Facility Condition Assessment Deficiencies 2021 FCA report1.xls
XLS spreadsheet 77 KB Posted
- Solicitation number
- 36C24924R0016
About this file
This Excel spreadsheet contains a facility condition assessment report for Building 35, an historic theater at the Mountain Home VA Medical Center. The report identifies over $12 million in deficiencies across architectural, electrical, plumbing, and structural systems that require repair or replacement. Deficiencies include inaccessible stages and restrooms, unreinforced masonry, single pane windows, and outdated electrical and lighting systems. The related federal contract opportunity is a pre-solicitation notice for an architect-engineer restoration contract. The solicitation number is 36C24924R0016 and the opportunity is for design services to address the deficiencies in the historic theater building identified in the condition assessment report. The restoration project will be conducted by the Department of Veterans Affairs Veterans Health Administration VISN 9.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24924R0016 0001.pdf | ||
| Past Performance Questionnaire (PPQ).pdf | ||
| 36C24924R0016.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Station Name | FCA_ID | Building No | Function Title | Maintenance Category | System | Subsystem | Correction Cost | Completed Correction Cost | Remaining Cost | Condition | Description |
| Mountain Home | 114902 | 35 | Old Theater | Heritage | Architectural | Accessibility | $91,349 | $91,349 | D | Stage not accessible, provide (1) wheel chair lift. * Restrooms do not meet VA ABAAS and are undersized per occupant load. Renovate (2) rooms at 200 SF each - which would inlcude a total of 4 sinks, 4 toilets, 4 36" grab bars and 4 42" grab bars. * Provide (1) compliant drinking fountain. * Remove approx 6 seats to provide wheelchair seating. Replace approx (10) door knobs with accessuble lever type hardware. | |
| Mountain Home | 59951 | 35 | Old Theater | Heritage | Architectural | Accessibility | $24,598 | $24,598 | D | Existing ramp to front doors does not meet VA ABAAS. Install new ramp, approx 20lf, with handrail to front doors. | |
| Mountain Home | 114903 | 35 | Old Theater | Heritage | Architectural | Exterior Walls | $78,302 | $78,302 | D | Tuckpoint 2000 SF of brick masonry. * Clean entire masonry exterior (approx 15,000SF) and apply water repellant. | |
| Mountain Home | 287860 | 35 | Old Theater | Heritage | Architectural | Interior Finish/Door | $5,132 | $5,132 | D | Replace flooring in projection room with vinyl planks - approx 500 SF. | |
| Mountain Home | 287856 | 35 | Old Theater | Heritage | Architectural | Interior Finish/Door | $9,593 | $9,593 | D | Repair approx 1000SF of plaster walls and repaint. | |
| Mountain Home | 59954 | 35 | Old Theater | Heritage | Architectural | Interior Finish/Door | $20,041 | $20,041 | D | Carpet in poor condition. Replace approx 2000 SF. | |
| Mountain Home | 340368 | 35 | Old Theater | Heritage | Architectural | Life Safety | $40,682 | $40,682 | D | Add panic hardware on (10) double doors. | |
| Mountain Home | 114905 | 35 | Old Theater | Heritage | Architectural | Roof | $10,414 | $10,414 | F | Replace approx 800SF of flat roof with TPO membrane. | |
| Mountain Home | 56893 | 35 | Old Theater | Heritage | Architectural | Roof | $15,778 | $15,778 | D | Replace approx 1000SF of slate roof | |
| Mountain Home | 56894 | 35 | Old Theater | Heritage | Architectural | Signage / Wayfindg | $5,150 | $5,150 | D | Add (1) exteior facility standard building identification sign. Add approx (15) interior room signs and (1) interior wayfinding sign. | |
| Mountain Home | 56895 | 35 | Old Theater | Heritage | Architectural | Windows | $149,367 | $149,367 | D | Single pane wood framed windows are in poor condition needing replacement. (25) windows, average size: 2' x 3'. Historic window replacement. | |
| Mountain Home | 56897 | 35 | Old Theater | Heritage | Electrical | Emerg Elec Sys. | $15,792 | $15,792 | F | There is no emergency egress lighting nor exit lighting. Provide 12 battery powered egress bug eyes and 12 LED exit signs/lights. | |
| Mountain Home | 56899 | 35 | Old Theater | Heritage | Electrical | Lighting & Power | $137,189 | $137,189 | D | Existing house lighting is incandescent. The stage has specialty stage lighting. Replace all with LED fixtures. | |
| Mountain Home | 56900 | 35 | Old Theater | Heritage | Electrical | Lightning Protect | $20,060 | $20,060 | D | Inspect existing sytem & repair lightning rods and grounding conductors to meet NFPA 780 requirements. | |
| Mountain Home | 114907 | 35 | Old Theater | Heritage | Electrical | Secondary Dist. | $17,338 | $17,338 | D | Replace one (1) 225A ITE panelboard located in the basement and two (2) 100A square D panelboards that are located by the stage. All of the panels have reached the end of their useful life and are rusted and obsolete.. | |
| Mountain Home | 56912 | 35 | Old Theater | Heritage | Plumbing | Fixtures / Piping | $123,507 | $123,507 | D | Plumbing fixtures and piping are in poor condition and should be replaced. | |
| Mountain Home | 340369 | 35 | Old Theater | Heritage | Structural | Building Frame Seismic | $3,652,454 | $3,652,454 | D | Unreinforced brick masonry shear walls with concrete slab diaphragms and wood sheathing diaphragm at roof on steel trusses. * HAZUS Model Building Type URML. * Current Assembly use. * Seismic retrofit required per VA Seismic Inventory. See Seismic Report for details. Code E0 (not exempt). * Building is in Moderate High (MH) seismic zone per H-18-8. | |
| Mountain Home | 56916 | 35 | Old Theater | Heritage | Structural | Foundations | $655,399 | $655,399 | D | Brick masonry foundation walls require repair and repointing. Approx 2000 SF | |
| Mountain Home | 340371 | 35 | Old Theater | Heritage | Structural | Non Structural Components & Equipments-Seismic | $3,140,389 | $3,140,389 | D | Building Partitions: Interior unreinforced brick walls not braced for out-of-plane. * Ceiling Systems: Tie bracing and compression strut were not observed. * Light Fixtures: Light system not braced to structure. * Mechanical & Electrical Equipment: Mechanical and electrical equipment is not anchored. * Piping: No bracing was observed on any fire protection piping or any other mechanical pipes. * Ductwork: Ducts in general are less than 6 sq.ft for rectangular and 28" diameter for round and therefore do not require bracing. The larger ducts in attic space are not braced. * Provide anchorage and bracing per H-18-8 and ASCE7-10 Chapter 13. |