SECTION 23 34 00 HVAC FANS
PART 1 - GENERAL
1.1 DESCRIPTION
A. Fans for heating, ventilating and air conditioning.
B. Product Definitions: AMCA Publication 99, Standard l-66.
1.2 RELATED WORK
| A. Section |
| 01 |
| 00 |
| 00, |
| GENERAL REQUIREMENTS. |
| B. Section |
| 01 |
| 33 |
| 23, |
| SHOP DRAWINGS, PRODUCT DATA, AND |
| SAMPLES. |
| C. Section |
| 23 |
| 05 |
| 11, |
| COMMON WORK RESULTS FOR HVAC AND |
| STEAM GENERATION. |
D. Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.
E. Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.
| F. Section |
| 23 |
| 05 |
| 93, |
| TESTING, ADJUSTING, AND BALANCING FOR HVAC. |
| G. Section |
| 23 |
| 73 |
| 00, |
| INDOOR CENTRAL-STATION AIR-HANDLING UNITS. |
| H. Section |
| 26 |
| 29 |
| 11, |
| LOW-VOLTAGE MOTOR STARTERS. |
1.3 QUALITY ASSURANCE
A. Fans and power ventilators shall be listed in the current edition of AMCA 262, and shall bear the AMCA performance seal.
B. Operating Limits for Centrifugal Fans: AMCA 99 (Class I, II, and III).
C. Fans and power ventilators shall comply with the following standards:
l. Testing and Rating: AMCA 2l0.
2. Sound Rating: AMCA 300.
D. Performance Criteria:
l. The fan schedule shows cubic meters per minute (CFM) and design static pressure. Scheduled fan motors, 0.37 kW (l/2 horsepower) and larger, are sized for design cubic meters per minute (CFM) at ll0 percent design static pressure, but not to exceed 185 Pa (3/4-inch) additional pressure.
2. Provide fans and motors capable of stable operation at design conditions and at ll0 percent pressure as stated above.
3. Lower than design pressure drop of approved individual components may allow use of a smaller fan motor and still provide the safety factor. When submitted as a deviation a smaller motor may be approved in the 06-04M
USP 797 Pharmacy Upgrade VA Medical Center Dayton, OH
23 34 00 -interest of energy conservation. The contractor shall be responsible for making necessary changes to the electrical system.
4. Select fan operating point as follows:
a. Forward curved and axial fans: Right hand side of peak pressure point.
b. Airfoil, backward inclined or tubular: Near the peak of static efficiency.
E. Safety Criteria: Provide manufacturer's standard screen on fan inlet and discharge where exposed to operating and maintenance personnel.
F. Corrosion Protection:
1. Except for fans in fume hood exhaust service, all steel shall be mill-galvanized, or phosphatized and coated with minimum two coats, corrosion resistant enamel paint. Manufacturers paint and paint system shall meet the minimum specifications of: ASTM D1735 water fog; ASTM B117 salt spray; ASTM D3359 adhesion; and ASTM G152 and G153 for carbon arc light apparatus for exposure of non-metallic material.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Manufacturers Literature and Data:
l. Fan sections, motors and drives.
2. Centrifugal fans, motors, drives, accessories and coatings.
a. In-line centrifugal fans.
b. Utility fans and vent sets.
C. Certified Sound power levels for each fan.
D. Motor ratings types, electrical characteristics and accessories.
E. Roof curbs.
F. Belt guards.
G. Maintenance and Operating manuals in accordance with Section 01 00 00, GENERAL REQUIREMENTS.
H. Certified fan performance curves for each fan showing cubic meters per minute (CFM) versus static pressure, efficiency, and horsepower for design point of operation and at ll0 percent of design static pressure. Include product application data to indicate the effect of capacity control devices such as inlet vane dampers on flow, pressure and kW (horsepower).
