S02-Drawings - VA Louisville Replace Roofs Bldgs 8 and 21 - CD - 210720 - compressed.pdf
PDF 9 MB Posted
- Solicitation number
- 36C24921B0015
About this file
This document package includes construction drawings and specifications for a roof replacement project at the Robley Rex VA Medical Center in Louisville, Kentucky. The project involves demolishing and replacing the existing roof systems on Buildings 8 and 21, totaling approximately 5,900 square feet, including new roofing, flashings, drains, and other components. Drawings show the existing conditions, demolition plans, new roof plans, details, and notes. Specifications reference applicable codes and design requirements. The related federal contract opportunity pre-solicitation provides additional details on the planned procurement. The project value is estimated between $250,000 and $500,000, and will be awarded as a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. The solicitation is scheduled for release on or by October 6, 2021, to be conducted as a sealed bid in accordance with FAR Part 14. Bidders must be registered in SAM and verified in CVE to be eligible to participate. The work will be performed for the Department of Veterans Affairs Veterans Health Administration at the Robley Rex VA Medical Center in Louisville, Kentucky.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXTERIOR ELEVATION
INTERIOR ELEVATION
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
XX
X
1/A101
X
A101
XX
TOILET ACCESSORY TAGX SIGNAGE TAG
A101
SIM
X
E 1 0th
S t.
E. M arke t S t.
S pring S t.
M ockingbird
V alley R d.
Z orn A ve.River R d.
B lanke nba ker L n.
D
r. M
.L .K
Jr. E xp y
Frankfort Ave.
Brownsboro R d.
C henow eth Ln.
W estport R d.
E. Main St.
Story Ave.
E. Broadway
Shelbyville Rd.
B axte r A ve.
VAMC
800 Zorn Ave.
Ohio R ive r
Kosair Children's Hospital
Cave Hill Cemetery
Thurm an
Hutc hin
P ark
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Department of Veterans Affairs Medical Center
ARCHITECTURE PLANNING INTERIOR DESIGN
524 FERNWOOD AVENUE
ALTAMONTE SPRINGS, FLORIDA 32701
407.830.6522 P
937.461.0260 F
RDC / JOHN POE ARCHITECTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
SD SCHEMATIC DESIGN 03/12/2121
DD DESIGN DEVELOPMENT 05/07/2121
/2
/2
:1
:1
P
M
Replace Roofs Bldgs 8 and 21
07.01.2021
COVER SHEET
G001
TWMD
603-20-302
Louisville, KY
Replace Roofs Bldgs 8 and 21
800 Zorn Avenue Louisville, KY 40206 PROJECT #: 603-20-302
CONSTRUCTION
DOCUMENTS
21002.00
G001 COVER SHEET
A101 ROOF PLANS
A102 WIND LOAD PLAN
A201 ROOF DETAILS
A202 ROOF DETAILS
A301 EXISTING IMAGES
GENERAL CONSTRUCTION NOTES
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO
ORDERING, FABRICATING OR INSTALLING NEW MATERIALS.
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO BE INSTALLED AS
PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE SPECIAL PROVISIONS TO INSTALL
EQUIPMENT THAT IS TOO LARGE TO FIT THROUGH FINISHED OPENINGS.
8. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS SPECIFICALLY NOTED
OTHERWISE. IF NO FINISH IS INDICATED AT A PARTICULAR SURFACE, CONTRACTOR SHALL
PROVIDE FINISH(S) AS INDICATED AT SIMILAR CONDITIONS.
9. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL SYSTEMS WHICH COMPLY
WITH STATED CODES AND REGULATIONS. WHERE THE OMISSION OF A PART OR ELEMENT OF A
SYSTEM WOULD RESULT IN THE NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM,
CONTRACTOR SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
10. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED WALLS SHALL BE
SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF THE WALL.
* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE CONTRACTING OFFICER'S
REPRESENTATIVE (C.O.R.).
