Revised Drawing M-701 Temperature Controls.pdf
PDF 413 KB Posted
- Attached to
- Y1DZ--Expand MRI Suite Project 541-CSI-103
- Solicitation number
- 36C25020B0043
About this file
This pre-solicitation notice provides details for an upcoming solicitation to expand an MRI suite at the Louis Stokes VA Medical Center in Cleveland, Ohio. The project scope includes adding a third 3T MRI unit to the existing MRI suite, renovating connecting areas, and reworking surrounding site, landscaping, sidewalks, and physical barriers. The estimated period of performance is 548 calendar days. The solicitation is designated as a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses, with a minimum 15% work requirement for the SDVOSB prime or subcontractor. The NAICS code is 236220 for commercial and institutional building construction up to $39.5 million. Interested parties should register to receive updates on www.beta.SAM.gov. A site visit will be scheduled, and questions are to be submitted in writing to the contracting officer.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
74490
L.D. HENDRIX, JR
GN
S S
A
I ON EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes
Cleveland
VA Medical
Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consulting Engineers
BARBER & HOFFMAN, INC.
2217 East 9th Street, Suite 350 Cleveland, OH 44115-1257 216-875-0100/ (F) 216-875-0111 barberhoffman.com
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF PERSPECTUS
ARCHITECTURE.
COPYRIGHT C 2019.
13212 Shaker Square Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
Expand MRI Suite 541-CSI-103
CLEVELAND, OHIO
19026
Z M y D o c u m e n ts
\1
F F
H C
F R c c a m p b e ll.
rv t
/1
/2
:3
:1
P
M
M-701
TEMPERATURE CONTROLS
11/15/2019 LDH DML
AHU-N-1-1 CONTROL DIAGRAM
RETURN AIR TEMP - MIXED AIR TEMP
RETURN AIR TEMP - OUTSIDE AIR TEMP
%OA= X 100
TH
I - RETURN AIRFLOW
OA
H L T
I - FREEZESTAT
N.C.
N.O.
M
M
O - MIXED AIR DAMPER
T
I - MIXED AIR TEMP (TS-1)
I - RETURN AIR TEMP (TS-5)
N.C.
STEAM
O - PREHEAT VALVE
LPR
LPS
RA
I - RETURN AIR SMOKE DETECTOR
EA
I - RETURN AIR HUMIDITY
I - PREFILTER STATUS
CHW
O - COOLING VALVE
CHS
CHR
I - SUPPLY AIRFLOW
MM
M
M
O - RETURN SMOKE DAMPER
T
I - OUTDOOR AIR TEMP
I - OUTSIDE AIRFLOW
T
T
I - AIR TEMP (TS-3)
I - SMOKE DAMPER STATUS
H L T
I - SUPPLY AIR TEMP (TS-4)
I - SUPPLY AIR SMOKE DETECTOR
I - SUPPLY AIR HUMIDITY
O - HUMIDIFIER
O - HUMIDIFIER ENABLE
H L
I - HIGH STATIC SHUTDOWN
I - FINAL FILTER STATUS
H L
I - SUPPLY AIR STATIC PRESSURE
SA
H
STM
M
M
CS
VSMC
O - SUPPLY FAN ENABLE/DISABLE
I - SUPPLY FAN STATUS
O - SUPPLY FAN VFD SPEED
I - SUPPLY FAN VFD FAULT
M
O - DISCHARGE SMOKE DAMPER
I - SUPPLY FAN VFD HOA
I - SMOKE DAMPER STATUS
M
CS
VSMC
O - RETURN FAN ENABLE/DISABLE
I - RETURN FAN STATUS
O - RETURN FAN VFD SPEED
I - RETURN FAN VFD FAULT
I - RETURN FAN VFD HOA
O - OUTSIDE AIR DAMPER
O - EXHAUST AIR DAMPER
MINIMUM
I - AIR TEMP
(TS-2)
RF
SF
H L
I - LOW STATIC SHUTDOWN
36"
LOCATE
APPROXIMATELY 2/3
DISTANCE DOWN
LONGEST DUCT RUN
1. RUN CONDITIONS - SCHEDULED
1.1 THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.
2. FREEZE PROTECTION
2.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A
FREEZESTAT STATUS. WHEN THE FREEZE STAT IS TRIPPED THE FOLLOWING
SEQUENCE SHALL OCCUR:
2.2 THE OUTSIDE AIR AND EXHAUST DAMPERS SHALL CLOSE AND THE MIXED AIR
DAMPER SHALL BE OPEN.