1.5 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American Bearing Manufacturers Association (ABMA):
9-90....................Load Ratings and Fatigue Life for Ball Bearings C. Air Movement and Control Association International, Inc. (AMCA): 99-86...................Standards Handbook 2l0-99..................Laboratory Methods of Testing Fans for Aerodynamic Performance Rating 262-03..................AMCA Directory of Agricultural Products With Certified Ratings 300-05..................Reverberant Room Method for Sound Testing of Fans D. American Society for Testing and Materials (ASTM):
B117-07.................Standard Practice for Operating Salt Spray (Fog) Apparatus D1735-04................Standard Practice for Testing Water Resistance of Coatings Using Water Fog Apparatus D3359-02................Standard Test Methods for Measuring Adhesion by Tape Test G152-06.................Standard Practice for Operating Open Flame Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials G153-04.................Standard Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials E. National Fire Protection Association (NFPA):
96-08...................Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations F. National Sanitation Foundation (NSF):
37-07...................Air Curtains for Entrance Ways in Food and Food Service Establishments G. Underwriters Laboratories, Inc. (UL):
181-05..................Standard for Factory-Made Air Ducts and Air Connectors
PART 2 - PRODUCTS
2.1 FAN SECTION (CABINET FAN)
Refer to specification Section 23 73 00, INDOOR CENTRAL-STATION AIR- HANDLING UNITS.
2.2 CENTRIFUGAL FANS
A. Standards and Performance Criteria: Refer to Paragraph, QUALITY ASSURANCE. Record factory vibration test results on the fan or furnish to the Contractor.
B. Fan arrangement, unless noted or approved otherwise:
l. DWDl fans: Arrangement 3.
2. SWSl fans: Arrangement l, 3, 9 or l0.
C. Construction: Wheel diameters and outlet areas shall be in accordance with AMCA standards.
l. Housing: Low carbon steel, arc welded throughout, braced and supported by structural channel or angle iron to prevent vibration or pulsation, flanged outlet, inlet fully streamlined. Provide lifting clips, and casing drain. Provide manufacturer's standard access door. Provide 12.5 mm (1/2") wire mesh screens for fan inlets without duct connections.
2. Wheel: Steel plate with die formed blades welded or riveted in place, factory balanced statically and dynamically.
3. Shaft: Designed to operate at no more than 70 percent of the first critical speed at the top of the speed range of the fans class.
4. Bearings: Heavy duty ball or roller type sized to produce a Bl0 life of not less than 40,000 hours, and an average fatigue life of 200,000 hours. Extend filled lubrication tubes for interior bearings or ducted units to outside of housing.
5. Belts: Oil resistant, non-sparking and non-static. Furnish one additional complete set of belts for each belt-driven fan.
6. Belt Drives: Factory installed with final alignment belt adjustment made after installation.
7. Motors and Fan Wheel Pulleys: Adjustable pitch for use with motors through 15HP, fixed pitch for use with motors larger than 15HP. Select pulleys, so that pitch adjustment is at the middle of the adjustment range at fan design conditions.
| 8. Motor, adjustable motor base, drive and guard: Furnish from factory with fan. | Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION for specifications. Provide protective sheet metal enclosure for fans located outdoors. |
| 9. Furnish variable speed fan motor controllers where shown on the drawings. | Refer to Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION for controller/motor combination requirements. |
D. In-line Centrifugal Fans: In addition to the requirements of paragraphs A and C, provide inlet and outlet flanges, bolted access door and arrangement 1, 4 or 9 supports as required.
E. Utility Fans, Vent Sets and Small Capacity Fans: Class l design, arc welded housing, spun intake cone. Applicable construction specification, paragraphs A and C, for centrifugal fans shall apply for wheel diameters
300 mm (l2 inches) and larger. Requirement for AMCA seal is waived for wheel diameters less than 300 mm (l2 inches) and housings may be cast iron.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install fan, motor and drive in accordance with manufacturer's instructions.
B. Align fan and motor sheaves to allow belts to run true and straight.
C. Bolt equipment to curbs with galvanized lag bolts.
D. Install vibration control devices as shown on drawings and specified in Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.
3.2 PRE-OPERATION MAINTENANCE
A. Lubricate bearings, pulleys, belts and other moving parts with manufacturer recommended lubricants.
B. Rotate impeller by hand and check for shifting during shipment and check all bolts, collars, and other parts for tightness.
C. Clean fan interiors to remove foreign material and construction dirt and dust.
3.3 START-UP AND INSTRUCTIONS
A. Verify proper operation of motor, drive system and fan wheel.
B. Check vibration and correct as necessary for air balance work.
C. After air balancing is complete and permanent sheaves are in place perform necessary field mechanical balancing to meet vibration tolerance in Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.
- - - E N D - - -