Revised Drawing E-301 One-Line Legend and Panelboard Schedules.pdf
PDF 415 KB Posted
- Attached to
- Y1DZ--Expand MRI Suite Project 541-CSI-103
- Solicitation number
- 36C25020B0043
About this file
This document provides details for a federal construction contract opportunity to expand an MRI suite at the Louis Stokes VA Medical Center in Cleveland, Ohio. The project scope includes adding a third 3T MRI unit north of the existing suite, renovating connecting areas, and reworking the surrounding site, landscaping, sidewalks and physical barriers. Interested Service-Disabled Veteran-Owned Small Businesses must closely coordinate all work with the VA Contracting Officer and Representative. The estimated period of performance is 548 calendar days from notice to proceed. A pre-solicitation notice and site visit are scheduled for early June 2020, with proposals due approximately 30 days later. The North American Industry Classification System code assigned is 236220 and the small business size standard is $39.5 million. The awardee must perform a minimum of 15% of construction work. Bid, payment and performance bonds are required. All work shall be conducted according to drawings, specifications and statements of work to be published in the solicitation.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Louis Stokes
Cleveland
VA Medical
Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consulting Engineers
BARBER & HOFFMAN, INC.
2217 East 9th Street, Suite 350 Cleveland, OH 44115-1257 216-875-0100/ (F) 216-875-0111 barberhoffman.com
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY PROHIBITED WITHOUT THE
EXPRESSED WRITTEN CONSENT OF PERSPECTUS
ARCHITECTURE.
COPYRIGHT C 2019.
13212 Shaker Square Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
Expand MRI Suite 541-CSI-103
CLEVELAND, OHIO
19026
Z M y D o c u m e n ts
\1
F F
H C
F R c c a m p b e ll.
rv t
/1
/2
:0
:0
P
M
E-301
ONE-LINE LEGEND AND PANELBOARD
SCHEDULES
11/15/2019 MPL CPC
Total New Demand Amps: 13 A
Total New Amps: 15 A 9 A 19 A
Total New Load: 1.7 kVA 1 kVA 2.2 kVA
H-41 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-42
H-39 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-40
H-37 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-38
H-35 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-36
H-33 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-34
H-31 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-32
H-29 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-30
H-27 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-28
H-25 PROVISION -- -- 0.0 0.0 -- -- PROVISION H-26