2.3 STEAM PREHEAT COIL VALVE SHALL OPEN TO 100%(ADJ)
2.4 COOLING COIL VALVE SHALL OPEN TO 50%(ADJ)
3. HIGH/LOW STATIC SAFETY SHUTDOWN
3.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH
STATIC SHUTDOWN SIGNAL. HIGH STATIC ALARM SETPOINT SHALL BE 1" BELOW
DUCTWORK PRESSURE CLASS.
3.2 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A LOW
STATIC SHUTDOWN SIGNAL. LOW STATIC ALARM SETPOINT SHALL BE NEGATIVE 2" S.P.
4. SMOKE DETECTION
4.1 THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON A DETECTOR TRIP ON
SUPPLY AIR OR RETURN AIR SMOKE DETECTOR. DISCHARGE AND RETURN SMOKE
DAMPERS SHALL CLOSE IN THIS EVENT.
5. SUPPLY FAN(S)
5.1 THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS
SHUTDOWN ON SAFETIES.
5.2 ALARMS:
SUPPLY FAN FAILURE
6. SUPPLY AIR DUCT STATIC PRESSURE CONTROL
6.1 THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL MODULATE
THE SUPPLY FAN VFD SPEED TO MAINTAIN THE DUCT STATIC PRESSURE SETPOINT.
THE SUPPLY FAN VFD SPEED SHALL NOT DROP BELOW 30%(ADJ.). THE INITIAL DUCT
STATIC PRESSURE SETPOINT SHALL BE 1.0", AND BE ADJUSTED UP DURING THE
BALANCING PROCESS. THE FINAL DUCT STATIC PRESSURE SETPOINT SHALL BE
DETERMINED, SET, AND DOCUMENTED BY THE BALANCING CONTRACTOR. THE
SETPOINT SHALL BE SUFFICIENT TO MEET THE VAV BOX AIRFLOW REQUIREMENTS
DURING DESIGN CONDITIONS.
6.2 ALARMS:
HIGH SUPPLY FAN STATIC PRESSURE
LOW SUPPLY FAN STATIC PRESSURE
SUPPLY FAN VFD FAULT
7. RETURN FAN(S)
7.1 THE RETURN FAN SHALL RUN WHENEVER THE SUPPLY FAN RUNS.
7.2 ALARMS
RETURN FAN FAILURE
RETURN FAN VFD FAULT
8. RETURN AIRFLOW
8.1 THE RETURN FAN VFD SHALL MODULATE IN UNISON WITH THE SUPPLY FAN VFD.
RETURN AIRFLOW SETPOINT SHALL BE EQUAL TO SUPPLY AIR FLOW MINUS 10%(ADJ.)
AND MINUS EXHAUST AIR FLOW. THE RETURN FAN VFD SPEED SHALL NOT DROP
BELOW 20%(ADJ.)
8.2 ALARMS
HIGH RETURN AIRFLOW (10% ABOVE SUPPLY AIRFLOW)
LOW RETURN AIRFLOW (30% BELOW SUPPLY AIRFLOW)
9. PREHEAT COIL
9.1 THE CONTROLLER SHALL MEASURE THE PREHEAT SECTION AIR TEMPERATURE (TS-2)
AND MODULATE THE PREHEAT COIL VALVE TO MAINTAIN SETPOINT. THE PREHEAT
SECTION TEMPERATURE SETPOINT SHALL EQUAL THE SUPPLY AIR TEMPERATURE
SETPOINT MINUS THE FAN HEAT OFFSET VALUE.
9.2 PREHEAT COIL SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS LESS THAN 50 DEG(ADJ),
AND THE ECONOMIZER IS DISABLED
AND THE SUPPLY FAN STATUS IS ON
9.3 THE PREHEAT COIL SHALL OPEN FOR FREEZE PROTECTION WHENEVER:
MIXED AIR TEMPERATURE DROPS BELOW 36 DEG F (ADJ.)