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE, INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF
VETERAN AFFAIRS, TECHNICAL INFORMATION LIBRRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST ARCHITECTURAL BARRIERS
ACT ACCESSIBILITY STANDARD (ABAAS) AND DEPARTMENT OF VETERANS AFFAIRS BARRIER
FREE DESIGN GUIDE PG-18-13 WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS
AFFAIRS TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT EXISTING
CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH ADJACENT EXISTING
SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT ARE DAMAGED DURING THE COURSE OF
DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF NEW WORK,
CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO REMAIN OR PROVIDE NEW
CONSTRUCTION TO MATCH EXISTING ADJACENT SURFACES TO REMAIN.
DRAWING INDEX
GRAPHIC SYMBOLS
N.T.S.Scale:
VICINITY MAP
Revisions Date
7.387.38
7.387.38
A201
A201
A201
A201
A201
A201
A201
A201
A201
A201
A201
A201
A201
HIGH
A201
LOW
A201
A201
HIGH
LOW
7.387.38
Slope 1/4" : 1'-0" Min.
Slope 1/4" : 1'-0" Min.
Slope 1/4" : 1'-0" Min.
7.087.08
7.07
7.057.05
7.07
7.05
7.077.07
7.05
7.057.05
7.06
5.10
5.10 5.19
A202
A202
A202
TYP.
TYP.
7.387.38
7.57
7.57
7.57
7.57
7.57
7.57
7.57
7.577.39 7.58
7.40
7.40
7.40
7.40
7.57
A202
7.397.39
7.40
7.407.40
7.39
5.10
7.06
7.58
A202
2.172.17
5.17
2.072.07
2.072.07
2.51 2.51
2.51
2.082.08
2.55
2.55
2.08
2.082.08
2.08
2.082.09 2.09
2.09 2.09
2.55
2.222.22
54' - 8 5/8" 25' - 3 3/8" 78' - 1 7/8"
158' - 2"
/4
"2.072.07
2.132.13
2.14
2.14
2.132.13
2.14
Typ.
2.05
Typ.
2.05 Typ.
2.08
2.16
2.172.17
2.23
2.23
2.062.06
2.062.06
Typ.
Typ.
2.192.19
2.20 2.212.21
A202
DC
A
B
BLDG 21 BLDG 8
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
SD SCHEMATIC DESIGN 03/12/2121
DD DESIGN DEVELOPMENT 05/07/2121
/2
/2
:1
:0
P
M
Replace Roofs Bldgs 8 and 21
07.01.2021
ROOF PLANS
A101
TWMD
603-20-302
Louisville, KY
CONSTRUCTION
DOCUMENTS
21002.00
NOTES
2.05 Existing lightning protection to remain, dismantle and
reassemble as required.
2.06 Existing wide flange structure to remain.
2.07 Remove existing built-up roofing and reglet flashing.
2.08 Existing drain to be removed.
2.09 Existing roof scupper to be removed.
2.13 Remove existing one piece reglet. Reglet receiver to remain.
2.14 Remove two piece reglet counter flashing. Reglet receiver to remain for reuse.
2.16 Existing sump.
2.17 Protect existing raised conduit in place.
2.19 Existing chillers mounted on existing steel platform.
2.20 Existing HVAC unit to remain.
2.21 Existing steel platform structural base.
2.22 Remove existing EPDM roof membrane.
2.23 Remove existing EPDM roof membrane over blocking and face of wall.
2.51 Remove existing capped piping & patch holes.
2.55 Remove existing access ladder and patch mounting holes.
5.10 New flat rung ladder w/ caged fall protection. Cage is at 6' - 9" above the bottom rung.
5.17 New crossover access ladder.
5.19 Hasp lockable security door.
7.05 Install new roof drain in same location of demolished roof drain.
Replace pipe with same size to nearest elbow.
7.06 Prefabricated asphalt plank roof walkway pads.
7.07 Install new roof drain scupper at existing location.
7.08 Replace existing roof drain down to elbow piping. Size to match existing. Verify in field.
7.38 Install new vapor barrier (base sheet), 3 1/2" min.
Polyisocyanurate insulation, 1/4" protection board, roofing membrane base sheet, and roofing membrane cap sheet.
