36C25020B0015-019.pdf

PDF Posted

Attached to
Y1DZ--Renovate Waiting Rooms 583-15-108
Solicitation number
36C25020B0015
Issued by

About this file

This notice announces a solicitation for a construction project to renovate waiting rooms at a Veterans Affairs medical center. The project is identified as number 583-15-108 with a project magnitude between $500,000 and $1,000,000. It is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses and the NAICS code is 236210 with a business size standard of $36.5 million. Offerors must be registered and verified in VIP and SAM databases. The solicitation will be posted on February 14, 2018 on FBO with proposals due approximately 30 days later. The duration of the project shall not exceed 365 calendar days from receipt of the notice to proceed. Bonds in the form of offer, payment and performance will be required. A one-time site visit will be scheduled. Questions will only be accepted through requests for information after documents are posted. Interested parties should monitor FBO for amendments and not contact the contracting officer.

36C25020B0015 Set 17.pdf

View the file

Other files

File Type Posted
36C25020B0015-0004002.docx DOCX document
36C25020B0015-0004003.pdf PDF
36C25020B0015-0003001.docx DOCX document
36C25020B0015-0002000.docx DOCX document
36C25020B0015-0001001.pdf PDF
36C25020B0015-0001000.docx DOCX document
36C25020B0015-005.pdf PDF
36C25020B0015-003.pdf PDF
36C25020B0015-017.pdf PDF
36C25020B0015-010.pdf PDF
36C25020B0015-008.pdf PDF
36C25020B0015-013.pdf PDF
36C25020B0015-023.docx DOCX document
36C25020B0015-018.pdf PDF
36C25020B0015-021.pdf PDF
36C25020B0015-014.pdf PDF
36C25020B0015-007.pdf PDF
36C25020B0015-002.docx DOCX document
36C25020B0015-016.pdf PDF
36C25020B0015-011.pdf PDF
36C25020B0015-009.pdf PDF
36C25020B0015-022.docx DOCX document
36C25020B0015-015.pdf PDF
36C25020B0015-012.pdf PDF
36C25020B0015-006.pdf PDF
36C25020B0015-020.pdf PDF
36C25020B0015-004.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N D

N D

WIFI

$MO

S

$MO

EX

30 MINUTE SMOKE BARRIER 30 MINUTE SMOKE BARRIER 30 MINUTE SMOKE BARRIER

WAITING ROOM

B-B001

MEN TOILET

B-B030

EXAM 1

B-B002

EXAM 2

B-B003

EXAM 3

B-B004

CORRIDOR

CB-11

RADIATION ONCOLOGY

RECEPTION OFFICE

B-B029

HANDICAP TOILET

B-B028

SOILED UTILITY

B-B027

DRESS. RM.

B-B005A

CHASE

CORRIDOR

CB-55

DOCTOR OFFICE

B-B026CORRIDOR

CB-2

CORRIDOR

CB-3

WOMEN TOILET

B-B031

NURSES

B-B005

T

D

D on e ei gh th in ch o ne f oo t

B

A

C

D th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e

W ai tin g

R oo m s\

-P re -B id \F

O R C E

Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5 -1

-1

.M

D .d w g

-0

-1

:2

:2

P

M

V H A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

1. ALL CONTRACTORS SHALL CLEAN SITE THOROUGHLY AT THE END OF EACH WORK DAY.

2. ALL CONTRACTORS TO VERIFY STAGING AND STORAGE LOCATIONS OF ALL MATERIALS

AND EQUIPMENT WITH CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO

BEGINNING OF CONSTRUCTION.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING

THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES, CONTRACTOR IS TO

CONTACT THE COR IMMEDIATELY.

EXISTING DIFFUSER / GRILLE TO BE REMOVED, CLEANED, AND PREPARE FOR

REINSTALLATION IN NEW CEILING.

SCALE: 1/4 = 1'-0"

MECHANICAL DEMOLITION-BASEMENT FLOOR PLAN UNIT "A"1

MD100

NOT TO SCALE

EXISTING BASEMENT KEY PLAN

N

RICHARD L. ROUDEBUSH

VA MEDICAL CENTER

UNIT A

UNIT B

UNIT

"A"

NOTE:

PATCH AND SEAL ALL UNUSED OPENINGS IN FLOOR TO

MAINTAIN FIRE RATING OF FLOOR.

