Bowling 3 year info Part 1.pdf
PDF 11 MB Posted
- Solicitation number
- 36C24920Q0261
About this file
This federal contract opportunity notice solicits proposals for preventive maintenance, inspection, testing, and arc flash studies of the electrical power distribution system at the Lexington VA Medical Center in Kentucky. Services are required for equipment at facilities on two campuses from August 15, 2020 through December 31, 2020.
The contractor will perform scheduled preventive maintenance, including inspection and testing of switchgear, transformers, generators, protective relays, grounding systems, and other electrical equipment. Additional requirements include infrared scanning, arc flash studies with labeling, and a 4-hour power outage test. The contractor must have qualified personnel, follow all applicable safety procedures, and submit written reports. Proposals are due by June 17, 2020 with award anticipated shortly thereafter. The contract will be fixed price and services must be completed by December 31, 2020.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bowling 3 year info Part 2.pdf | ||
| 36C24920Q0261 0002.docx | DOCX document | |
| 36C24920Q0261.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER PAGE
INFORMATION
This document contains proprietary information related to the Contracted
Inspection, Testing and Preventative Maintenance Services provided by Alset Power Grid, Inc. The unauthorized disclosure of this information may subject both the discloser and recipient of the information to contractual, civil, and/or criminal penalties as provided by law.
PROPRIETARY
VAMC Cooper Drive
Lexington, KY
November 7, 2017
Table Of Contents
PO #596C70187; Triennial Electrical Power
Inspection Services
I. TABLE OF CONTENTS
II. REPORT AND DEFICIENCIES
III. DESCRIPTION OF TEST
IV. LOW VOLTAGE CIRCUIT BREAKERS
V. MEDIUM VOLTAGE CIRCUIT BREAKERS
VI. PROTECTIVE RELAYS
VII. AIR SWITCHES
VIII. ATS’S, MCC’s
IX. OIL TRANSFORMER & FLUID REPORTS-WEIDMANN
X. GENERATOR FLUID REPORTS-OHIO CAT
XI. ARC FLASH, IR SCANNED PANELS
XII. MISC.
Total Electrical Protective System Reliability
513 Mill Ave. S.E. #111, New Philadelphia, OH 44663
1-330-795-3041 Email Address: ALSETPowergrid@msn.com
Department of VAMC (Cooper Drive) November 10, 2017
138 CD Electronics Shop
1101 Veterans Drive
Lexington, KY 40502
Attn: Mr. Herbert Sparks
Reference: PO #596C70187; Triennial Electrical Panel
Inspection Services
Dear Mr. Sparks, I. DESCRIPTION OF TESTS
The following is a description of tests and testing procedures intended for checking the insulation condition, basic electrical operation and/or timing parameters of the applicable equipment tested.
INSULATION RESISTANCE TESTING
In an Insulation resistance Test, voltage, from 100 to 5,000 Volts, supplied from a source of constant potential, is applied across the insulation (transformers, cables, circuit breakers, starters, motors, etc.). The usual potential is a megohmmeter, either hand or power operated, which indicates the insulation resistance directly on a scale calibrated in megohms. The quality of the insulation is evaluated based on the level of the insulation resistance.
DIELECTRIC ABSORPTION
In a Dielectric Absorption Test, a voltage, supplied from a source of constant potential, is applied across the insulation. The voltage is applied for an extended period of time, from 5 to 15 minutes, and periodic readings are taken of the insulation resistance or leakage current. The test data is evaluated on the basis that if insulation is in good condition, its apparent insulation resistance will increase as the test progresses.
POLARIZATION INDEX
The Polarization Index is a specialized application of the dielectric absorption test. The index is usually the ratio of insulation resistance at ten minutes to the insulation resistance at one minute. The use of PI Testing is usually confined to rotating machines, cables and transformers (on this particular job-only the 4160V motors.
HIGH POTENTIAL TESTING
A High Potential Test consists of applying voltage across insulation at or above the DC equivalent of the 60HZ operating crest voltage. This test can be applied either as a dielectric absorption test or a step-voltage test.