OR THE FREEZESTAT IS ON.
10. SUPPLY AIR TEMPERATURE SETPOINT
10.1 THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE (TS-4) AND SHALL
MAINTAIN A SUPPLY AIR TEMPERATURE SETPOINT RESET BASED ON ZONE COOLING
AND HEATING REQUIREMENTS.
10.2 THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR COOLING BASED ON
ZONE COOLING REQUIREMENTS AS FOLLOWS:
THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55 DEG F(ADJ.)
AS COOLING DEMAND INCREASES (i.e. 75% OF THE BOXES ARE IN COOLING), THE SETPOINT
SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 53 DEG F (ADJ.)
AS COOLING DEMAND DECREASES (i.e. 75% OF THE BOXES ARE IN HEATING), THE SETPOINT
SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 58 DEG F (ADJ.).
11. COOLING COIL
11.1 THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE (TS-4) AND
MODULATE THE COOLING COIL VALVE TO MAINTAIN THE SUPPLY AIR TEMPERATURE
SETPOINT.
11.2 THE COOLING SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS GREATER THAN 50 DEGREES
AND THE SUPPLY FAN STATUS IS ON
AND THE HEATING IS NOT ACTIVE
11.4 THE COOLING COIL VALVE SHALL OPEN TO 50%(ADJ.) WHENEVER THE FREEZESTAT IS
ON.
11.5 ALARMS
HIGH SUPPLY AIR TEMPERATURE ALARM, THE CONTROLLER SHALL ALARM IF THE SUPPLY
AIR TEMPERATURE(TS-4) IS 5 DEG F(ADJ.) GREATER THAN THE SUPPLY AIR SETPOINT.
LOW SUPPLY AIR TEMPERATURE ALARM, THE CONTROLLER SHALL ALARM IF THE SUPPLY AIR
TEMPERATURE IS LESSTHAN 45 DEG F(ADJ.).
12. ECONOMIZER
12.1 THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE
THE OUTSIDE AIR AND EXHAUST AIR DAMPERS IN SEQUENCE TO MAINTAIN THE ECONOMIZER
TEMPERATURE SETPOINT (TS-4). THE OUTSIDE AIR DAMPER SHALL MAINTAIN A
MINIMUM ADJUSTABLE POSITION TO MAINTAIN MINIMUM OUTSIDE AIR REQUIRED.
12.2 THE ECONOMIZER SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS LESS THAN 60 DEG F(ADJ)
AND THE OA TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE
AND THE OA ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY
AND THE SUPPLY FAN STATUS IS ON
12.3 THE OUTSIDE AIR DAMPER SHALL CLOSE WHENEVER:
MIXED AIR TEMPERATURE DROPS BELOW 36 DEG F(ADJ.)
OR THE FREEZESTAT IS ON
OR THE SUPPLY FAN STATUS IS OFF
12.4 THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE MIXED AIR
DAMPER SHALL OPEN WHEN THE UNIT IS OFF.
13. HUMIDIFIER CONTROL
13.1 THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND MODULATE THE
HUMIDIFIER TO MAINTAIN A SETPOINT OF 35% RH(ADJ.). THE HUMIDIFIER SHALL BE
ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON AND THE OUTSIDE AIR
TEMPERATURE IS BELOW 65 DEGREES.
13.2 THE HUMIDIFIER SHALL TURN OFF WHENEVER:
SUPPLY AIR HUMIDITY MEASURERS 90%
OR WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 65 DEGREES
OR ON A LOSS OF SUPPLY FAN STATUS
13.3 ALARMS
HIGH SUPPLY AIR HUMIDITY 90%(ADJ)
LOW SUPPLY AIR HUMIDITY 30%(ADJ)
14. AIRFLOW CONTROL
14.1 THE CONTROL SYSTEM SHALL MONITOR AND DISPLAY SUPPLY AIR FLOW, RETURN AIR
FLOW, AND MIXED AIR FLOW IN CFM. IT WILL CALCULATE, AND DISPLAY OUTDOOR AIR
PERCENTAGE FROM THE MEASURED VALUES BASED ON THE FOLLOWING FORMULA:
14.2 THE OUTSIDE AIR DAMPER SHALL BE CONTROLLED AS FOLLOWS:
14.2.1 WHEN OUTSIDE AIR TEMPERATURE IS BELOW 50 DEGREES AND THE
ECONOMIZER CONTROL SEQUENCE HAS REDUCED THE OUTSIDE AIRFLOW
DOWN TO THE MINIMUM OUTSIDE AIR FLOW RATE, THE OUTSIDE AIR DAMPER
SHALL BE MODULATED TO MAINTAIN THE MINIMUM AIRFLOW SETPOINT.