AutoCAD SHX Text

MD100

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text N

AutoCAD SHX Text

UNIT-"A"

AutoCAD SHX Text

BASEMENT-FLOOR-PLAN-

AutoCAD SHX Text

MECHANICAL-DEMOLITION-

AutoCAD SHX Text

DDK

AutoCAD SHX Text

TEH

AutoCAD SHX Text

GENERAL MECHANICAL DEMO NOTES

AutoCAD SHX Text

MECHANICAL DEMOLITION NOTES

T

CORRIDOR

C2-27

CORRIDOR

C2-28

RECOVERY ROOM

C-2041

PROG. ASSISTANT

RADIOLOGY C-2043

RADIOLOGY READING

ROOM C-2038

RADIOLOGY WAITING ROOM

C-2040

RECEPTION

C-2039

CORRIDOR

C2-25

CONTROL

C-2057

9" Ø

"x

"x

"x

28"x10"

10" Ø

"x

"x

10" Ø

RG

10"x8"

"x

8" Ø

24"x10"

"x

8" Ø

TU-32-56

TU

-3

-4

7 EG

TU-32-47

TU-32-56

D

D

D

D

D

16"x8" on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e

W ai tin g

R oo m s\

-P re -B id \F

O R C E

Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5 -1

-1

.M

D A .d w g

-0

-1

:2

:3

P

M

V H A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

1. ALL CONTRACTORS SHALL CLEAN SITE THOROUGHLY AT THE END OF EACH WORK DAY.

2. ALL CONTRACTORS TO VERIFY STAGING AND STORAGE LOCATIONS OF ALL MATERIALS

AND EQUIPMENT WITH CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO

BEGINNING OF CONSTRUCTION.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING

THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES, CONTRACTOR IS TO

CONTACT THE COR IMMEDIATELY.

REMOVE DIFFUSER.

REMOVE GRILLE. PREPARE DUCT FOR INSTALLATION OF NEW DIFFUSER.

REMOVE DUCTWORK TO POINT INDICATED AND PREPARE FOR RECONNECTION.

REMOVE TEMPERATURE SENSOR AND ASSOCIATED WIRING. PREPARE FOR

RELOCATION. PATCH AND REPAIR WALL TO SHOW NO EVIDENCE OF CONSTRUCTION.

REMOVE DUCTWORK TO POINT INDICATED. PATCH OPENING IN MAIN DUCT AND SEAL

AIRTIGHT.

SCALE: 1/4" = 1'-0"

MECHANICAL DEMOLITION-SECOND FLOOR PLAN UNIT "A"1

MD102A

NOT TO SCALE

EXISTING SECOND FLOOR KEY PLAN

NRICHARD L. ROUDEBUSH

VA MEDICAL CENTER

UNIT

"D"

UNIT

"C"

UNIT

"A"UNIT

"B"

NOTE:

PATCH AND SEAL ALL UNUSED OPENINGS IN FLOOR TO

MAINTAIN FIRE RATING OF FLOOR.

AutoCAD SHX Text

TEH

AutoCAD SHX Text

DDK

AutoCAD SHX Text

MD102A

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text

GENERAL MECHANICAL DEMO NOTES

AutoCAD SHX Text

MECHANICAL DEMOLITION NOTES

AutoCAD SHX Text N

AutoCAD SHX Text

UNIT-"A"

AutoCAD SHX Text

SECOND-FLOOR-PLAN

MECHANICAL-DEMOLITION

KIOSK

T

M.H. WAITING AREA

D-5030

M.H. PRRC CHECK-IN

D-5029

M.H. SOC. WORKER

D-5028

CORRIDOR

C5-16

M.H. ADMIN OFFICE

D-5031

D-5032

8"Ø

8"Ø

"x1

2" 14 " O

VA

L

RG

8"Ø

RG

8"Ø

TU-13-163

TU-13-162

D (225)

D (180)

D (180)

TU-13-162

TU-13-163

on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e W ai tin g R oo m s\

-P re -B id \F

O R C

E Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5

-1

-1

.M D

.d w g

-0

-1

:2

:4

P

M

V H A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

1. ALL CONTRACTORS SHALL CLEAN SITE THOROUGHLY AT THE END OF EACH WORK DAY.

2. ALL CONTRACTORS TO VERIFY STAGING AND STORAGE LOCATIONS OF ALL MATERIALS

AND EQUIPMENT WITH CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO

BEGINNING OF CONSTRUCTION.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING

THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES, CONTRACTOR IS TO

CONTACT THE COR IMMEDIATELY.