7.39 New copper counterflashing installed in existing receiver.
7.40 Install new 2-piece reglet at bottom of stone cap.
7.57 Remove existing sealant at stone cap joints. Install new sealant and backer rod at all joints.
7.58 Extend roof membrane over blocking. Turn down face of wall.
Scale: 1/8" = 1'-0"1 New Work Roof Plan
Scale: 1/8" = 1'-0"2 Demo Roof Plan
A. Design wind speed (3-second gust): Vult = 120 MPH; (Vasd = 93
MPH)
B. Risk category: IV
C. Wind exposure: C
D. Internal pressure coefficient: enclosed building, GCpi = +/- 0.18
E. Deduct Alternate 1: Delete roof Area D from project scope.
F. Existing lightning protection system to remain. Remove and resinstall in same location as required for removal and installion of roof system.
GENERAL NOTES
Key Plan
Zone 1D (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -52.6 16.0 / -44.6 16.0 / -41.1
Zone 1D (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -31.6 9.6 / -26.8 9.6 / -24.7
Zone 2D (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -69.4 16.0 / -59.1 16.0 / -54.6
Zone 2D (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -41.6 9.6 / -35.5 9.6 / -32.8
Zone 3D (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -94.6 16.0 / -73.9 16.0 / -64.9
Zone 3D (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -56.8 9.6 / -44.3 9.6 / -38.9
3D
3D
3D
3D
2D
1D
3C
3C
3C
3C
Zone 1C (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -51.3 16.0 / -43.4 16.0 / -40.0
Zone 1C (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -30.8 9.6 / -26.0 9.6 / -24.0
Zone 2C (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -67.6 16.0 / -57.5 16.0 / -53.2
Zone 2C (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -40.6 9.6 / -34.5 9.6 / -31.9
Zone 3C (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -92.1 16.0 / -72.0 16.0 / -63.2
Zone 3C (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -55.3 9.6 / -43.2 9.6 / -37.9
1C 2C
2A3A 3A
2B3B 3B
Zone 2B (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -76.6 16.0 / -65.2 16.0 / -60.2
Zone 2B (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -46.0 9.6 / -39.1 9.6 / -36.1
Zone 3B (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -104.4 16.0 / -81.5 16.0 / -71.7
Zone 3B (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -62.6 9.6 / -48.9 9.6 / -43.0
Zone 3A (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -112.0 16.0 / -87.5 16.0 / -76.9
Zone 3A (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -67.2 9.6 / -52.5 9.6 / -46.1
Zone 2A (Ultimate Strength Design)
10 SF 50 SF 100 SF
16.0 / -82.2 16.0 / -69.9 16.0 / -64.6
Zone 2A (Allowable Stress Design)
10 SF 50 SF 100 SF
9.6 / -49.3 9.6 / -41.9 9.6 / -38.8
ROOF D ROOF C
R O
O F
A
A2021
A202
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
SD SCHEMATIC DESIGN 03/12/2121
DD DESIGN DEVELOPMENT 05/07/2121
/2
/2
:1
:0
P
M
Replace Roofs Bldgs 8 and 21
07.01.2021
WIND LOAD PLAN
A102
TWMD
603-20-302
Louisville, KY
CONSTRUCTION
DOCUMENTS
21002.00
N Scale: 1/8" = 1'-0"1 New Work Roof Wind Load Plan
NOTES
GENERAL PLAN NOTES
1. Roof replacement wind load - components and cladding Roof Design
Design wind speed (3-second gust): Vult = 120 MPH; (Vasd = 93 MPH) Risk category: IV Wind exposure: C Internal pressure coefficient: enclosed building, GCpi = +/- 0.18
5.31
7.93
6.36
6.27
5.27
5.30
5.29
7.36
7.09
6.09
7.35
7.16
2.11
2.03
5.27
6.09
7.09
7.35
7.36
7.92
7.95
7.94
7.65
5.29
7.96
5.40
5.29
2.04
2.03
2.12
7.16
2.11
6.09
7.09
7.35
7.36
7.95
7.92
7.94
5.29
7.96
5.32
3.32
7.65
2.03
2.12
2.11
7.16
5.26
7.65
5.28
7.29
5.27
6.27
7.91
7.09
6.09
2.11
7.36
7.35
7.16
2.03
5.27
2.11
6.09
7.09
7.36
7.92
7.95
7.94
5.29
7.96
5.32
3.32
7.65
7.16
7.35
6.09
7.09
7.35
7.36
7.60
7.95
7.94
7.65
2.11
7.37
7.65
7.37
2.11
6.09
7.09
7.65
5.35
5.38
7.24
7.91
7.99
2.11
6.09
7.09
7.24
7.91
5.34
5.33
5.35
5.36
7.65
7.65
7.16
2.11
6.09
7.24
7.91
1" Min.