14.2.2 WHEN THE AIR HANDLING UNIT CONTROLS ARE OPERATING IN ECONOMIZER
MODE, THE ECONOMIZER CONTROL SEQUENCE WILL MODULATE THE
OUTSIDE AIR DAMPER TO MAINTAIN THE MIXED AIR ECONOMIZER
TEMPERATURE SETPOINT. THE OUTSIDE AIR CALCULATION ABOVE IN 14.1
SHALL DISPLAY THE OUTSIDE AIR PERCENTAGE BUT WILL NOT BE USED TO
CONTROL THE OUTSIDE AIR DAMPER IN THE ECONOMIZER MODE.
14.2.3 WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 60 DEGREES AND THE
ECONOMIZER IS NOT ENABLED BASED ON THE OUTSIDE AIR TEMPERATURE OR
ENTHALPY PER 12.2 ABOVE, THE CONTROL SEQUENCE SHALL REDUCE THE
OUTSIDE AIRFLOW DOWN TO THE MINIMUM OUTSIDE AIR FLOW RATE. THE
OUTSIDE AIR DAMPER SHALL CLOSE TO A PRESET POSITION. THE PRESET
DAMPER POSITION SHALL BE DETERMINED BASED ON ADJUSTING THE
DAMPER POSITION AND MEASURING THE OUTSIDE AIRFLOW, WITH THE
SUPPLY AND RETURN FANS OPERATING AT 100% CAPACITY, UNTIL THE
MINIMUM OUTSIDE AIRFLOW IS MEASURED. THE OUTSIDE AIR CALCULATION
ABOVE IN 14.1 SHALL DISPLAY THE OUTSIDE AIR PERCENTAGE BUT WILL NOT
BE USED TO CONTROL THE OUTSIDE AIR DAMPER. WHEN THE OUTSIDE AIR
TEMPERATURE AND THE RETURN TEMPERATURE ARE EQUAL, ADJUST THE
RETURN AIR TEMPERATURE UPWARD BY 0.1 DEGREE F TO ENABLE THE
OUTSIDE AIR CALCULATION TO FUNCTION.
15. FILTERS
15.1 ALARMS
PREFILTER DIRTY -DIFFERENTIAL PRESSURE IS 1" GREATER THAN CLEAN FILTER
FINAL FILTER DIRTY -DIFFERENTIAL PRESSURE IS 1" GREATER THAN CLEAN FILTER
16. FAN HEAT OFFSET VALUE
16.1 FAN HEAT OFFSET (0-5)- THE BCS SHALL RESET THE FAN HEAT OFFSET VALUE BASED
UPON THE DIFFERENCE BETWEEN SUPPLY AIR SETPOINT AND SUPPLY AIR
TEMPERATURE. THE LOWER LIMIT SHALL BE 0. THE UPPER LIMIT SHALL BE 5.
16.2 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE OF 2°F BELOW
THE SUPPLY AIR SETPOINT, THE PDI LOOP SHALL SUBTRACT 1 FROM THE FAN HEAT
OFFSET VALUE. IF THE FAN HEAT OFFSET VALUE IS GREATER THAN 0, THEN THE FAN
HEAT OFFSET SHALL BE SET TO 0. AFTER AN ADJUSTABLE PERIOD OF 15 MINUTES THE
PID LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO THE SETPOINT AND ADJUST
THE VALUE.
16.3 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE + OR - 2°F OF
THE SUPPLY AIR SETPOINT, THE PDI LOOP SHALL ADD ZERO TO THE FAN HEAT OFFSET
VALUE. AFTER AN ADJUSTABLE PERIOD OF 15 MINUTES THE PID LOOP SHALL COMPARE
THE SUPPLY TEMPERATURE TO THE SETPOINT AND ADJUST THE VALUE.