H-23 VAV MRI 1B550 20 A 1 0.0 1.0 1 20 A MRI DOOR COMP. H-24
H-21 VAV MRI BB622 20 A 1 0.0 0.5 1 20 A TEMP CTRL PNL H-22
H-19 AHU DAMPERS 20 A 1 0.5 0.7 1 20 A REC MRI 1B556 H-20
H-17 AHU LTG 20 A 1 0.5 0.7 1 20 A REC CTRL 1B554 H-18
H-15 EX. WTR TRSDR 20 A 1 0.0 0.5 1 15 A EF-1 H-16
H-13 EX. REC 1B-218 20 A 1 0.0 0.5 1 15 A EF-2 H-14
H-11 EX. 1B-109 PIXIS 20 A 1 0.0 0.0 1 20 A EX REC RAD ELEC H-12
H-9 EX. MRI AUTODR 20 A 1 0.0 0.0 1 20 A EX REC RAD ELEC H-10
H-7 EX TEMP CTRL PNL 20 A 1 0.0 0.0 H-8
H-5 EX. EF-6 20 A 1 0.0 0.0
2 25 A EX. CU-4
H-6
H-3 EX. EF-5 20 A 1 0.0 0.0 H-4
H-1 EX. EF-4 20 A 1 0.0 0.0
2 25 A EX. CU-3
H-2
CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
Comments: EXISTING A.I.C Rating: 10 KAIC
Mounting: Surface Main: MLO
Location: EXISTING PENTHOUSE... OCP: 100 A
RAD2PGL1-120/208 Wye-3Φ-4W ESS. EQUIPMENT
Total New Demand Amps: 109 A
Total New Amps: 93 A 130 A 113 A
Total New Load: 11.2 kVA 15.3 kVA 13.3 kVA
E-41 EX MICRO 20 A 1 1.2 0.4 1 20 A EX TOILET CTRLS E-42
E-39 EX WATER COOL 20 A 1 1.2 0.9 1 20 A EX REC WAITING E-40
E-37 EX. REF 20 A 1 1.2 1.1 1 20 A EX REC OFFICE E-38
E-35 EX REC RECEPT 20 A 1 0.8 1.1 1 20 A EX REC CONSULT E-36
E-33 EX. REC OFFICE 20 A 1 1.0 1.3 1 20 A EX REC OFFICE E-34
E-31 2.3 0.6 1 20 A EX REC TV WAIT E-32
E-29 3.7 0.5 1 20 A EX REC STAFF LNG E-30
E-27
NEW PANEL
RAD1LNL3
60 A 3
4.3 0.7 1 20 A EX REC VEST WAIT E-28
E-25 EX PHIL EPO 20 A 1 1.1 0.5 1 20 A EX REC UTIL & TR E-26
E-23 EX PHIL EQUIP RM 20 A 1 0.9 0.2 1 20 A EX AUTODOOR E-24
E-21 EX PHIL SCAN 20 A 1 1.1 0.7 1 20 A EX REC CORR E-22
E-19 EX PHIL CTRL RM 20 A 1 0.9 0.2 1 20 A EX REC OFFICE E-20
E-17 EX PHIL CTRL RM 20 A 1 0.5 0.7 1 20 A EX REC OFFICE E-18
E-15 EX TOSH EPO 20 A 1 1.1 0.7 1 20 A EX REC ANTE E-16
E-13 EX TOSH EQIP RM 20 A 1 0.5 0.7 1 20 A EX REC WAIT E-14
E-11 EX TOSH CTRL 20 A 1 0.5 0.5 1 20 A EX REC LV RM E-12
E-9 EX TOSH CTRL 20 A 1 0.5 0.8 1 20 A EX VAV E-10
E-7 EX BSMT UH 20 A 1 0.1 0.5 1 20 A EX PHIL COMP&DR E-8
E-5 EX REC BSMT 20 A 1 0.9 1.2 1 20 A EX PHIL MRI COMP E-6
E-3 EX REC SUB BSMT 20 A 1 0.5 0.5 1 20 A EX TOSH MRI LTG E-4
E-1 EX NXTL REPEAT 20 A 1 0.3 1.2 1 20 A EX TOSH MRI LTG E-2
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: EXISTING A.I.C Rating: 22 KAIC
Mounting: Surface Main: MLO
Location: Elec.-1 1B526-1 OCP: 225 A
RAD1LNL1-120/208 Wye-3Φ-4W NORMAL
Total New Demand Amps: 27 A
Total New Amps: 37 A 33 A 19 A
Total New Load: 4.3 kVA 3.7 kVA 2.3 kVA
F-41 SPARE 20 A 1 0.0 0.0 1 20 A SPARE F-42
F-39 SPARE 20 A 1 0.0 0.0 1 20 A SPARE F-40
F-37 SPARE 20 A 1 0.0 0.0 1 20 A SPARE F-38
F-35 SPARE 20 A 1 0.0 0.0 1 20 A SPARE F-36
F-33 SPARE 20 A 1 0.0 0.0 1 20 A SPARE F-34
