626-22-203 Mixing Valves Faucets and Showers SOW Final 07.07.2023.pdf
PDF 158 KB Posted
- Solicitation number
- 36C24923B0015
About this file
This statement of work outlines requirements for a construction project to upgrade mixing valves, faucets, and showers at the Tennessee Valley Healthcare System Nashville Campus. The scope of work includes removing existing fixtures and installing new valves, faucets, shower assemblies, and biocide injection ports. It specifies performance periods, contractor requirements, submittal processes, coordination needs, safety and infection control protocols, and reporting requirements. Key details include replacing approximately 130 fixtures and installing 20 biocide injection ports within 130 calendar days of the notice to proceed. The Department of Veterans Affairs is the contracting agency, with oversight from the Veterans Health Administration and Veterans Integrated Service Network 9.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 224000 Plumbing Fixtures 07.07.2023.pdf | ||
| 36C24923B0015 0004.docx | DOCX document | |
| RFI Answers Final.pdf | ||
| 36C24923B0015 0003.docx | DOCX document | |
| 36C24923B0015 0002.docx | DOCX document | |
| 36C24923B0015 0002 626-22-203 Upgrade Mixing Valves Faucets and Showers Site Visit Sign In Sheet.pdf | ||
| 36C24923B0015 0001.docx | DOCX document | |
| 36C24923B0015 06012023.docx | DOCX document | |
| RFI Form.docx | DOCX document | |
| Copy of Nashville Campus - 626-22-203 Work and Locations.pdf | ||
| UEI _ TAX ID.docx | DOCX document | |
| 626-22-203 Specs Upgrade Valves Faucets and Shower.pdf | ||
| General Decision Number TN20230178 05122023.pdf | ||
| BIOCIDE INJECTION PORT DETAIL.pdf | ||
| Contractor EMR Certification Form.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT #626-22-203 UPGRADE MIXING VALVES, FAUCETS AND SHOWERS
STATEMENT OF WORK
Department of Veterans Affairs TVHS, Nashville Campus
Construction Requirements Project Number 626-22-203
Upgrade Mixing Valves, Faucets and Showers
A. GENERAL INFORMATION
1. Scope of Work: Provide construction services to Upgrade Mixing Valves, Faucets and Shower assemblies and the removal of identified fixtures and/or piping for project 626-22-203 at the Tennessee Valley Healthcare System Nashville Campus at 1310 24th Avenue South, Nashville, TN 37212. In addition, the work includes the installation of valves and biocide injection ports. The contractor shall furnish all labor, material, equipment, and supervision necessary to successfully complete all work as described. The job includes general construction, plumbing, disconnecting some electrical fixtures, and the restoration of drywall and finishes.
2. Performance Period: The contractor shall complete the work required under this statement of work (SOW) within the 130 calendar days from date of the Notice to Proceed, which includes all work, submittals, material lead times, inspection, and closeout. Unless otherwise stated, any modifications required under the resulting contract and shall be submitted by the contractor and approved by the Contracting Officer (CO).
B. CONTRACTOR GENERAL REQUIREMENTS
1. Fully Functional & Complete: When “furnish”, “provide”, “install”, “construct”, “renovate’, “upgrade” or similar term is used, it shall mean a complete installation by the contractor, fully functional and ready for use, including all supervision, coordination, labor, materials, equipment and to perform the job, as well as all associated costs, such as disposal, handling, delivery/transportation, storage, fees, taxes, etc. For the purposes of this contract/project, if direction/statement is silent as to who shall performs work or provides services/items, it is meant to be the contractor’s responsibility.
2. Time for Deliverables (5-day max): Unless noted otherwise, any written milestone or deliverable shall be provided within 5 days. VA reviews of a deliverable shall also be completed within 5 business days from the date of receipt. If revisions are required, the contractor shall deliver any revisions within 5 days from the date of receipt. All written deliverables shall be phrased in lay person language.
3. Survey of Existing Conditions: The Department of Veterans Affairs intends to have the contractor fully survey, investigate, and document the existing conditions/locations, fixtures, connections and finishes to gain the knowledge and insight necessary to determine the required labor, supervision, and materials, including all components, accessories, and options to successfully develop a complete bid and perform the work.