When applied as a step-voltage test, the maximum voltage is applied in a number of equal intervals of time. The time interval between steps should be long enough to allow the leakage current to reach stability, approximately one or two minutes. A leakage current reading is taken at the end of each interval before the voltage is raised to the next level. A linear increase in leakage current is expected and it should stabilize of decrease from the initial value at each step. A nonlinear increase in leakage current may indicate imminent failure and the test should be discontinued. This test was only applied to the systems' main buses; no cables were hi-potted.
INSULATION POWER FACTOR TESTING
The power factor of insulation is the cosine of the angle between the charging current vector and the impressed voltage vector when the insulation system is energized with an AC voltage. In other words, it is a measure of the energy component of the charging current. The term "Power Factor Testing" means any testing performed in order to determine the power factor of an insulation system. Power factor testing is a useful tool in evaluating the quality of insulation in power, distribution and instrument transformers, circuit breakers, rotating machines, cables, regulators and insulating liquids.
On transformer tests, the power factor of (1) each winding with respect to ground and (2) each winding with respect to each other winding should be obtained. In addition, tests should be made of each bushing with a rated voltage above 600 volts, either using the power factor or capacitance tap if the bushing is so equipped or by use of a "Hot-
Collar" test using a test electrode around the outside shell of the bushing.
Evaluation of the data obtained should be based on (1) industry standards for the particular type of equipment tested, (2) correlation of data obtained with test data from other similar units tested, and (3) comparison of data with previous test data on the same equipment.
PROTECTIVE DEVICE TESTING
FUSES - There is no way to test the operation of fuses on a system since this type of device destroys itself while performing its protective function. The only test that can be performed on a fuse in the field is a continuity test to determine whether or not the fuse has "blown".
LOW VOLTAGE CIRCUIT BREAKERS, GENERAL - Low voltage circuit breakers can generally be divided into tow categories depending upon the applicable industry design standards, molded case circuit breakers and low voltage power circuit breakers.
When testing circuit breaker tripping characteristics, it is recommended that the overcurrent tests be performed on individual poles at 300 percent of rated current. The reaction of the circuit breaker to this overload is indicative of its reaction throughout its entire overcurrent tripping range. This load is chosen as the test point because it is relatively easy to generate the required current in the field and the wattage per pole from line to load is large enough, so the dissipation of heat in the nonactive pole spaces is minor and does not affect the test results appreciably.
The testing of electromechanical trip devices or solid-state devices by the primary injection method requires the use of a high current test set capable of producing sufficient current at low voltage to operate each of the elements of the trip device. This test must have means of adjusting the amount of current applied to the trip device and a cycle and second timer to measure the amount of time to trip the breaker at each current setting. At least one test should be made in the range of each element of the trip device. The long time delay element should ordinarily be tested at approximately 300 percent of its setting.
The short time delay element should be tested at 150 percent to 200 percent of its setting.
The instantaneous element should be tested to assure that it does not operate at too low a current level, yet will operate at the proper level. For the test of the instantaneous element, the applied current must be symmetrical without an asymmetrical offset or random errors will be introduced.
CONTACT RESISTANCE TESTING
This test is used to test the quality of the contacts on switches and circuit breakers.
A test set designed for this purpose is available with direct scale calibration in microhms, capable of reading contact resistances of 10 microhms or less.
The contact resistance should be kept as low as possible to reduce power losses at the contacts with the resultant localized heating, which will shorten the life of both contacts and nearby insulation.
PROTECTIVE RELAY TESTING
Protective relays are used in conjunction with medium voltage circuit breakers
(above 600 volts) to sense an abnormality and cause the trouble to be isolated with minimum disturbance to the electrical system and with the least damage to the equipment at fault. They have the accuracy and sophistication demanded by the protective requirements of the primary feeder circuits and larger electrical equipment. Protective relays designed to be responsive to an abnormal excursion in current voltage, frequency, phase-angle, direction of current or power flow, etc., and with varying operation characteristics are commercial available. Each relay application requires custom engineering to satisfy the parameters of its particular intended function in the system.
TRANSFORMER TURNS RATIO AND POLARITY TESTS
The Turns Ratio Test is used to determine the number of turns in one winding of a transformer in relation to the number of turns in the other windings of the same phase of the transformer. The Polarity Test determines the vectoral relationships of the various transformer windings.
This test is useful in determining whether a transformer has any shorted turns or improper connections and, on acceptance testing, to verify nameplate information.