REMOVE TEMPERATURE SENSOR AND ASSOCIATED WIRING. PREPARE FOR

RELOCATION. PATCH AND REPAIR WALL TO SHOW NO EVIDENCE OF CONSTRUCTION.

SCALE: 1/4" = 1'-0"

MECHANICAL DEMOLITION-FIFTH FLOOR PLAN UNIT "A"1

MD105

NOT TO SCALE

EXISTING FIFTH FLOOR KEY PLAN

NRICHARD L. ROUDEBUSH

VA MEDICAL CENTER

UNIT

"A"

NOTE:

PATCH AND SEAL ALL UNUSED OPENINGS IN FLOOR TO

MAINTAIN FIRE RATING OF FLOOR.

AutoCAD SHX Text

MD105

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text

GENERAL MECHANICAL DEMO NOTES

AutoCAD SHX Text

MECHANICAL DEMOLITION NOTES

AutoCAD SHX Text N

AutoCAD SHX Text

FLOOR-PLAN-UNIT-"A"

AutoCAD SHX Text

MECHANICAL-DEMOLITION-FIFTH-

AutoCAD SHX Text

DDK

TEH

RHWHR

RHWH

3/4"

T

CLINIC / CLERK RECEPT.

A-6100

WAITING ROOM

A-6090

CARDIOLOGY RESIDENTS

A-6106

CARDIOLOGY OFFICE

A-6107

CARDIOLOGY FILES

A-6108

CARDIOLOGY FILES

A-6109

CORRIDOR

C6-5

TU-46-9

8"Ø

14"x14"

TU-46-9

8"Ø

"Ø

10"Ø

10"Ø

TU-39-15

D

D

RG

D

RG

10"ØTU-46-6

16"x10"

10"Ø

T

T

MICU WAITING

A-6002

ELEC. ROOM

A-6004

MONITOR ROOM

A-6005

MICU1-1

A-6006

MICU RECEPT.

A-6003

CORRIDOR

C6-15

WOMEN TOILET

A-6001

CHASE

EG

1 1

D D on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e W ai tin g R oo m s\

-P re -B id \F

O R C

E Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5

-1

-1

.M D

.d w g

-0

:2

:4

A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

1. ALL CONTRACTORS SHALL CLEAN SITE THOROUGHLY AT THE END OF EACH WORK DAY.

2. ALL CONTRACTORS TO VERIFY STAGING AND STORAGE LOCATIONS OF ALL MATERIALS

AND EQUIPMENT WITH CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO

BEGINNING OF CONSTRUCTION.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING

THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES, CONTRACTOR IS TO

CONTACT THE COR IMMEDIATELY.

EXISTING DIFFUSER / GRILLE TO BE REMOVED, CLEANED, AND PREPARE FOR

REINSTALLATION IN NEW CEILING.

SCALE: 1/4" = 1'-0"

MECHANICAL DEMOLITION-SIXTH FLOOR PLAN UNIT "B"1

MD106

NOT TO SCALE

EXISTING SIXTH FLOOR KEY PLAN

N

RICHARD L. ROUDEBUSH

VA MEDICAL CENTER

UNIT

"B"

UNIT

"A"

SCALE: 1/4" = 1'-0"

MECHANICAL DEMOLITION-SIXTH FLOOR PLAN UNIT "A"2

MD106

NOTE:

PATCH AND SEAL ALL UNUSED OPENINGS IN FLOOR TO

MAINTAIN FIRE RATING OF FLOOR.

AutoCAD SHX Text

MD106

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text N

AutoCAD SHX Text

UNITS-"A"-AND-"B"

AutoCAD SHX Text

SIXTH-FLOOR-PLAN-

AutoCAD SHX Text

MECHANICAL-DEMOLITION-

AutoCAD SHX Text N

AutoCAD SHX Text

DDK

AutoCAD SHX Text

TEH

AutoCAD SHX Text

GENERAL MECHANICAL DEMO NOTES

MECHANICAL DEMOLITION NOTES

on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e W ai tin g R oo m s\

-P re -B id \F

O R C

E Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5

-1

-1

.M G

.d w g

-0

:2

:3

A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

ROOFTOP UNITRTU-

DUCT WORK (UNLINED)

DUCT WORK (LINED)

VARIABLE AIR VOLUME TERMINAL BOX

DIFFUSER

DUCT COIL

FAN POWERED VAV BOX WITH REHEAT

EXHAUST OR RETURN GRILLE

RECTANGULAR DUCTXX"xXX"

ROUND DUCTX"Ø

DUAL DUCT TERMINAL BOX

SHUT-OFF TERMINAL BOX W/ REHEAT

SHUT-OFF TERMINAL BOX

FIRE DAMPER

TRANSFER AIR GRILLETG-

UNIT VENTILATOR

ABOVE FINISHED FLOOR

FLAT OVAL DUCT

UV-

VAV-

A.F.F.