4. Submittals: Contractor shall prepare quality, accurate submittals, and material orders to perform the construction in a professional and competent manner. Submit all materials to COR. Long lead items shall be submitted within 5 days of NTP. All items, accessories and options shall be clearly marked on the submittal, along with any specified codes/standards. Whenever possible, accessories shall be provided from the fixture manufacturer. Submittals shall indicate the suitable fixture/materials for each location. Contractor shall field verify each installation/location prior to bid, submittals, and ordering materials. Submit a sample of the custom stainless steel shower wall-plate. All materials will be for use in wet areas.
5. Contractual Provisions: This SOW shall be considered as the most specific requirement for this project and shall quash any conflicting requirement(s) or terms. When the requirements/terms of the contract do not directly conflict, that provision shall be considered as an additional requirement.
6. High Temp (170-180 degrees): Materials shall be selected to meet the high temperature requirements
(170-180 degrees) for thermal eradiation system flushing. Fixtures in the Reference Equipment Sheets basis of design were selected with this in mind. In addition, any accessories or options shall also meet this requirement. For this reason, rubber and PVC (including tube liners) are not permitted. Stainless Steel tubing must have a non-toxic lining rated for greater than 170 degrees F.
7. IT Information Security: The Information Technology Certification and Accreditation requirements do not apply, and a Security Accreditation Package is not required.
8. Superintendent: The contractor shall appoint a qualified superintendent that shall be on-site during the performance of the work associated with this contract.
9. Coordination of Work / Minimize Impact: The contractor will coordinate all work with the VA COR to minimize the impact on medical center operations. Each week, the superintendent shall survey and coordinate future work with COR, providing a 2 to 3 week look-ahead review and appropriately addressing after-hours work, shutdowns, and any issues.
10. Safety: The contractor’s safety manager is responsible for safety inspections of all contract operations.
All VA and OSHA safety regulations shall be observed during the performance of work identified on this contract. Provide signage, barricades and infection control as required to maintain safety and protection around the project work site.
11. Infection Control: Provide and maintain infection control. If infection control precautions are not required by the policy/specification, such as work at locations/setups lasting less than a shift and not producing dust (such as typical faucet replacements), contractor shall close room doors, provide a scrubber.
12. Parking: The Contractor will have one designated parking location. Working materials should be contained in this authorized truck/van. Drivers should be particularly concerned with pedestrian traffic, yielding to pedestrians. Seat Belt use is mandatory on all VA grounds.
13. Cleaning: After installing of each fixture, Contractor shall clean the room, leaving it in an orderly condition, hospital clean and ready for use or patient treatment. VA will terminally clean Surgical, PACU, SICU and MICU areas after the contractor’s work and cleaning is complete. The Contractor shall always keep the work area, including any areas where materials and/or equipment is being stored, free from accumulations of waste materials. Before completing the work, the Contractor shall remove from the work and premises any rubbish, tools, equipment, and materials that are not the property of the Government.
14. Staging/Storage: An office, storage building, Connex or staging area is not authorized for this project.
Materials and construction items must be limited to on-site useable amounts and what may be contained in an authorized/parked workman’s truck/van.
15. Demo / Removal: When items or equipment, are shown to be demolished, remove and dispose of all materials and appurtenances. Do not leave any abandoned components or utility feeds. Remove utilities feeds back to the source or an active line, main, or main branch. Per the legionella directive, pipe shall be removed and cap within 2.5 pipe diameters by VA legionella. In-Wall Exceptions to Minimize Wall Repairs: When removing dead-ends, in-wall pipe can remain to minimize impact to wall/finishes, but the remainder of the piping shall be removed and capped close to the active line.
Hard wired electronic faucets shall be disconnected, wire removed to the active j-box above ceiling and a blank brushed stainless-steel cover-plate installed over the vacant box below the sink; In-wall conduit and box can remain.
16. Waste / Disposal: Disposal shall include all associated costs, such as handling, packaging, wrapping, container costs, and any offsite costs, such as transportation and disposal/dumping fees. The contractor is responsible for any byproducts of their construction (such as dust, runoff, leaks, stains, fumes, rubbish, waste) and any associated impact or costs. Once items/materials are removed/demolished, they are the contractor’s property and responsibility (unless noted otherwise).