ULTRASONIC (CORONA DETECTION) TESTS
Perform Ultrasonic Testing on main switchgear bus and circuit breaker elements and lightning arrestors to test for corona and leaking lightning and surge arrestors.
INFRA-RED SURVEY
The infrared scanner is an instrument that provides a real-time television like image on the natural infrared energy being emitted from objects within its field of view.
This is in contrast to infrared thermometer-type devices, which view a point or single line. Infrared scanners are not cameras; they do not use infrared film. They work because any object at its temperature above absolute zero is radiating energy proportional to its temperature, and these scanners contain detector material sensitive to infrared energy.
Applied to electrical power distribution systems, infrared scanning is one of the few tests that can be performed while the system is energized and under load to determine if weaknesses exist that could lead to power failures and "surprise" electrical outages.
The above tests were performed in accordance with standard testing procedures, and calibrated testing instruments.
Sincerely yours, ALSET Power Grid, Inc.
Larry A. Wise Larry A. Wise, Field Engineer
Location LEXINGTON, KY (COOPER DRIVE
Equip Desig SBA-5
Date 10/28/2017
Tested By LAW
MSR LVB-001
Manufacturer GE
Frame Size 600
Circuit ID BRKR 5 MACH RM
Type AKU-2A-25-1
Sensor Size 300
IC 25000
1C 3 1C 3
3C INT 3C INT
N/A N/A N/A N/A
10X 10X
109 110
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
300% 36.3 36.3 36.3
150% 0.27 0.27 0.27
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type MICRO VERSA TRIP
Rating Plug N/A
Trip Unit # TA9VT20SLA1
SENS
SENS
SENS
BAND
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
B
Customer VAMC
Equip Desig SBG
Date 10/28/2017
Tested By LAW
MSR LVB-002
Manufacturer GE
Frame Size 1600
Circuit ID SBG 1 SOUTH WING
Type AK-2A-50-1
Sensor Size 1600
IC 50000
1.0 3 1.0 20
3 MAX 3 MAX
N/A N/A N/A N/A
3 3
32 41
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 29.9 29.9 29.9
150% 0.44 0.44 0.44
N/A N/A N/A N/A
N/A N/A N/A
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type GE
Rating Plug 600
Trip Unit # PRO TRIP
SENS
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBA-1
Date 10/28/2017
Tested By LAW
MSR LVB-004
Manufacturer GE
Frame Size 3000
Circuit ID MAIN
Type AK-3A-75
Sensor Size 3000
IC 65000
0.7 2.5 0.7 2.5
2.5 0.2 2.5 0.2
N/A N/A N/A N/A
N/A N/A
21 23
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 2.8 2.8 2.8
150% 0.229 0.229 0.229
N/A N/A N/A N/A
N/A N/A N/A
Status PASSED
Comments DIP SWITCH-SLI-8 SETTING=1,2,4,5,6,7,8 ON. 3 OFF
DIP SWITCH-SSI-8 SETTING=1,2,3,4,6,8 ON. 5,7 OFF
DIP SWITCH-SGI-8 SETTING=1 THRU 8 OFF
DIP SWITCH-SII-8 SETTING=1 THRU 8 OFF
Voltage Rating 600
Trip Unit Type MULTILIN
Rating Plug N/A
Trip Unit # FB600E
SENS
SENS
SEC.
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SEC.
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBA-2
Date 10/28/2017
Tested By LAW
MSR LVB-005
Manufacturer GE
Frame Size 1600
Circuit ID BRKR 2 SHOP
Type AKU-2A-50-1
Sensor Size 400
IC 50000
0.5 10 0.5 10
10 2 10 2
N/A N/A N/A
6 6
132 135
MEG-OHMS
2000 2000 SS
2000 2000 SS
2000 2000 SS
600% 18.76 18.76 18.76
150% 0.12 0.12 0.12
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type MULTILIN
Rating Plug N/A
Trip Unit # FB600
SENS
SEC.
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SEC.