F-31 SPARE 20 A 1 0.0 0.5 1 20 A REC CORR 1B541 F-32
F-29 SPARE 20 A 1 0.0 0.1 1 20 A MRI MRU 1B555 F-30
F-27 SPARE 20 A 1 0.0 1.0 1 20 A AUTODOOR 1B555 F-28
F-25 SPARE 20 A 1 0.0 1.0 1 20 A AUTODOOR 1B550 F-26
F-23 SPARE 20 A 1 0.0 0.2 1 20 A REC CTRL 1B554 F-24
F-21 SPARE 20 A 1 0.0 0.2 1 20 A REC CTRL 1B554 F-22
F-19 SPARE 20 A 1 0.0 0.2 1 20 A REC CTRL 1B554 F-20
F-17 SPARE 20 A 1 0.0 0.7 1 20 A REC 1B553 F-18
F-15 SPARE 20 A 1 0.0 0.7 1 20 A REC CTRL 1B554 F-16
F-13 SPARE 20 A 1 0.0 1.1 1 20 A REC CTRL 1B554 F-14
F-11 SPARE 20 A 1 0.0 0.4 1 20 A REC MRI 1B556 F-12
F-9 SPARE 20 A 1 0.0 0.5 1 20 A SCR 1B556 F-10
F-7 CUH-1 20 A 1 0.0 0.2 1 20 A REC 1B556, 1B552 F-8
F-5 REC CORR BB621 20 A 1 0.7 0.2 1 20 A REC MRI EQUIP RM F-6
F-3 REC STOR BB622 20 A 1 1.1 0.2 1 20 A REC MRI INJECTOR F-4
F-1 REC STOR BB622 20 A 1 1.1 0.2 1 20 A REC MRI RM 1B555 F-2
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: NEW A.I.C Rating:
Mounting: Surface Main: MLO
Location: MRI EQUIPMENT 1B556 OCP: 60 A
RAD1LNL3-120/208 Wye-3Φ-4W NORMAL
# PANELBOARD CODED NOTES
Total New Demand Amps: 1 A
Total New Amps: 0 A 1 A 1 A
Total New Load: 0 kVA 0.2 kVA 0.2 kVA
B-31 PROVISION -- -- 0.0 0.0 -- -- PROVISION B-32
B-29 0.0 0.0 1 20 A SPARE B-30
B-27 0.0 0.0 1 20 A SPARE B-28
B-25
EX. CONDENSATE
PUMP 2
20 A 3
0.0 0.0 1 20 A SPARE B-26
B-23 0.0 0.0 1 20 A SPARE B-24
B-21 0.0 0.0 1 20 A SPARE B-22
B-19
EX. CONDENSATE
PUMP 1
20 A 3
0.0 0.0 1 20 A SPARE B-20
B-17 0.0 0.0 -- -- PROVISION B-18
B-15 0.0 0.0 -- -- PROVISION B-16
B-13
SPARE 20 A 3
0.0 0.0 1 20 A SPARE B-14
B-11 0.0 0.2 1 20 A MRI LTG 1B555 B-12
B-9 0.0 0.2 1 20 A LTG 1ST FL MRI B-10
B-7
EX. SUMP PUMP 20 A 3
0.0 0.0 1 20 A EX. LTG E OFFICES B-8
B-5 0.0 0.0 1 20 A EX. LTG MRI SUPP B-6
B-3 0.0 0.0 1 20 A EX. LTG CORR B-4
B-1
EX. SUMP PUMP 20 A 3
0.0 0.0 1 20 A SPARE B-2
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: EXISTING A.I.C Rating: 35 KAIC
Mounting: Surface Main: MCB
Location: Elec.-1 1B526-1 OCP: 225 A
RAD1LNH1-480/277 Wye-3Φ-4W NORMAL
SEE ONE-LINE DIAGRAM
SEE ONE-LINE DIAGRAM
1 RELOCATE EXISTING LOAD AT CIRCUIT #31 TO SPARE 20A-1P CIRCUIT BREAKER AT CIRCUIT #39 TO ACCOMMODATE NEW 60A-3P CIRCUIT BREAKER TO FEED NEW PANEL 'RAD1LNL3' AT CIRCUITS 27-31.
PROVIDE NEW 60A-3P CIRCUIT BREAKER IN EXISTING SPACE MATCH EXISTING BREAKER TYPE AND KAIC
RATING.
UPS LOAD IS BASED ON 100% OF MOMENTARY RATING OF NEW MRI EQUIPMENT PLUS 50% OF MOMENTARY RATING OF EXISTING MRI EQUIPMENT + BATTERY CHARGING CURRENT. TEMPORARY MRI CONNECTION LOAD IS NOT INCLUDED ON THIS PANEL AS IT HAS BEEN INCLUDED IN THE UPS LOAD CALCULATION FOR
FINAL CONNECTIONS.
