKE PRECAUTIONARY MEASURES TO
PROTECT ALL TURF, TREES AND PLANTS THAT ARE IN THE
VICINITY OF CONSTRUCTION AREAS AND BE RESPONSIBLE
TO REPAIR/REPLACE ANY DAMAGED VEGETATION AND/OR
PERFORM ANY LAWN RESTORATION AS A RESULT.
8. CONTRACTOR SHALL NOT BLOCK AREAS OF
INGRESS/EGRESS FOR VEHICLE TRAFFIC OR PATIENT/STAFF
ACCESS DURING CONSTRUCTION ACTIVITIES. IF THIS
CANNOT BE AVOIDED, WRITTEN PERMISSION MUST BE
OBTAINED FROM THE COR PRIOR. PROVIDE TRAFFIC CONES
OR BARRICADES AND/OR PROVIDE A PERSON AT THE
SUBJECT AREA TO ALERT PEDESTRIANS DURING WORK.
9. SEE SPECIFICATION FOR HAZARDOUS MATERIAL LEGACY
REPORTS AVAILABILITY. LEAD BASED PAINT WILL LIKELY BE
ENCOUNTERED IN THIS WORK SCOPE. CONTRACTOR SHALL
INCLUDE ABATEMENT OF ALL MATERIAL AFFECTED BY THE
WORK SCOPE AND REFERENCED IN THE LEGACY REPORTS
THAT HAS TESTED OR INDICATED AS ASSUMED POSITIVE. IF
SUSPECTED HAZARDOUS MATERIALS ARE ENCOUNTERED
BEYOND THOSE IN THE OWNER PROVIDED LEGACY
REPORTS, DO NOT DISTURB AND IMMEDIATELY NOTIFY THE
CONTRACTING OFFICER REPRESENTATIVE FOR DIRECTION.
KEYNOTE LEGEND
2 REMOVE DAMAGED AND DETERIORATED FINISHES.
INSPECT SURFACE FOR ANY CRACKING IN
FOUNDATION WALLS AND FILL AND SEAL CRACK
WITH HYRDOPHOBIC POLYURETHANE GROUT WHERE
CRACK IS OBSERVED. PATCH AND REPAIR FINSHES
TO MATCH ADJACENT SURFACE.
6 REMOVE DAMAGED AND DETERIORATED FINISHES
AND MORTAR AT MASONRY CRACK BETWEEN FIRST
MASONRY COURSE AND TOP OF CONCRETE
FOUNDATION WALL. PATCH AND SEAL CRACK WITH
NEW MORTAR. PATCH AND REPAIR FINISHES TO
MATCH ADJACENT SURFACES.
1 REMOVE DAMAGED AND DETERIORATED FINISHES
AROUND FOUNDATION CRACK WHERE OBSERVED.
FILL AND SEAL CRACK WITH HYRDOPHOBIC
POLYURETHANE GROUT. PATCH AND REPAIR
FINSHES TO MATCH ADJACENT SURFACE
5 INJECT BETOGROUT REMEDIAL WATERPROOFING IN
INDICATED AREA DOWN TO FOUNDATION FOOTING.
REFER TO FOOTING DEPTH SCHEDULE AND DETAIL
02/AE200.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
DWG. ___ OF XX
7GAE PROJECT NO.: 220111
Sprinkler:
600 E. Michigan Avenue, Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7GenAE.com
1635 Prince Street
Alexandria, VA 22314
P: 202.617.8485 www.alliance.us.com
100% BID DOCUMENTS
35% SCHEMATIC DESIGN
65% DESIGN DEVELOPMENT
95% CONSTRUCTION DESIGN
12.23.2020
04.29.2021
12.17.2021
100% BID DOCUMENTS 05.02.2022
ENCLOSED WALKWAY FLOOR
PLAN - AREA B
WATERPROOF BASEMENTS,
VARIOUS BUILDNGS
5500 ARMSTRONG RD
BATTLE CREEK, MI 49037
515-21-108
PROJECT DIRECTOR
MAY 2, 2022 Checker Author
100% BID
DOCUMENTS
CW-AE100B
Revisions: Date:
SCALE: 1/32" = 1'-0"CW-AE100B
COVERED WALKWAY FLOOR PLAN - AREA B1
KEY PLAN
PLAN NORTH
COVERED WALKWAY - IMAGE 12
COVERED WALKWAY - IMAGE 13
COVERED WALKWAY - IMAGE 14
COVERED WALKWAY - IMAGE 15
COVERED WALKWAY - IMAGE 16
COVERED WALKWAY - IMAGE 17
COVERED WALKWAY - IMAGE 18
COVERED WALKWAY - IMAGE 19
COVERED WALKWAY - IMAGE 20
JRD
PRELIM
IN
A
RY
N O
T FO
R C
O N
STRUC
TIO
N
BATTLE CREEK
+/-5 LF OF
CONCRETE
FOUNDATION
CRACK REPAIR
+/-5 LF OF
CONCRETE
FOUNDATION
CRACK REPAIR
28' - 0"
' - 0
5 1
+/-70 LF OF CONCRETE
FOUNDATION CRACK
REPAIR
AVERAGE
FOUNDATION
DEPTH: 6'-0"
AVERAGE
FOUNDATION
DEPTH: 8'-0"
FLOOR PLAN LEGEND
EXISTING NON-FIRE RATED WALL
BENTONITE INJECTION
AREAS - SOFT
SURFACE/EARTH
BENTONITE INJECTION
AREAS - HARD
SURFACE/CONCRETE
GENERAL NOTES
1. PRIOR TO COMMENCING EACH NEW PHASE OF WORK
CONTRACTORS ARE TO VERIFY EXISTING FIELD CONDITIONS
AND DIMENSIONS. IMMEDIATELY NOTIFY THE COR OF ALL
DISCREPANCIES OR CONCERNS A MINIMUM OF (10) TEN
WORKING DAYS IN ADVANCE OF THE WORK
2. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS,
EQUIPMENT, TESTING, AND ALL APPURTENANCES TO
COMPLETE THE PROJECT.