16.4 WHEN SUPPLY AIR TEMPERATURE SENSOR INDICATES A TEMPERATURE OF 2°F ABOVE
THE SUPPLY AIR SETPOINT, THE PDI LOOP SHALL ADD 1 TO THE FAN HEAT OFFSET
VALUE. IF THE FAN HEAT OFFSET VALUE IS GREATER THAN 5, THEN THE FAN HEAT
OFFSET SHALL BE SET TO 5. AFTER AN ADJUSTABLE PERIOD OF 15 MINUTES THE PID
LOOP SHALL COMPARE THE SUPPLY TEMPERATURE TO THE SETPOINT AND ADJUST
THE VALUE.
17. CONTINUOUS COMMISSIONING ALARMS
17.1 IF IN COOLING MODE (OUTSIDE AIR IS GREATER THAN 50 DEGREES):
TS-2 IS GREATER THAN TS-1 BY 1 DEG F, OR MORE, THEN ALARM "STEAM VALVE OPEN IN
COOLING MODE"
17.2 IF IN HEATING MODE (OUTSIDE AIR IS LESS THAN 50 DEGREES):
TS-3 IS LESS THAN TS-2 BY 1 DEG F, OR MORE, THEN ALARM "CHILLED WATER VALVE IS OPEN
IN HEATING MODE"
SEQUENCE OF OPERATION FOR AIR HANDLING UNIT (N-1-1)
NOT TO SCALE
AHU-N-1-1 POINTS LIST
INPUT INPUT DEVICE OUTPUT OUTPUT DEVICE
NUMBER TYPE NUMBER TYPE
1 DIGITAL SF1 VFD HAND OFF AUTO 1 DIGITAL SF1 VSMC ENABLE/DISABLE
2 DIGITAL RF1 VFD HAND OFF AUTO
3 DIGITAL SF1 STATUS CS
3 DIGITAL RF1 VSMC ENABLE/DISABLE4 DIGITAL RF1 STATUS CS
5 DIGITAL PRE-FILTER STATUS DP
5 DIGITAL DISCHARGE SMOKE DAMPER
6 DIGITAL FINAL FILTER STATUS DP
6 DIGITAL RETURN SMOKE DAMPER
7 DIGITAL FREEZESTAT
DIGITAL HUMIDIFIER ENABLE
8 DIGITAL HIGH DISCHARGE DUCT STATIC DP
DIGITAL SPARE
DIGITAL DISCHARGE DUCT SMOKE DETECTOR STATUS10
DIGITAL RETURN DUCT SMOKE DETECTOR STATUS11
DIGITAL DISCHARGE SMOKE DAMPER STATUS12
DIGITAL RETURN SMOKE DAMPER STATUS13
DIGITAL SF1 VFD FAULT14
DIGITAL RF1 VFD FAULT15
INPUT DEVICE
OUTPUT OUTPUT DEVICE
INPUT
NUMBER TYPE
NUMBER TYPE
1 ANALOG
SPARE
1 ANALOG SF1 VSMC SPEED REFERENCE
2 ANALOG
SPARE
2 ANALOG
3 ANALOG
SPARE
3 ANALOG
RF1 VSMC SPEED REFERENCE
4 ANALOG
DISCHARGE AIR TEMPERATURE
4 ANALOG
OUTSIDE AIR DAMPER
5 ANALOG
RETURN AIR TEMPERATURE
5 ANALOG
MIXED AIR DAMPER
6 ANALOG
MIXED AIR TEMPERATURE
6 ANALOG
EXHAUST AIR DAMPER
7 ANALOG
7 ANALOG
SPARE
8 ANALOG
RETURN AIR HUMIDITY
8 ANALOG
CHILLED WATER VALVE
9 ANALOG
DISCHARGE DUCT STATIC PRESSURE
PRE-HEAT VALVE
10 ANALOG
SUPPLY AIR FLOW MEASURING STATION
11 ANALOG
RETURN AIR FLOW MEASURING STATION
ANALOG
12 ANALOG
OUTDOOR AIR TEMPERATURE
ANALOG
SPARE
13 ANALOG
LEAVING PRE-HEAT COIL AIR TEMPERATURE
14 ANALOG
LEAVING COOLING COIL AIR TEMPERATURE
15 ANALOG
OUTSIDE AIRFLOW STATION
16 ANALOG
SUPPLY AIR HUMIDITY
SPARE
SPARE
DIGITAL LOW RETURN DUCT STATIC DP
DIGITAL SPARE
DIGITAL SPARE
ANALOG HUMIDIFIER
ANALOG SPARE
DIGITAL SPARE16
DIGITAL SPARE17
DIGITAL SPARE18
DIGITAL SPARE19
DIGITAL SPARE20
DIGITAL SPARE21
DIGITAL SPARE22
IN DIAGRAMS, 'I' INDICATES AN INPUT, 'O' INDICATES AN OUTPUT.