17. Patch-Back & Restoration of Finishes: Patch back as necessary using materials to match the adjacent construction and finishes. When sink/lavatory or piping stub-outs are removed, patch holes and skim wall to level 3. Spot painting (touch-up) is not permitted. Electronically match existing paint and roll (prime and 2 base coats) from corner to corner. On walls with vinyl wallcovering, fill any wall screw holes with silicone. Match or complement wall color. Sealant and color selection shall be equal to Dow Corning 795 Silicone and 14 color selection charts. Coordinate color selections with COR prior to installation.
18. Normal Hours & After-hours Work and Work Productivity: Normal duty hours will be 7:00 am - 4:00 pm
Monday through Friday. No work shall be performed on federal holidays unless approved by COR. This project will require work to be performed outside of normal duty hours (after-hours) to minimize the impact on patients and Medical Center operations and must be coordinated with and approved by COR two (2) weeks in advance. Installation of fixtures in clinics, exam, treatment, emergency department, surgical areas, and PACU shall be performed after-hours. Installation of fixtures in wards, office and support areas can be performed during the normal duty hours, but progress will be slower. Shutdowns of mains or risers shall be performed after-hours. Based on previous fixture replacement projects during normal operational hours, 2 plumbers (2 crews) completed approximately 4 faucets and 1 shower per workday. Daytime plans were routinely altered due to room utilization and plumbers had to remain flexible, working with the COR to find available rooms each day. For fixture swap-outs, the facility will only be able to accommodate 2 plumbers (2 crews) during normal working hours and 3 crews after-hours. Contractor expectations for productivity/progress during normal working hours should be based on this real-world performance observed on the previous projects. Multiple shifts per day is not authorized for this project.
19. Shutdowns: Shutdowns of main lines and risers must be requested 3 weeks in advance (and performed after-hours). When draining the entire system, in addition to the time required for the installation (such as riser valves and/or injection ports), the contractor’s crew(s) shall be present while the system is drained (typically 2-3 hours) and refilled (typically 3-5 hours) with the contractor checking for leaks.
20. No Smoking: This is a smoke free facility. Contractor shall enforce the no smoking policy with his project staff. Smoking is not allowed on VA property, buildings, vehicles or grounds.
21. Identify Locations: To identify the location of a new valve or valve assembly (including biocide injection port assemblies), apply a blue-colored dot (1/4” or 3/8” water and UV resistant vinyl sticker) to the grid.
22. Final Inspection: 2 weeks in advance, request final inspection in writing to the CO and COR.
23. Warranty: All work shall be warranted for one (1) year.
BB. SPECIFIC TASKS AND ASSOCIATED DELIVERABLES
Description of Tasks and Associated Deliverables:
Contractor shall provide construction services within the specified period of performance in accordance with the statement of work and specifications including all documentation, schedules, submittals, coordination, certifications, test reports, training, warranties, manuals, etc. as specified in the contract documents. Work includes but is not limited to:
1. The contractor shall thoroughly investigate each identified room/location (see attachment) to select the appropriate fixture and components/accessories for each location. Prior to performing the work in a room, the contractor shall survey to identify and document issues, such as leaks, non-working stops/valves, clogged drain, or damage to the fixture and surrounding surfaces. Notify the COR and M&O of issues for correction before performing work at that location. If issues are not reported and documented prior to starting work at that location, any issues and resulting corrections will be the contractor’s responsibility.
2. Completely remove identified fixtures including any associated devices or accessories (such as connections, hoses, tubing, mixing valves, foot-pedals, mounts, automatic sensor electric devices, connections, surface mounted plastic boxes, cover-plates, transformers, solenoids, batteries, etc.). Patch back to match adjacent finishes. Thoroughly clean all surfaces exposed by fixture removal. Clean the mounting area, removing any gasket, sealant or putty material and water stains.
3. Faucet Replacement with New Mixing Valve:
a. Remove faucet and accessories. Remove any foot-pedals (patch back as necessary; see attachment for locations). For hardwired sensor faucets after wire is removed to the j-box above ceiling, in-wall electrical conduit and boxes can remain. Install new blank brushed stainless-steel electrical cover-plate.
b. Install the appropriate faucet arrangement with supply lines, mixing valves and trim in locations/rooms identified; Refer to the attachment and the Basis of Design Plumbing Fixture specification section for selection guidance; contractor shall field verify. The faucet mixing valve shall be firmly secured (mechanically fastened; no zip ties), so it is hidden behind the bowl.
