36C25018B0814-0002001.docx

DOCX document 12 KB Posted

Attached to
Update In-Patient Pharmacy to Comply with USP 800 - 583-19-201
Solicitation number
36C25018B0814
Issued by

About this file

36C25018B0814 0002 Solicitation 36C25018B0814 - RFI Responses #1.docx

View the file

Other files

File Type Posted
36C25018B0814-0002000.docx DOCX document
36C25018B0814-0001001.pdf PDF
36C25018B0814-0001000.docx DOCX document
36C25018B0814-020.pdf PDF
36C25018B0814-018.doc DOC document
36C25018B0814-027.pdf PDF
36C25018B0814-019.docx DOCX document
36C25018B0814-023.pdf PDF
36C25018B0814-022.pdf PDF
36C25018B0814-025.pdf PDF
36C25018B0814-017.docx DOCX document
36C25018B0814-026.pdf PDF
36C25018B0814-016.docx DOCX document
36C25018B0814-024.pdf PDF
36C25018B0814-021.pdf PDF
36C25018B0814-000.docx DOCX document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation 36C25018B0814, Update Inpatient Pharmacy RFI Responses

Question #1: Who is existing HEPA Filter Housing Manufacturer?

Response #1: The HEPA filter manufacturer that we use is American Air, Inc. We have hired Artech Environmental, Inc. to perform the installation work as part of an annual contract.

Question #2: Dwg MH-104: Exhaust fans 1-EF-10 & 11 are located on the roof. Where do we access the roof?

Response #2: Roof access is via a stairway located at Column 14 and G at the top of the page.

Question #3: On dwg MH-401, Notes 5,7 & 10 show new supply and exhaust duct penetrating the floor next to the existing AHU AC-50. There is an existing floor drain next to AC-50 that is adjacent to the new duct penetrations. Do we know the routing of this existing floor drain so there is no interference with the new duct work?

Response #3: The eighth-floor mechanical room existing floor drain piping can be found on PP102, Detail 5.