XX"xXX"Ø

UNIT HEATERUH-

PRESSURE RELIEF VALVE

PRESSURE REGULATING VALVE

EXPANSION LOOP

TURBINE FLOWMETER

ORIFICE FLOWMETER

SUPPLY REGISTER

TERMINAL BOX

SUPPLY FANSF-

SR-

TB-

RELIEF VENTRV-

T H

SECURITY THERMOSTAT

HUMIDISTAT

AV

MV

S SMOKE SENSOR

MANUAL AIR VENT

AUTOMATIC AIR VENT

HUMIDIFIERH-

ELECTRIC RADIATIONRAD-

RETURN AIR GRILLE

RETURN REGISTER

ROOF CAP

RELIEF FAN

RC-

RF-

RG-

RR-

T T T

P

S TEMPERATURE SENSOR

ELECTRONIC THERMOSTAT

PNUEMATIC THERMOSTAT

FLEXIBLE DUCT

BACKDRAFT DAMPER

HEAT EXCHANGER

LOUVER

PUMP

CONDITIONING UNIT

HX-

L-

P-

HEATING VENTILLATION AIRHVAC-

P

MANUAL AIR BALANCING DAMPER

MANUAL OPPOSED BLADE DAMPER

ACTUATOR

PRESSURE GAUGE

TIE-IN

INLINE PUMP

EXHAUST GRILLEEG-

EXPANSION TANK

EXHAUST REGISTER

FINNED TUBE RADIATION

FIRE DAMPER

ER-

ET-

FD-

FTR-

PRESSURE & TEMPERATURE TEST PLUG

THERMOMETER

STRAINER

TEMPERATURE WELL

DUCT COILDC-

EXHAUST FANEF-

D-

CUH-

B- BOILER

DIFFUSER

CABINET UNIT HEATER

METER

PIPING RISE

PIPING DROP

THREADED HOSE CONNECTION W/ CAP

INLINE DROP

CHILLED WATER SUPPLY PIPING

CHILLED WATER RETURN PIPING

AS-

AHU-

AFMS-

ACCU-

CWR

AIR FLOW MEASURING STATION

AIR COOLED CONDENSING UNIT

CONDENSER WATER RETURN

AIR HANDLING UNIT

AIR SEPARATOR

AUTOMATIC FLOW CONTROL VALVE

MANUAL FLOW CONTROL VALVE

UNION

WITH P & T PORTS

BLIND FLANGE CONNECTION

WITH P & T PORTS

D

HWS

CHWS

HWR HOT WATER RETURN PIPING

HOT WATER SUPPLY PIPING

CONDENSATE DRAIN

CWS CONDENSER WATER SUPPLY

CHWR

PNEUMATIC 3-WAY VALVE

PNEUMATIC 2-WAY VALVE

ELECTRONIC 3-WAY VALVE

ELECTRONIC 2-WAY VALVE

CHECK VALVE

GLOBE VALVE

STEAMS

COND STEAM CONDENSATE

BALL VALVE

BUTTERFLY VALVE

MECHANICAL SYMBOL SCHEDULE

DUCT WORK (DOUBLE WALL/PERFORATED INNER)

NEW MECHANICAL EQUIPMENT

NEW MECHANICAL DUCTWORK

EXISTING MECHANICAL EQUIPMENT AND

DUCTWORK TO REMAIN

M

M

SMOKE/FIRE DAMPER

FD

SFD

LRP- LINEAR RADIANT PANEL

SFD- SMOKE/FIRE DAMPER

O.A.C. OPENING ABOVE CEILING

ST

T

HEAT PUMPHP-

MAU- MAKE UP AIR UNIT

GATE VALVE

FLANGE CONNECTION

PIPING SLEEVE

FLOW SWITCHF

SPHERICAL RUBBER VIBRATION ISOLATOR

PIPING INCREASER

T STEAM TRAP

FLOW METER WITH WELL

3 NTS

DUCTWORK SQUARE VANE ELBOWS

NOTE:

1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE

REGARDLESS OF W DIMENSION.

3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE

VANE TYPE.

W

W1

2 NTS

DUCTWORK RADIUS ELBOWS

VANE

VANE

NOTE:

1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS.

ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,

SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R SHALL EQUAL

OR BE GREATER

THAN W.

R SHALL EQUAL

OR BE GREATER

THAN 1/3W.

W

R

R

2/3W 1 /3

W R SHALL EQUAL

OR BE GREATER

THAN 1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W W

1/2W 1 /3

W

1/6W

R

4 NTS

SUPPLY DUCTWORK TAKE-OFFS

DESIGNER'S NOTES:

1. THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF THE MAIN DUCT CFM.

THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM ANYTIME

AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000 FPM [5.1 M/S] OR LESS. THE AIR

SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL OTHER CASES AND MAY BE USED AT ANYTIME.

2. SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.

AIR SPLIT DUCT TAKE-OFF PLAN

VIEW

BRANCH DUCT TAKE-OFF PLAN VIEW

SUPPLY REGISTER TAKE-OFF PLAN

VIEW

AIR

FLOW

AIR

FLOW

A

IR

FL

O

W

SUPPLY REGISTER OR

BRANCH DUCT

TURNING VANES

MAIN SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

PROVIDE VOLUME

DAMPER

PROVIDE VOLUME

DAMPER

ADJUSTABLE

METAL ROD OR

LINKAGE

TOP REGISTER

MAIN SUPPLY

DUCT

VOLUME EXTRACTOR; ADJUSTABLE FROM

FULLY CLOSED POSITION TO CFM NOTED

ON FLOOR PLANS

AIR

FLOW

AIR

FLOW

1/4 W OR

4" [100mm] MIN.

AIR

FLOW

MAIN SUPPLY DUCT

W

A

IR

FL

O

W

6 NTS

EXHAUST OR RETURN BRANCH DUCTWORK

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR

FLOW AIR

FLOW

W

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4"

[100mm] MIN.

BRANCH DUCT

VD

5 NTS

VOLUME DAMPER DETAIL

NOTE:

1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8" [6mm]

CLEARANCE ALL

AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION

STAND-OFF

1/2" [15mm] ROUND

ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

1 NTS

FLEXIBLE DUCT CONNECTIONS

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED CONNECTION

ON FAN SIDE

WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" [25x3mm] DRAW BAND

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS ON

12" [300mm] CENTERS

RIVET ON 4"

[100mm] CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEM

ALTERNATE

POSITION

OF BOLT

1 1/2" [40mm]

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1/2" [15mm]

1/2" [15mm]

1 1/2" [40mm]

1 1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL AS

SPECIFIED

DIFFUSER - SEE PLANS FOR

TYPES AND SIZES.

SUPPORT FROM CEILING

GRIDWORK OR BUILDING

STRUCTURE.

MANUAL BALANCE DAMPER LEAVE HANDLE

CLEAR FOR BALANCING, EXTEND BLADE

SHAFT TO PREVENT EXTERNAL INSULATION

DAMAGE FROM HANDLE

SEE PLANS FOR

DUCT SIZES

FLEXIBLE DUCT. KEEP DUCT

AS SHORT AS POSSIBLE.

MAX. LENGTH 6 FT. MAY BE

LOCATED IN VERTICAL DROP

TO DIFFUSER

RIGID METAL

ELBOW USE FOR

CHANGES IN

DIRECTION

7 NTS

TYPICAL CEILING DIFFUSER INSTALLATION DETAIL

TAG

D-1 D-2 D-3 D-4

RG-1

EG-1

EG-2

REMARKS:

1. PROVIDE ALL NECESSARY TRIM AND BORDERS FOR INSTALLATION INTO CEILING TYPES AND WALLS. REFER TO ARCHITECTURAL

DRAWINGS FOR ROOM FINISHES.

2. PROVIDE AND INSTALL DUCT TRANSITION FITTINGS AS REQUIRED FOR CONNECTION TO DIFFUSERS AND GRILLES.

3. COLOR SHALL BE WHITE.

MFG

MODEL

NECK

6" 8" 10" 6"

FACE

24" x 24" 24" x 24" 24" x 24" 12" x 12"

24" x 24"

8"x8" 24" x 24"

PATTERN

4-WAY

4-WAY

4-WAY

4-WAY

DIFFUSER SCHEDULE

TYPE

LOUVER

LOUVER

LOUVER

LOUVER

PERFORATED

BAR

PERFORATED

MAX CFM

MAX PD

(TOTAL)

0.04 0.05 0.03 0.02

0.05

0.07 0.04

MAX NC

THROW

(FEET)