A p p ro x
7.66
5.33
7.09
7.16
7.36
7.35
5.20
5.370
/4
7.09
7.35
7.36
4" Min. Flange
7.24
7.91
7.55
7.541" V.I.F. 1"
6.09
7.162.11
2.11
7.09
6.09
7.50
7.47
7.92
7.91
7.24
7.34
7.98
7.97 7.16
2.11
6.09
7.09
7.24
7.91
7.99
4.30
7.28
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
SD SCHEMATIC DESIGN 03/12/2121
DD DESIGN DEVELOPMENT 05/07/2121
/2
/2
:1
:0
P
M
Replace Roofs Bldgs 8 and 21
07.01.2021
ROOF DETAILS
A201
TWMD
603-20-302
Louisville, KY
CONSTRUCTION
DOCUMENTS
21002.00
Base Flashing at Parapet Wall with Metal Coping
Base Flashing with Sheet Metal Reglet at Wall Supported Deck
Base Flashing with Surface-Mounted Counterflashing at Wall
Embedded Edge Metal Flashing
Base Flashing at Wall
NOTES
2.03 Existing wall to remain.
2.04 Existing sheet-metal reglet to remain.
2.11 Existing roof decking to remain.
2.12 Existing stone coping.
3.32 Concrete fasteners.
4.30 Grout Solid.
5.20 Weatherproof sheet-metal pitch pan, soldered/welded (4" min.
height).
5.26 Aluminum 2 mm. (,078") gravel stop set in compatible roof cement, prime flange before stripping.
5.27 Continuous cleat.
5.28 Fasteners at 3" to 6" O.C., staggered.
5.29 Fasteners at 8" O.C.
5.30 Gasketed fasteners.
5.31 Sheet-metal parapet cap sloped to drain to roof.
5.32 Sheet-metal counterflashing.
5.33 Weatherproof sheet-metal rain collar with soldered/welded joints overlapping penetration pocket with appropriate sealant (E.G. Polyurethane).
5.34 Sheet-metal flashing.
5.35 Drawband.
5.36 Metal liner and insulation.
5.37 4" min. flange, set in compatible roof cement, prime flange before stripping (for factory-applied granule surfacing, the pipe flashing flange and membrane stripping can be installed between the base ply and granule-surfaced sheet).
5.38 Weatherproof sheet-metal rain collar overlapping flashing collar by 3 to 4"
5.40 Copper counterflashing.
6.09 1/4" Protection board.
6.27 Wood blocking.
6.36 Continuous shim.
7.09 3 1/2" thick Polyisocyanurate insulation. Taper as needed to achieve required slope.
7.16 Vapor retarder. Seal all joints and penetratons.
7.24 Compatible roof cement or compatible sealant at
penetration-to-membrane juncture.
7.28 Pourable sealant. Slope away from penetration.
7.29 Roof membrane.
7.34 Deck Clamp
7.35 Field membrane base sheet.
7.36 Field membrane cap sheet.
7.37 Exterior closure flange.
7.47 Clamping ring.
7.50 Drain strainer.
7.54 Top of flashing capped or rolled into pipe approximately 1".
7.55 Plumbing vent stack with soft metal pipe flashing.
7.60 Membrane flashing sheet adhered to backer, mop or
cold-applied (for roof systems with factory applied granule surfacing, the multiple-ply membrane flashing can be installed between the base ply and granule-surfaced sheet).