Total New Demand Amps: 150 A
Total New Amps: 150 A 150 A 150 A
Total New Load: 41.6 kVA 41.6 kVA 41.6 kVA
J-23 28.0 0.0 1 20 A SPARE J-24
J-21 28.0 0.0 1 20 A SPARE J-22
J-19
MRI CHILLER 125 A 3
28.0 0.0 1 20 A SPARE J-20
J-17 0.9 0.0 1 20 A SPARE J-18
J-15 0.9 0.0 1 20 A SPARE J-16
J-13
AHU RETURN FAN 15 A 3
0.9 0.0 1 20 A SPARE J-14
J-11 2.5 3.0 J-12
J-9 2.5 3.0 J-10
J-7
AC-2 15 A 3
2.5 3.0
3 20 A AHU SUPPLY FAN
J-8
J-5 4.6 2.5 J-6
J-3 4.6 2.5 J-4
J-1
AC-1 25 A 3
4.6 2.5
3 15 A AC-3
J-2
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: NEW A.I.C Rating:
Mounting: Surface Main: MLO
Location: PENTHOUSE 2B500 OCP: 225 A
RAD2PGH2-480/277 Wye-3Φ-4W ESS. EQUIPMENT
SEE ONE-LINE DIAGRAM
Total New Demand Amps: 1 A
Total New Amps: 0 A 2 A 0 A
Total New Load: 0 kVA 0.2 kVA 0 kVA
K-41 PROVISION -- -- 0.0 0.0 -- -- PROVISION K-42
K-39 PROVISION -- -- 0.0 0.0 -- -- PROVISION K-40
K-37 PROVISION -- -- 0.0 0.0 -- -- PROVISION K-38
K-35 PROVISION -- -- 0.0 0.0 -- -- PROVISION K-36
K-33 PROVISION -- -- 0.0 0.0 -- -- PROVISION K-34
K-31 PROVISION -- -- 0.0 0.0 -- -- PROVISION K-32
K-29 SPARE 20 A 1 0.0 0.0 1 20 A SPARE K-30
K-27 SPARE 20 A 1 0.0 0.0 1 20 A SPARE K-28
K-25 SPARE 20 A 1 0.0 0.0 1 20 A SPARE K-26
K-23 SPARE 20 A 1 0.0 0.0 1 20 A SPARE K-24
K-21 SPARE 20 A 1 0.0 0.0 1 20 A SPARE K-22
K-19 SPARE 20 A 1 0.0 0.0 1 20 A SPARE K-20
K-17 EX. MED GAS 20 A 1 0.0 0.0 1 20 A SPARE K-18
K-15 SPARE 20 A 1 0.0 0.2 1 20 A MRI MAGNET MON. K-16
K-13 EX. MED GAS 20 A 1 0.0 0.0 1 20 A EXISTING LOAD K-14
K-11 SPARE 20 A 1 0.0 0.0 1 20 A SPARE K-12
K-9 EX. AUTODOOR 20 A 1 0.0 0.0 1 20 A SPARE K-10
K-7 EX. AUTODOOR 20 A 1 0.0 0.0 1 20 A EX. AUTODOOR K-8
K-5 EX. AUTODOOR 20 A 1 0.0 0.0 1 20 A SPARE K-6
K-3 EX. AUTODOOR 20 A 1 0.0 0.0 1 20 A EXISTING LOAD K-4
K-1 SPARE 20 A 1 0.0 0.0 1 20 A EX. FA PANEL K-2
CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
Comments: EXISTING A.I.C Rating: 10 KAIC
Mounting: Surface Main: MLO
Location: Space BC479 OCP: 100 A
LEB1LS-120/208 Wye-3Φ-4W LIFE SAFETY
Revisions: Date:
Addendum #1 09 SEP 2020
Total New Demand Amps: 583 A
Total New Amps: 583 A 583 A 583 A
Total New Load: 161.5 kVA 161.5 kVA 161.5 kVA
23 PROVISION -- -- 0.0 0.0 -- -- PROVISION 24
21 PROVISION -- -- 0.0 0.0 -- -- PROVISION 22
19 PROVISION -- -- 0.0 0.0 -- -- PROVISION 20
17 PROVISION -- -- 0.0 0.0 -- -- PROVISION 18