3. ALL CONSTRUCTION AREAS ARE TO BE PROPERLY
IDENTIFIED, CLEANED AND MAINTAINED BY THE
CONTRACTOR ON A DAILY BASIS. NO CONSTRUCTION
DEBRIS IS TO REMAIN ON SITE AT PROJECT COMPLETION
4. CONTRACTOR TO VERIFY CONSTRUCTION WASTE
DUMPSTER LOCATIONS WITH THE COR PRIOR TO
BEGINNING ANY DEMOLITION AT EACH BUILDING
5. ALL CONTRACTORS ARE TO PROTECT EXISTING EQUIPMENT,
FINISHES AND BUILDING COMPONENTS FROM
CONSTRUCTION ACTIVITIES.
6. CONTRACTORS SHALL BE RESPONSIBLE FOR ANY/ALL
DAMAGE CAUSED DURING CONSTRUCTION OPERATIONS
INCLUDING BUT NOT LIMITED TO SIDEWALK, CURBS,
BUILDINGS, IRRIGATION, PRIVATE PROPERTY, LAWN
RESTORATION, ETC. THE CONTRACTOR SHALL NOTIFY THE
COR IMMEDIATELY IF ANY DAMAGE OCCURS AS A RESULT
OF WORK ACTIVITIES.
7. CONTRACTOR IS TO TAKE PRECAUTIONARY MEASURES TO
PROTECT ALL TURF, TREES AND PLANTS THAT ARE IN THE
VICINITY OF CONSTRUCTION AREAS AND BE RESPONSIBLE
TO REPAIR/REPLACE ANY DAMAGED VEGETATION AND/OR
PERFORM ANY LAWN RESTORATION AS A RESULT.
8. CONTRACTOR SHALL NOT BLOCK AREAS OF
INGRESS/EGRESS FOR VEHICLE TRAFFIC OR PATIENT/STAFF
ACCESS DURING CONSTRUCTION ACTIVITIES. IF THIS
CANNOT BE AVOIDED, WRITTEN PERMISSION MUST BE
OBTAINED FROM THE COR PRIOR. PROVIDE TRAFFIC CONES
OR BARRICADES AND/OR PROVIDE A PERSON AT THE
SUBJECT AREA TO ALERT PEDESTRIANS DURING WORK.
9. SEE SPECIFICATION FOR HAZARDOUS MATERIAL LEGACY
REPORTS AVAILABILITY. LEAD BASED PAINT WILL LIKELY BE
ENCOUNTERED IN THIS WORK SCOPE. CONTRACTOR SHALL
INCLUDE ABATEMENT OF ALL MATERIAL AFFECTED BY THE
WORK SCOPE AND REFERENCED IN THE LEGACY REPORTS
THAT HAS TESTED OR INDICATED AS ASSUMED POSITIVE. IF
SUSPECTED HAZARDOUS MATERIALS ARE ENCOUNTERED
BEYOND THOSE IN THE OWNER PROVIDED LEGACY
REPORTS, DO NOT DISTURB AND IMMEDIATELY NOTIFY THE
CONTRACTING OFFICER REPRESENTATIVE FOR DIRECTION.
KEYNOTE LEGEND
2 REMOVE DAMAGED AND DETERIORATED FINISHES.
INSPECT SURFACE FOR ANY CRACKING IN
FOUNDATION WALLS AND FILL AND SEAL CRACK
WITH HYRDOPHOBIC POLYURETHANE GROUT WHERE
CRACK IS OBSERVED. PATCH AND REPAIR FINSHES
TO MATCH ADJACENT SURFACE.
6 REMOVE DAMAGED AND DETERIORATED FINISHES
AND MORTAR AT MASONRY CRACK BETWEEN FIRST
MASONRY COURSE AND TOP OF CONCRETE
FOUNDATION WALL. PATCH AND SEAL CRACK WITH
NEW MORTAR. PATCH AND REPAIR FINISHES TO
MATCH ADJACENT SURFACES.