Piping shall be neat with no visible excess. Provide chromed copper tubing from the wall stops to the mixing valve (run square). Install stainless steel flexible tubing from the mixing valve to the fixture with one loop. Excess flexible tubing shall be tucked neatly behind the bowl.
c. Trim-out sink fixture holes to ensure they are properly covered. Provide and install baseplate (deck-plate) as necessary. If unable to cover the sink/lav fixture holes with a baseplate, use a polished stainless-steel faucet hole cover with bolt and wingnut. Trim shall match fixture.
4. Shower Valve, Head & Wand Replacement
a. Replace shower valve, shower head, and handheld spray-head and hose. Install bracket/holder for spray-heads.
b. Remove tile, grout, and substrate / backer board sufficient to access and replace the shower valve. Contractor shall minimize the wall impact and hole size to create sufficient access for the replacement. Ensure grab bars and backer plates are not compromised. Close the wall opening using a custom brushed, stainless-steel cover-plate (14 gauge, 304, approximately 16x18).
Wall-plate shall be machined offsite by a professional metal fabricator/shop. The wall-plate shall be sized and punched/cut/machined to tightly accommodate valve. Edges shall be beveled and smooth with corners slightly rounded/eased. Tap existing studs or install sufficient solid backing on all 4 sides of the cutout with minimum 1” overlap. Backer shall be metal channel, firmly fastened and held in place before the wall—plate is installed. Fasten cover plate with appropriated sized stainless-steel anchors/toggles (minimum 3 per side) countersunk into cover plate. Provide a waterproof closed-cell gasket between the plate and wall to ensure the assembly is watertight.
5. Immediately after each installation, fixtures shall be thermostatically tested with a calibrated thermometer and documented. Adjust the mixing valve and re-test as required to achieve the VA temperature target of 102 to105 degrees Fahrenheit. Record location/room number, final temperature and sign/date certifying the work completing on the line item of the attachment.
6. While installing fixtures, the contractor will encounter wall stops and isolation valves that won’t not shutoff. To address broken/leaking valves when encountered in the normal course of fixture swap-outs, the contractor shall replace them at the following quantities: 60 wall stops and 60 fixture isolation valves.
7. Install 20 15 biocide injection port assemblies, to isolate 20 15 areas to facilitate future treatments/eradication. The COR will identify exact installation locations in the field to isolate areas such as a wards, ICUs, PACU, ER, clinics, etc. Work will be done after-hours, one area at a time, to minimize the impact on medical center operations. Each injection port assembly consists of ports on the hot-water and cold-water supplies with corresponding valves on the other end to isolate an area (see attached Biocide Injection Port detail, which represents one assemble).
8. Install balancing isolation valves at the base of risers noted below 6 risers:
a) 5 Valves in ACRE Building crawlspaces (1x6”, 1x8” on south end and 3x2” ball valve on North end),
b) 4 Valves on Main building third floor (4x6”) near room B-317 in hallway.
C. BASIS OF DESIGN REFERENCE EQUIPMENT
The basis of design salient characteristics of the fixture selections (faucets, showers, and mixing valves) are based on facility standards due to temperature and Legionella prevention requirements and are being provided to illustrate arrangements/configurations to assist the contractor with their fixture selections.
Fixtures/options/components/tubing shall be selected to meet the high temperature requirements (170-180 degrees) for thermal eradiation system flushing. Any fixture deviations/substitutions must be submitted in writing and accepted by the COR and CO prior to bid as part of the RFI process. Contractor shall provide brand name or equal. Any fixture deviations/substitutions must be submitted in writing and accepted by the COR as part of the performance submittal process. Refer to the specifications for additional information, which includes Reference Equipment Sheets.