BAND
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBB-1
Date 10/28/2017
Tested By LAW
MSR LVB-006
Manufacturer GE
Frame Size 3000
Circuit ID BRKR 1 MAIN
Type AKU-2A-75-1
Sensor Size 2000
IC 65000
2000 1 2000 1
4000 2 4000 2
N/A N/A N/A N/A
N/A N/A
28 27
MEG-OHMS
1000 1000 1000
1000 1000 1000
1000 1000 1000
300% 36.97 35.34 35.10
150% 0.58 0.63 0.73
N/A N/A N/A N/A
N/A N/A N/A
Status RETROFIT
Comments RECOMMEND RETROFITTING TO SOLID STATE. UNIT HAS OLD
OBSOLETE ELECTOR-MECHANICAL TRIP DEVICES.
Voltage Rating 600
Trip Unit Type G.E. EC-1B
Rating Plug 1CC-2CC
Trip Unit # 177L226DAG-30
SENS
SENS
SEC.
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SEC.
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
D
Equip Desig SBB-2
Date 10/28/2017
Tested By LAW
MSR LVB-007
Manufacturer GE
Frame Size 1600
Circuit ID BRKR 2 Radiology
Type AKU-2A-50-1
Sensor Size 600
IC 50000
0.5 3 0.5 3
1.5 INT 1200 INT
N/A N/A N/A N/A
1.5 1.5
47 45
MEG-OHMS
1000 1000 1000
1000 1000 1000
1000 1000 1000
600% 35.11 35.11 35.11
150% 0.2 0.2 0.2
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type G.E.
Rating Plug 1600
Trip Unit # PRO TRIP
SENS
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBB-3
Date 10/28/2017
Tested By LAW
MSR LVB-008
Manufacturer GE
Frame Size 1600
Circuit ID BRKR 3 PATHOLOGY
Type AK-2A-50-1
Sensor Size 800
IC 50000
.5 20 .5 20
3 0.15 3 0.15
N/A N/A N/A N/A
10 10
39 35
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 23.05 23.05 23.05
150% 0.2 0.2 0.2
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type MULTILIN
Rating Plug NA
Trip Unit # FB600E
SENS
SENS
SENS
SEC.
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
SEC.
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBB-4
Date 10/28/2017
Tested By LAW
MSR LVB-009
Manufacturer GE
Frame Size 1600
Circuit ID BRKR 4 DIST BD
Type AK-2A-50-1
Sensor Size 800
IC 50000
1.15 12.5 1.15 12.5
2.5 0.4 2.5 0.4
N/A N/A N/A N/A
N/A N/A
43 40
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
300% 33.88 32.78 34.16
150% 0.42 0.42 0.42
N/A N/A N/A N/A
N/A N/A N/A
Status PASSED
Comments DIP SWITCH-SLI-8 SETTING 2,5,6,8 ON. 1,3,4,7 OFF.
DIP SWITCH-SSI-8 SETTING 1,2,3,4,7,8 ON. 5,6 OFF.
DIP SWITCH-SII-8 SETTING 1,2,3 ON. 4,5,6,7,8 OFF.
Voltage Rating 600
Trip Unit Type MULTILIN
Rating Plug N/A
Trip Unit # FB600
SENS
SENS
SEC.
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SEC.
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBB-5
Date 10/28/2017
Tested By LAW
MSR LVB-010
Manufacturer GE
Frame Size 1600
Circuit ID BRKR 5 KITCHEN
Type AKU-2A-50-1
Sensor Size 400
IC 50000
560 N/A 560 N/A
2000 N/A 2000 N/A
N/A N/A N/A N/A
N/A N/A
80 76
MEG-OHMS
100 100 100
100 100 100
100 100 100
300% 107.24 102.34 97.73
150% 0.238 0.29 0.229
N/A N/A N/A N/A
N/A N/A N/A
Status RETROFIT
Comments RECOMMEND RETROFITTING TO SOLID STATE. UNIT HAS OLD
OBSOLETE ELECTOR-MECHANICAL TRIP DEVICES.
Voltage Rating 600
Trip Unit Type G.E. EC-1
Rating Plug 1A-2C
Trip Unit # 238U685G1-EG
SENS
SENS
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBC-4
Date 10/1/2017
Tested By LAW
MSR LVB-012
Manufacturer GE
Frame Size 600
Circuit ID BRKR 4 RES PATH
Type AK-2A-25-1
Sensor Size 300
IC 25000
0.7 20 0.7 20
4 0.2 0.2 0.2
N/A N/A N/A N/A
N/A N/A
107 161
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 20.59 20.59 20.59
150% 0.258 0.258 0.258
N/A N/A N/A N/A
N/A N/A N/A
Status PASSED
Comments Replace due to age, the obsolence availabilty parts.