1 REMOVE DAMAGED AND DETERIORATED FINISHES
AROUND FOUNDATION CRACK WHERE OBSERVED.
FILL AND SEAL CRACK WITH HYRDOPHOBIC
POLYURETHANE GROUT. PATCH AND REPAIR
FINSHES TO MATCH ADJACENT SURFACE
5 INJECT BETOGROUT REMEDIAL WATERPROOFING IN
INDICATED AREA DOWN TO FOUNDATION FOOTING.
REFER TO FOOTING DEPTH SCHEDULE AND DETAIL
02/AE200.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
DWG. ___ OF XX
7GAE PROJECT NO.: 220111
Sprinkler:
600 E. Michigan Avenue, Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7GenAE.com
1635 Prince Street
Alexandria, VA 22314
P: 202.617.8485 www.alliance.us.com
100% BID DOCUMENTS
35% SCHEMATIC DESIGN
65% DESIGN DEVELOPMENT
95% CONSTRUCTION DESIGN
12.23.2020
04.29.2021
12.17.2021
100% BID DOCUMENTS 05.02.2022
ENCLOSED WALKWAY FLOOR
PLAN - AREA C
WATERPROOF BASEMENTS,
VARIOUS BUILDNGS
5500 ARMSTRONG RD
BATTLE CREEK, MI 49037
515-21-108
PROJECT DIRECTOR
MAY 2, 2022 Checker Author
100% BID
DOCUMENTS
CW-AE100C
Revisions: Date:
SCALE: 1/32" = 1'-0"CW-AE100C
COVERED WALKWAY FLOOR PLAN - AREA C1
KEY PLAN
PLAN NORTH
COVERED WALKWAY - IMAGE 21
COVERED WALKWAY - IMAGE 22
JRD
PRELIM
IN
A
RY
N O
T FO
R C
O N
STRUC
TIO
N
BATTLE CREEK
| 15 000.CG101 |
| D101 |
| 15 000.CG102 |
| Layout1 |
| 15 000.CG103 |
| CG-101 |
| 15 000.CG201 |
| 101 |
| 15 000.CJ301 |
| Layout1 |
| 15 000.CS101 |
| 101 |
| 15 001.CG101 |
| 102 |
| 15 001.LS101 |
| 102 |
| 15 002.CG101 |
| 002.CG101 |
| 15 002.LS101 |
| 002.LS101 |
| 15 003.CG101 |
| 003.CG101 |
| 15 003.LS101 |
| 003.LS101 |
| 15 004.CG101 |
| 004.CG101 |
| 15 004.LS101 |
| 004.LS101 |
| 15 005.CG101 |
| 005.CG101 |
| 15 005.LS101 |
| 005.LS101 |
| 15 006.CG101 |
| 006.CG101 |
| 15 006.LS101 |
| 006.LS101 |
| 15 007.CG101 |
| 007.CG101 |
| 15 007.LS101 |
| 007.LS101 |
| 15 008.CG101 |
| 008.CG101 |
| 15 008.LS101 |
| 008.LS101 |
| 15 009.CG101 |
| 009.CG101 |
| 15 009.LS101 |
| 009.LS101 |
| 15 010.CG101 |
| 010.CG101 |
| 15 010.LS101 |
| 010.LS101 |
| 15 011.CG101 |
| 011.CG101 |
| 15 011.LS101 |
| 011.LS101 |
| 15 012.CG101 |
| 104 |
| 15 012.LS101 |
| 012.LS101 |
| 15 013.CG101 |
| 013.CG101 |
| 15 013.LS101 |
| 013.LS101 |
| 15 014.CG101 |
| 014.CG101 |
| 15 014.LS101 |
| 014.LS101 |
| 15 019.020.021.CG101 |
| 109 |
| 15 019.020.021.LS101 |
| 019.020.021.LS101 |
| 15 024.CG101 |
| 024.CG101 |
| 15 024.LS101 |
| 024.LS101 |
| 15 039.CG101 |
| 039.CG101 |
| 15 039.LS101 |
| 039.LS101 |
| 15 082.CG101 |
| 082.CG101 |
| 15 082.LS101 |
| 082.LS101 |
| 15 083.CG101 |
| 083.CG101 |
| 15 083.LS101 |
| 083.LS101 |
| 15 084.CG101 |
| 084.CG101 |
| 15 084.LS101 |
| 084.LS101 |
| 15 127.CG101 |
| 127.CG101 |
| 15 127.LS101 |
| 127.LS101 |
| 15 134.CG101 |
| 134.CG101 |
| 15 134.LS101 |
| 134.LS101 |
| 15 138.CG101 |
| 138.CG101 |
| 15 138.LS101 |
| 105 |
| 34 138-AE100 - BUILDING 138 BASEMENT FLOOR PLAN |