2-3-5 3-5-9 3-5-9 2-2-5

MATERIAL

STEEL

STEEL

STEEL

STEEL

ALUMINUM

ALUMINUM

ALUMINUM

REMARKS

1, 2, 3 1, 2, 3 1, 2, 3 1, 2, 3

1, 2, 3

1, 2, 3 1, 2, 3

AutoCAD SHX Text

MECHANICAL-GENERAL-INFORMATION

AutoCAD SHX Text

MG001

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text

DDK

N D

N D

WIFI

$MO

S

$MO

EX

30 MINUTE SMOKE BARRIER 30 MINUTE SMOKE BARRIER 30 MINUTE SMOKE BARRIER

WAITING ROOM

B-B001

MEN TOILET

B-B030

EXAM 1

B-B002

EXAM 2

B-B003

EXAM 3

B-B004

CORRIDOR

CB-11

RADIATION ONCOLOGY

RECEPTION OFFICE

B-B029

HANDICAP TOILET

B-B028

SOILED UTILITY

B-B027

DRESS. RM.

B-B005A

CHASE

CORRIDOR

CB-55

DOCTOR OFFICE

B-B026CORRIDOR

CB-2

CORRIDOR

CB-3

WOMEN TOILET

B-B031

NURSES

B-B005

T

D

D on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e W ai tin g R oo m s\

-P re -B id \F

O R C

E Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5

-1

-1

.M H

.d w g

-0

:2

:2

A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

1. ALL CONTRACTORS SHALL CLEAN SITE THOROUGHLY AT THE END OF EACH WORK DAY.

2. ALL CONTRACTORS TO VERIFY STAGING AND STORAGE LOCATIONS OF ALL MATERIALS

AND EQUIPMENT WITH CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO

BEGINNING OF CONSTRUCTION.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING

THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES, CONTRACTOR IS TO

CONTACT THE COR IMMEDIATELY.

EXISTING DIFFUSER / GRILL TO BE CLEANED AND REINSTALLATION IN NEW CEILING AT

THE SAME LOCATION.

SCALE: 1/4 = 1'-0"

MECHANICAL - BASEMENT FLOOR PLAN UNIT "A"1

MH100

NOT TO SCALE

EXISTING BASEMENT KEY PLAN

N

RICHARD L. ROUDEBUSH

VA MEDICAL CENTER

UNIT A

UNIT B

UNIT

"A"

NOTE:

PATCH AND SEAL ALL UNUSED OPENINGS IN FLOOR TO

MAINTAIN FIRE RATING OF FLOOR.

AutoCAD SHX Text

MECHANICAL-BASEMENT-FLOOR-PLAN

AutoCAD SHX Text

MH100

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text

GENERAL MECHANICAL NOTES

AutoCAD SHX Text

MECHANICAL NOTES

AutoCAD SHX Text N

AutoCAD SHX Text

UNIT-"A"

AutoCAD SHX Text

DDK

CORRIDOR

C2-27

CORRIDOR

C2-28

RECOVERY ROOM

C-2041

PROG. ASSISTANT

RADIOLOGY C-2043

RADIOLOGY READING

ROOM C-2038

RADIOLOGY WAITING ROOM

C-2040

RECEPTION

C-2039

CORRIDOR

C2-25

CONTROL

C-2057

T

9" Ø FLEX

EG-2

(195)

"x8

"x8

16"x8"

28"x10"

8"Ø

"x1

0"

"x1 0"

10"x8"

"x8

24"x10"

"x1

0"

TU

-3

2-

D-2 (120)

T

TU-32-47

D-2 (220)

D-2 (220)

TU-32-47

TU-32-56

RG-1

(120)

RG-1

(325)

8"Ø

8"Ø

12"Ø

10"Ø

8"Ø

8"Ø

8"Ø on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e W ai tin g R oo m s\

-P re -B id \F

O R C

E Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5

-1

-1

.M H

A .d w g

-0

:2

:0

A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

1. ALL CONTRACTORS SHALL CLEAN SITE THOROUGHLY AT THE END OF EACH WORK DAY.

2. ALL CONTRACTORS TO VERIFY STAGING AND STORAGE LOCATIONS OF ALL MATERIALS

AND EQUIPMENT WITH CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO

BEGINNING OF CONSTRUCTION.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING

THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES, CONTRACTOR IS TO

CONTACT THE COR IMMEDIATELY.