7.65 Sealant.
7.66 Pourable sealant.
7.91 Modified bitumen membrane stripping sheet - prime flange before stripping.
7.92 Modified bitumen membrane stripping sheet.
7.93 Continuous weatherproof membrane.
7.94 Fiber board cant.
7.95 Backer.
7.96 Seal top of flashing with a compatible vertical grade roof cement and reinforcement.
7.97 Membrane field plies, metal flashing and stripping sheet extend under clamping ring.
7.98 Drain bowl.
7.99 1/4" minimum clearance between flashing collar and support.
GENERAL NOTES
Base Flashing at Overflow Scupper
1. Roof replacement wind load - components and cladding Roof Design
Design wind speed (3-second gust): Vult = 120 MPH; (Vasd = 93 MPH) Risk category: IV Wind exposure: C Internal pressure coefficient: enclosed building, GCpi = +/- 0.18
Equipment Support Stand and Typical Rain Collar
Isolated Stack Flashing - Sheet Metal (Hot or Cold)
Penetration Pocket
Plumbing Vent
Roof Drain
Wide Flange Equipment Support Stand and Pitch Pocket
V .I
.F
/8
A201
A201
5.17
T y p
T y p
2'-1"
T y p
A201
5.10
5.19
6 1/2"
/4
(V
.I .F
T y p
2'-1"
T y p
A201
A201
/4
5.10
/4
(V
.I .F
T y p
2'-1"
T y p
V .I
.F
5.39
5.39
7.657.65
5.10
2.18
2.24
5.41 5.41
V .I
.F
E Q
E Q
E Q
M a x
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
SD SCHEMATIC DESIGN 03/12/2121
DD DESIGN DEVELOPMENT 05/07/2121
/2
/2
:1
:0
P
M
Replace Roofs Bldgs 8 and 21
07.01.2021
ROOF DETAILS
A202
ACMD
603-20-302
Louisville, KY
CONSTRUCTION
DOCUMENTS
21002.00
Scale: 1" = 1'-0"2 Ladder Parapet Detail
Scale: 1/2" = 1'-0"4 Ladder Section
NOTES
2.18 Concrete structural foundation. See A301 Existing Image #1.
2.24 Existing door to remain.
5.10 New flat rung ladder w/ caged fall protection. Cage is at 6' - 9" above the bottom rung.
5.17 New crossover access ladder.
5.19 Hasp lockable security door.
5.39 Attach new ladder to existing platform structural beam.
5.41 New aluminuml stair at door sill. Verify sill height and adjust stair rungs as required. Fasten stair to deck below.
7.65 Sealant.
GENERAL PLAN NOTES
1. Roof replacement wind load - components and cladding Roof Design
Design wind speed (3-second gust): Vult = 120 MPH; (Vasd = 93 MPH) Risk category: IV Wind exposure: C Internal pressure coefficient: enclosed building, GCpi = +/- 0.18
Scale: 1/2" = 1'-0"5 Ladder Section
Scale: 1/2" = 1'-0"3 Ladder Section
Scale: 1" = 1'-0"1 Stair Detail
A202
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
SD SCHEMATIC DESIGN 03/12/2121
DD DESIGN DEVELOPMENT 05/07/2121
/2
/2
:1
:1
P
M
Replace Roofs Bldgs 8 and 21
07.01.2021
EXISTING IMAGES
A301
ACMD
603-20-302
Louisville, KY
CONSTRUCTION
DOCUMENTS
21002.00
1. 4.2. 3. 5. 6.
7. 8. 9. 10. 11.
14.13.12.
C D
A
B
15.
A. Contractor is responsible to field verify all conditions and dimensions prior to ordering, fabricating or installing new materials.
B. The photos on this sheet have been provided as representative of the conditions on site and are not meant to be exhaustive documentation of all existing conditions. Contractor to field verify all existing conditionns and provide flashings, sealants, terminations, etc. as required for complete roof system.
GENERAL NOTES EXISTING IMAGES
| Sheets |
| G001 - COVER SHEET |
| A101 - ROOF PLANS |
| A102 - WIND LOAD PLAN |
| A201 - ROOF DETAILS |
| A202 - ROOF DETAILS |
| A301 - EXISTING IMAGES |