DAMPER OPERATORS TO BE PROVIDED BY TEMPERATURE CONTROLS CONTRACTOR.
TEMPERATURE CONTROL TEST SHALL INCLUDE, BUT NOT BE LIMITED TO:
· DAMPER OPERATION
· VALVE ACTUATION RESPONSE AND VALIDATION OF CORRECT OPERATION
· VERIFIED ENTIRE CONTROL SEQUENCE OPERATES PER DESIGN
· ACCOUNT FOR ALL CONTROL POINTS LISTED
ALL SYSTEMS SHALL BE COMMISSIONED. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
TEMPERATURE CONTROLS SHALL BE TRIDIUM. ALL CONTROLS WORK SHALL INTERFACE WITH EXISTING
TRIDIUM BUILDING CONTROL SYSTEM.
ALL REQUIRED POINTS MAY NOT BE LISTED ON POINTS LIST/DIAGRAM. ADDITIONAL POINTS MAY BE REQUIRED BASED ON FINAL EQUIPMENT SELECTION. CONTRACTOR SHALL PROVIDE ANY ADDITIONAL
CONTROLS POINTS REQUIRED.
REFERENCE SPECIFICATION SECTIONS 230923 AND 230940 FOR ADDITIONAL INFORMATION.
A.
B.
C.
D.
E.
F.
G.
TEMPERATURE CONTROLS GENERAL NOTES:
18. COLD START SEQUENCE
18.1 WHENEVER UNIT IS STARTED AND OUTDOOR AIR TEMPERATURE IS BELOW 30 DEG F INITIATE
THE FOLLOWING SEQUENCE.
18.2.1 OA DAMPER SHALL BE CLOSED. EXHAUST AIR DAMPER SHALL BE CLOSED, MIXED AIR DAMPER
SHALL BE 100% OPEN (ECONOMIZER DISABLED).
18.2.2 COMMAND ON STEAM PREHEAT VALVE.
18.2.3 STEAM PREHEAT VALVE SHALL MAINTAIN 80- DEGREE SUPPLY AIR TEMPERATURE.
18.2.4 SMOKE DAMPER SHALL BE OPEN.
18.2.5 COMMAND ON SUPPLY AND RETURN (DRIVE) ALLOW TO RAMP UP NORMALLY.
18.2.6 SET MIXED AIR SETPOINT TO 70 DEG F ONCE SUPPLY/RETURN FAN-ON STATUS HAS BEEN
PROVEN.
18.2.7 FIVE MINUTES AFTER SUPPLY/RETURN FAN-ON STATUS HAS BEEN PROVEN, OA DAMPER SHALL DELIVER 5% OF CFM RA AND EX DAMPERS SHOULD OPEN/CLOSE SIMULTANEOUSLY WITH OA DAMPER.
(OA=5% RA=95% EX=5%).
18.2.8 FIVE MINUTES AFTER OA DAMPER STARTED DELIVERING 5%, RELEASE OA, RA RELIEF AIR
DAMPERS TO CONTROL TO MEET MIXED AIR SETPOINT.
18.2.9 LOWER MIXED AIR SETPOINT TO 60 DEGREES F FOR 10 MINUTES.
18.2.10 RELEASE MIXED AIR SETPOINT BACK TO ORIGINAL SETTING.
Revisions: Date:
Addendum #1 09 SEP 2020
| 19026 FFH CF R18_ccampbell |
| M-701 - TEMPERATURE CONTROLS |