SCALE: 1/4" = 1'-0"

MECHANICAL - SECOND FLOOR PLAN UNIT "A"1

MH102A

NOT TO SCALE

EXISTING SECOND FLOOR KEY PLAN

NRICHARD L. ROUDEBUSH

VA MEDICAL CENTER

UNIT

"A"

PROVIDE AND INSTALL NEW DIFFUSER/GRILLE. TRANSITION AND CONNECT TO EXISTING

DUCTWORK AS REQUIRED

RELOCATE EXISTING TEMPERATURE SENSOR. EXTEND WIRING TO NEW LOCATION.

MAINTAIN EXISTING SEQUENCE OF OPERATION.

RECONNECT TO EXISTING DUCT.

PATCH EXISTING SUPPLY AIR DUCTWORK TO BE AIRTIGHT.

NOTE:

PATCH AND SEAL ALL UNUSED OPENINGS IN FLOOR TO

MAINTAIN FIRE RATING OF FLOOR.

AutoCAD SHX Text

MECHANICAL-SECOND-FLOOR-PLAN-UNIT-"A"

AutoCAD SHX Text

MH102A

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text

GENERAL MECHANICAL NOTES

AutoCAD SHX Text

MECHANICAL NOTES

AutoCAD SHX Text N

AutoCAD SHX Text

DDK

TU-12-163

TU-12-163

M.H. WAITING AREA

D-5030

M.H. PRRC CHECK-IN

D-5029

M.H. SOC. WORKER

D-5028

CORRIDOR

C5-16

M.H. ADMIN OFFICE

D-5031

D-5032

8"Ø

8"Ø

"x1

2"

" O

VA

L

RG

8"Ø

RG

8"Ø

TU-13-163

TU-12-162

D (225)

D (180)

D (180) on e ei gh th in ch o ne f oo t

B

A

C

D th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e W ai tin g R oo m s\

-P re -B id \F

O R C

E Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5

-1

-1

.M H

.d w g

-0

:2

:5

A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

1. ALL CONTRACTORS SHALL CLEAN SITE THOROUGHLY AT THE END OF EACH WORK DAY.

2. ALL CONTRACTORS TO VERIFY STAGING AND STORAGE LOCATIONS OF ALL MATERIALS

AND EQUIPMENT WITH CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO

BEGINNING OF CONSTRUCTION.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING

THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES, CONTRACTOR IS TO

CONTACT THE COR IMMEDIATELY.

RELOCATE EXISTING TEMPERATURE SENSOR. EXTEND WIRING TO NEW LOCATION.

MAINTAIN EXISTING SEQUENCE OF OPERATION.

SCALE: 1/4" = 1'-0"

MECHANICAL - FIFTH FLOOR PLAN UNIT "A"1

MH105

NOT TO SCALE

EXISTING FIFTH FLOOR KEY PLAN

NRICHARD L. ROUDEBUSH

VA MEDICAL CENTER

UNIT

"A"

NOTE:

PATCH AND SEAL ALL UNUSED OPENINGS IN FLOOR TO

MAINTAIN FIRE RATING OF FLOOR.

AutoCAD SHX Text

MH105

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text

GENERAL MECHANICAL NOTES

AutoCAD SHX Text

MECHANICAL NOTES

AutoCAD SHX Text N

AutoCAD SHX Text

UNIT-"A"

AutoCAD SHX Text

MECHANICAL-FIFTH-FLOOR-PLAN

AutoCAD SHX Text

DDK

RHWHR

RHWH

3/4"

T

CLINIC / CLERK RECEPT.

A-6100

WAITING ROOM

A-6090

CARDIOLOGY RESIDENTS

A-6106

CARDIOLOGY OFFICE

A-6107

CARDIOLOGY FILES

A-6108

CARDIOLOGY FILES

A-6109

CORRIDOR

C6-5

TU-46-9

8"Ø

14"x14"

TU-46-9

8"Ø

"Ø

10"Ø

10"Ø

TU-39-15

D

D

RG

D

RG

10"ØTU-46-6

16"x10"

10"Ø

T

T

MICU WAITING

A-6002

ELEC. ROOM

A-6004

MONITOR ROOM

A-6005

MICU1-1

A-6006

MICU RECEPT.

A-6003

CORRIDOR

C6-15

WOMEN TOILET

A-6001

CHASE

1 1

D D on e ei gh th in ch o ne f oo t

B

A

C

D th re e in ch es o ne f oo t 6 on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

S :\1

_P ro je ct s\

FY

\5

-1

-1

R en ov at e

W ai tin g

R oo m s\

-P re -B id \F

O R C E

Pk g.