15 PROVISION -- -- 0.0 0.0 -- -- PROVISION 16
13 PROVISION -- -- 0.0 0.0 -- -- PROVISION 14
11 PROVISION -- -- 0.0 0.0 -- -- PROVISION 12
9 PROVISION -- -- 0.0 0.0 -- -- PROVISION 10
7 PROVISION -- -- 0.0 0.0 -- -- PROVISION 8
5 161.5 0.0 6
3 161.5 0.0 4
MBP-RADUPS 800 A 3
16... 0.0
3 200 A
TEMPORARY FEED
TO TOSHIBA MRI
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: NEW A.I.C Rating:
Mounting: Surface Main: MLO
Location: OCP: 800 A
RAD2DPNH2-480/277 Wye-3Φ-4W NORMAL
SEE ONE-LINE DIAGRAM
RAD. SUB PENTHOUSE
2 2
EXISTING EQUIPMENT FEEDER/CIRCUIT - TO BE DEMOLISHED
NEW FEEDER/CIRCUIT AND FEEDER TAG
EXISTING EQUIPMENT FEEDER/CIRCUIT - TO REMAIN
BOLTED STATIONARY FUSED SWITCH - 3-POLE UNLESS OTHERWISE NOTED
AS - SWITCH RATING
AF - FUSE RATING
GROUNDING TERMINATION POINT FOR AN EQUIPMENT GROUNDING CONDUCTOR.
CONNECTION SHALL BE MADE BY BONDING THE EQUIPMENT GROUNDING CONDUCTOR TO
THE GROUNDED SERVICE CONDUCTOR AND THE GROUNDING ELECTRODE CONDUCTOR.
NEW EQUIPMENT OUTLINE
NAME
EXISTING EQUIPMENT OUTLINE
NAME
PANELBOARD
TRANSFORMER
VOLTAGE
MAIN
AMPS
NAME
AUTOMATIC TRANSFER SWITCH - TYPE AS EXISTING (IE, BYPASS ISOLATION IS NOT SHOWN)
3/4"C - 3 #10 & 1 #10 EG
2500AS
2500AF
225A
BOLTED STATIONARY CIRCUIT BREAKER - 3-POLE UNLESS OTHERWISE NOTED
GFI - EQUIP BREAKER W/ GROUND FAULT TRIP
FA - EQUIP BREAKER W/ GROUND FAULT ALARM
LSI - EQUIP BREAKER W/ ADJUSTABLE LONG, SHORT AND INSTANT. SETTINGS
LSIG - EQUIP BREAKER W/ ADJUSTABLE LONG, SHORT AND INSTANT. SETTINGS AND
GROUND FAULT TRIP.
KIRK-KEY INTERLOCKING
BATT.
UNINTERRUPTABLE POWER SUPPLY (UPS)
BASIS-OF-DESIGN (OR EQUAL) - CPN POWER, INC. (TEL: 800-491-1210).
UPS SUPPLIER SHALL BE EXPERIENCED IN PROVIDING UPS EQUIPMENT FOR RADIOLOGY
EQUIPMENT INCLUDING AT LEAST (5) EXAMPLES OF UPS EQUIPMENT SUPPLING 3+ MODALITIES
IN THE LAST (2) YEARS. PROVIDE DOCUMENTATION OF REQUIRED EXPERIENCE WITH
EQUIPMENT SHOP DRAWING SUBMITTAL. EQUIPMENT WILL NOT BE APPROVED WITHOUT
REQUIRED DOCUMENTATION. SPECIFICATIONS BELOW ARE FOR REFERENCE. VENDOR SHALL
CONFIRM EQUIPMENT PROVIDED IS CAPABLE OF SUPPORTING THE FOLLOWING MODALITIES:
• (1) EXISTING PHILIPS ACHIEVA 3T MRI
• (1) EXISTING CANON 1.5T TITAN MRI
• (1) NEW GE SIGNA PREMIER 3T MRI
• WITH ADDITIONAL CAPACITY TO REPLACE EXISTING PHILIPS OR CANON MRI EQUIPMENT
WITH A 2ND GE SIGNA PREMIER MRI.