DIP SWITCH-SLI-8 SETTING=1,2,4,8 ON. 3,5,6,7 OFF
DIP SWITCH-SSI-8 SETTING=3,4,6,8 ON. 1,2,5,7 OFF
DIP SWITCH-SII-8 SETTING=1,2 ON. 3,4,5,6,7,8 OFF
Voltage Rating 600
Trip Unit Type MULTILIN
Rating Plug N/A
Trip Unit # FB600
SENS
SENS
SEC.
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SEC.
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBC-5
Date 10/1/2017
Tested By LAW
MSR LVB-013
Manufacturer GE
Frame Size 600
Circuit ID BRKR 5 PATH LAB
Type AK-2A-25-1
Sensor Size 600
IC 25000
0.5 20 0.5 20
3 0.2 3 0.2
N/A N/A N/A N/A
N/A N/A
15 70
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 18.2 18.25 18.79
150% 0.21 0.21 0.21
N/A N/A N/A N/A
N/A N/A N/A
Status PASSED
Comments Replace due to age, the obsolence availabilty parts.
DIP SWITCH-SLI-8 SETTING=1,2,3,4,8 ON. 5,6,7 OFF
DIP SWITCH-SSI-8 SETTING=2,3,4,6,8 ON. 1,5,7 OFF
DIP SWITCH-SII-8 SETTING=1,3 ON. 2,4,5,6,7,8 OFF
TRIP BUTTON STICKS, NEEDED WORK TO RESET & CLOSE.
Voltage Rating 600
Trip Unit Type MULTILIN
Rating Plug NA
Trip Unit # FB600
SENS
SENS
SEC.
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SEC.
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBB-6
Date 10/28/2017
Tested By LAW
MSR LVB-014
Manufacturer GE
Frame Size 600
Circuit ID BRKR 6, RM CLOSE
Type AKU-7A-25-1
Sensor Size 300
IC 200000
1.1 3 1.1 3
N/A N/A N/A N/A
N/A N/A N/A N/A
10 10
155 172
MEG-OHMS
100 100 100
100 100 100
100 100 100
600% 11.42 11.42 11.42
N/A N/A N/A N/A
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments 1200 AMPTRAP, TYPE BG, IC 200,000 A.
Voltage Rating 600
Trip Unit Type MICRO VERSA TRIP
Rating Plug 150
Trip Unit # RMS-9
SENS
SENS
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBC-3
Date 10/1/2017
Tested By LAW
MSR LVB-015
Manufacturer GE
Frame Size 1600
Circuit ID BRKR 3 CRIT RIS
Type AKU-2A-50
Sensor Size 1600
IC 50000
0.8X 2 0.8X 2
4C MAX 4C MAX
N/A N/A N/A N/A
15X 15X
36 30
MEG-OHMS
1000 175 460
290 1450 250
560 855 559
600% 5.72 5.72 5.72
150% 0.39 0.39 0.39
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments NEW REBUILT.
Voltage Rating 600
Trip Unit Type MICRO VERSA TRIP
Rating Plug 150
Trip Unit # RMS-9
SENS
SENS
SENS
BAND
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBC-2
Date 10/1/2017
Tested By LAW
MSR LVB-016
Manufacturer GE
Frame Size 1600
Circuit ID BRKR 2 SERV RM (MCC)
Type AK-2A-50-1
Sensor Size 800
IC 50000
0.6 15 0.6 15
5 0.2 0.2 N/A
N/A N/A N/A N/A
N/A N/A
42 50
MEG-OHMS
705 678 750
285 532 341
511 705 486
600% 12.914 12.914 12.914
150% 0.3 0.28 0.27
N/A N/A N/A N/A
N/A N/A N/A
Status PASSED
Comments DIP SWITCH-SLI-8 SETTING=1,3,4,6,8 ON; 2,5,7 OFF.
DIP SWITCH-SSI-8 SETTING=2,4,6,8 ON; 1,3,5,7 OFF.