-2

-1

\N ew R ev is ed D ra w in gs \A ut oC

A D

\5 -1

-1

.M

H

.d w g

-0 -1

:2

:3

P

M

V H A

IN

D

FE

R N A A

Scale: 1/4"=1'-0"

All concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design

Inc. and shall not be used for any purpose without prior expressed written consent. The

Contracting Officer Representative shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard

Suite 200

Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

VIRIDIAN

ARCHITECTURAL DESIGN INC.

1. ALL CONTRACTORS SHALL CLEAN SITE THOROUGHLY AT THE END OF EACH WORK DAY.

2. ALL CONTRACTORS TO VERIFY STAGING AND STORAGE LOCATIONS OF ALL MATERIALS

AND EQUIPMENT WITH CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO

BEGINNING OF CONSTRUCTION.

3. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING

THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES, CONTRACTOR IS TO

CONTACT THE COR IMMEDIATELY.

EXISTING DIFFUSER / GRILLE TO BE CLEANED AND REINSTALLATION IN NEW CEILING AT

THE SAME LOCATION.

NOT TO SCALE

EXISTING SIXTH FLOOR KEY PLAN

N

RICHARD L. ROUDEBUSH

VA MEDICAL CENTER

UNIT

"B"

UNIT

"A"

SCALE: 1/4" = 1'-0"

MECHANICAL - SIXTH FLOOR PLAN UNIT "B"

SCALE: 1/4" = 1'-0"

MECHANICAL - SIXTH FLOOR PLAN UNIT "A"

MH106

MH106

NOTE:

PATCH AND SEAL ALL UNUSED OPENINGS IN FLOOR TO

MAINTAIN FIRE RATING OF FLOOR.

AutoCAD SHX Text

MH106

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of 88

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

INDIANAPOLIS, INDIANA

AutoCAD SHX Text

RENOVATE WAITING ROOMS, 8FY15

AutoCAD SHX Text 583-15-108

AutoCAD SHX Text 08/06/2019

AutoCAD SHX Text

BUILDING 1

AutoCAD SHX Text

CERTIFICATION:

AutoCAD SHX Text This is an original design, created by SCO ENGINEERING, LLC.

AutoCAD SHX Text The concepts, ideas, plans and details are the sole property

AutoCAD SHX Text of SCO ENGINEERING, LLC. None of the concepts, ideas, plans

AutoCAD SHX Text or details shall be used by or disclosed to any person, firm

AutoCAD SHX Text or corporation for any purpose without the prior written

AutoCAD SHX Text permission of SCO ENGINEERING, LLC. Written dimensions on

AutoCAD SHX Text these drawings shall have precedence over scale dimensions

AutoCAD SHX Text Contractors shall verify and be responsible for all dimensions

AutoCAD SHX Text and conditions on the job and SCO ENGINEERING, LLC must be

AutoCAD SHX Text notified of any variation from the dimensions and conditions

AutoCAD SHX Text shown on these drawings. Shop drawings shall be submitted

AutoCAD SHX Text to SCO ENGINEERING, LLC for approval before fabrication.

AutoCAD SHX Text Copyright 2018 c

AutoCAD SHX Text Fort Wayne, Indiana 46804

AutoCAD SHX Text

FORT WAYNE

AutoCAD SHX Text 6534 Constitution Dr.

AutoCAD SHX Text

(260) 436-9213

AutoCAD SHX Text

(260) 432-5481 fax

AutoCAD SHX Text scofw@sco-llc.com

AutoCAD SHX Text

SOLUTIONS PROVIDED PROBLEMS SOLVED

AutoCAD SHX Text

GENERAL MECHANICAL NOTES

AutoCAD SHX Text

MECHANICAL NOTES

AutoCAD SHX Text

MECHANICAL-SIXTH-FLOOR-PLAN

AutoCAD SHX Text

-UNITS-"A"-AND-"B"

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text

DDK

583-15-108-MD100
Sheets and Views
MG001
583-15-108-MD102A
Sheets and Views
MD102A
583-15-108-MD105
Sheets and Views
MG001
583-15-108-MD106
Sheets and Views
MD106
583-15-108-MG001
Sheets and Views
MG001
583-15-108-MH100
Sheets and Views
MG001
583-15-108-MH102A
Sheets and Views
MH102A
583-15-108-MH105
Sheets and Views
MG001
583-15-108-MH106
Sheets and Views
MH106

File details come from the government source that posted it. Updated .