SPECIFICATIONS:
• 750KVA, 480:480V-3Ø-3W, ON-LINE DOUBLE CONVERSION
• +/- 1% VOLTAGE REGULATION DURING PEAK CURRENT CONDITIONS WITHIN 100% RATING
• +/- 2% VOLTAGE REGULATION WITHIN 150% OVERLOAD CAPABILITY
• 96.3% FULL LOAD EFFICIENCY
• 95.5% EFFICIENCY AT 25% LOAD.
• SINE WAVE SAMPLING RATE 1000x PER CYCLES (MIN)
• BATTERY CAPACITY: APPROX. 200kWh, •• ~40 MIN AT ~180kVa •• ~15 MIN AT ~375kVa •• ~7 MIN AT ~550kVa
•• ~5 MIN AT ~670KW
UPS MUST:
• SUPPORT MEDICAL IMAGING EQUIPMENT, INCLUDING MULTIPLE MODALITIES, FROM A
SINGLE SYSTEM.
• BE CAPABLE OF +/- 1% VOLTAGE REGULATION DURING EVENTS WHERE BASE LOAD
EXISTING ALONG WITH PEAK CURRENTS FROM ADDITIONAL MODALITIES.
• OPERATE WITHOUT REQUIRING DC CURRENT DURING PEAK CURRENT EVENTS FROM
MULTIPLE MODALITIES OR NORMAL PEAK CONDITIONS TO PREVENT OVER-CYCLING.
• OPERATE WITHOUT TRANSFERRING TO STATIC BYPASS PEAK CURRENT EVENTS FROM
MULTIPLE MODALITIES OR NORMAL PEAK CONDITIONS.
VENDOR MUST PROVIDE ON-SITE SYSTEM COMMISSIONING. REFER TO ONE-LINE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
SPLICE JOINT FOR RECONNECTION OF EXISTING CIRCUITS TO NEW SOURCE.
PROVIDE NEW SPLICE BOX (MINIMUM 4-11/16"SQ X 2-1/8"D, SIZE PER NEC 314.16).
REFER TO JOINTS AND SPLICES SPECIFICATIONS FOR ADDITIONAL INFORMATION.
NE
1. FOR #10 AWG CONDUCTORS AND SMALLER, JOINTS AND SPLICES SHALL BE MADE WITH SCREW-ON WIRE CONNECTORS. CONNECTOR
JOINTS SHALL BE INSULATED WITH TAPE.
2. FOR #8 AWG AND LARGER WIRES SHALL BE MADE WITH COMPRESSION TYPE MECHANICAL CONNECTORS AND INSULATED WITH HEAT
SHRINK TUBING TO A 600V INSULATION LEVEL.
3. LABEL BOX COVER WITH SOURCE, CIRCUIT, AND LOAD INFORMATION. LABEL SHALL BE MADE WITH PERMANENT MARKER. STICK ON
LABELS ARE NOT ACCEPTABLE.
4. VERIFY PHASE ROTATION OF ALL LOADS PRIOR TO STARTING. CREATE REPORT OF PHASE ROTATION FOR EACH LOAD WITH 1) EXISTING
PHASE ROTATION, 2) RECONNECTED PHASE ROTATION, 3) TIME AND DATE OF PHASE ROTATION TEST, 4) IDENTIFICATION INFORMATION
OF TECHNICIAN VERIFYING PHASE ROTATION.
JOINTS AND SPLICES SPECIFICATION:
K
| 19026 FFH CF R18_ccampbell |
| E-301 - ONE-LINE LEGEND AND PANELBOARD SCHEDULES |