1. T & S Bronze and Brass Works – Model B-1141-2VL15CR4
2. T & S Bronze and Brass Works – Model B-0890-CR-LF05 add outlet B-0199-08-LF15
3. T & S Bronze and Brass Works –Model B-2866-05CR-L15
4. T & S Bronze and Brass Works – Model B-2990 – BWH4CR add outlet B-0199-08-LF15
5. T & S Bronze and Brass Works – Model B-0231-CR4-L22
6. T & S Bronze and Brass Works – B-1122-XS-V22CR
7. T & S Bronze and Brass Works – Model BP-0300-CR-VF15
8. Shower - Provide additional options and accessories as required
Acorn Shower Valve SV16 (T/P Balancing Valve, ASSE 1016 compliant, self-contained cartridge, adjustable temp stops, ceramic shut-offs, integral check stops)
Acorn Showerhead LSH25 (only on some showers)
Acorn Handheld Spray Head HHC15 w/pause control (on wards showers) (submit sample)
HHSE Handheld Supply elbow (90 degree elbow at wall)
HHSH 60” stainless steel hose (submit sample)
IVB inline vacuum breaker (submit sample)
GR30 Glide Rail & holder (conceal existing slide bar screw holes). (Submit sample)
D. STATEMENT OF BID ITEMS:
1. BID ITEM NO. I (BASE BID): All work and items as indicated in this SOW.
2. BID ITEM NO.2 (DEDUCTIVE ALTERNATE A): Bid Items No. 1, minus all the shower replacements/work.
3. BID ITEM NO.3 (DEDUCTIVE ALTERNATE B): Bid Items No. 2, minus the installation of balancing isolation valves (6 total) at the base of risers.
E. CHANGES TO THE STATEMENT OF WORK
Any changes to this SOW must be authorized and approved through written modifications to the contract by the CO. Costs incurred by the contractor through the actions of parties other than the CO shall be borne by the contractor.
F. REPORTING REQUIREMENTS
1. Prior to work commencing the contractor shall provide the COR with a performance schedule and a schedule of values. The schedule of values (SOV) shall be a true representation of the work required. The schedule of values (SOV) line item total shall be based on the per unit install cost (including all mark-up).
2. The contractor shall provide a Daily Work Report (DWR) each day or the day after at the latest. The report must contain forces by trade, equipment, locations, and work performed, testing documentation/certification and any issues encountered. DWR’s shall be submitted electronically in a format agreed upon by the contractor and COR.
3. The superintendent shall also provide a copy of the updated report of installed unit counts/certifications/tests during the weekly coordination (look-ahead) survey with the COR.
4. Monthly payments will be based on the number of units installed, such as faucet/mixing valve, mixing valves, and shower units installed. The performance shall be updated with each pay application. Unit installation counts shall also be tracked in the contractor’s weekly installation report reports. If installation reports/certifications are not provided, the payment request will be rejected until the delinquent reports are provided.
G. CONTRACTOR EXPERIENCE AND PERSONNEL REQUIREMENTS
1. The contractor shall identify all employees that will be working under the awarded contract. Contractor personnel shall include employees, sub-contractors, suppliers, and delivery personnel entering the medical center. Those employees shall bring photo ID and social security card or passport to obtain a VA Contractor identification badge. The badge shall always be worn above the belt while on medical center property. The contractor’s employees shall return all I.D. badges to designated personnel at the end of the period of performance of the contract. Lost badges compromise security and will result in action, including removal and/or surcharge.
2. The contractor must inform the COR and the CO when personnel are removed from the contract for any reason.
3. If a key person becomes unavailable to complete the contract, the proposed substitutions of key personnel shall be made by the contractor in writing to the COR and CO for approval.
4. The COR may request contractor or contractor personnel to be removed from the site for violating VA Medical Center rules and regulations. The Contractor will provide a corrective action write-up on personnel removed that shall be approved by CO. Corrective action may include permanent removal of personnel from the premises.
5. Each plumbing crew (working in an area) must include a Master Plumber (licensed) to perform the
Plumbing installations.
H. CONFIDENTIALITY AND NONDISCLOSURE
1. The preliminary and final deliverables, and all associated working papers, application source code, and other material deemed relevant by VA which have been generated by the contractor in the performance of this contract, are the exclusive property of the U.S. Government and shall be submitted to the CO at the conclusion of the contract.
2. The CO will be the sole authorized official to release any data, draft deliverables, final deliverables, or any other written or printed materials pertaining to this contract. No information shall be released by the contractor. Any request for information relating to this contract, presented to the contractor, shall be submitted to the CO for a response.
3. Press releases, marketing material, or any other printed or electronic documentation related to this project, shall not be publicized without the written approval of the CO.