DIP SWITCH-SII-8 SETTING=INST. AND GF DISABLED.
Voltage Rating 600
Trip Unit Type MULTILIN
Rating Plug N/A
Trip Unit # FB600E
SENS
SENS
SEC.
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SEC.
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBD-1
Date 10/28/2017
Tested By LAW
MSR LVB-017
Manufacturer GE
Frame Size 1600
Circuit ID SBD BRKR 1 CRITICAL
Type AKU-2A-50-1
Sensor Size 1600
IC 50000
E TB#4 E TB#4
3 TB#2 3 TB#2
N/A N/A N/A N/A
N/A N/A
58 53
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
300% 2.24 2 2
150% 0.5 0.5 0.5
N/A N/A N/A N/A
N/A N/A N/A
Status RETROFIT
Comments BREAKER WOULD NOT RECLOSE. TRIP BAR & ROLLERS NEEDED
LUBRICATION. RECOMMEND RETROFITTING THE OBSELETE LTS TRIP
BOX & ACTUATOR.
Voltage Rating 600
Trip Unit Type SIEMENS LTS
Rating Plug N/A
Trip Unit # 2010-6-4
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBD-2
Date 10/28/2017
Tested By LAW
MSR LVB-018
Manufacturer GE
Frame Size 1600
Circuit ID SBD BRKR 2 EMERG.
Type AKU-2A-50-1
Sensor Size 1600
IC 50000
B TB#3 B TB#3
3 TB#2 3 TB#2
N/A N/A N/A N/A
N/A N/A
37 43
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 3 3 3
150% 0.26 0.26 0.26
N/A N/A N/A N/A
N/A N/A N/A
Status RETROFIT
Comments BREAKER WOULD NOT RECLOSE. TRIP BAR & ROLLERS NEEDED
LUBRICATION. RECOMMEND RETROFITTING THE OBSELETE LTS TRIP
BOX & ACTUATOR.
Voltage Rating 600
Trip Unit Type SIEMENS LTS
Rating Plug N/A
Trip Unit # 2010-6-3
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBE-2
Date 10/1/2017
Tested By LAW
MSR LVB-019
Manufacturer GE
Frame Size 1600
Circuit ID BRKR 2 EMRG RIS
Type AKU-2A-50
Sensor Size 1600
IC 50000
0.8X 2 0.8X 2
7C MAX 7C MAX
N/A N/A N/A N/A
15 15
32 31
MEG-OHMS
775 320 220
420 520 1240
960 1240 480
600% 5.72 5.72 5.72
150% 0.39 0.39 0.39
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments New Rebuilt. Trip Flags do not pop out.
Voltage Rating 600
Trip Unit Type MICRO VERSA TRIP
Rating Plug 150
Trip Unit # RMS-9
SENS
SENS
SENS
BAND
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBE-3
Date 10/1/2017
Tested By LAW
MSR LVB-020
Manufacturer GE
Frame Size 600
Circuit ID SBE 3, HEMG-1
Type AKU-2A-25-1
Sensor Size 1100
IC 25000
160 30-90 160 30-90
600 N/A 600 N/A
N/A N/A N/A N/A
0 0
266 298
MEG-OHMS
1486 2000 2000
2000 2000 1200
2000 1500 2000
300% 200.43 N/A N/A
150% 0.16 0.17 N/A
N/A N/A N/A N/A
N/A N/A N/A
Status RETROFIT
Comments REPLACE TRIP DEVICES, RETROFIT TRIP DEVICES TO SOLID STATE.
Voltage Rating 600
Trip Unit Type G.E. EC-1
Rating Plug 1A-2C
Trip Unit # 238U685G1-LF
SENS
SENS
SENS
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBE-4
Date 10/1/2017
Tested By LAW
MSR LVB-021
Manufacturer GE
Frame Size 600
Circuit ID BRKR 4 RAD FAN & HEMG EMRG
Type AKU-2A-25-1
Sensor Size 200
IC 30000
1.0 3 1.0 3
4C MIN N/A N/A
N/A N/A N/A N/A
10X 10X
182 142
MEG-OHMS
2000 200 500
2000 300 280
2000 500 1160
600% 16.4 16.4 16.4
150% 0.14 0.14 0.14
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type MICRO VERSA TRIP
Rating Plug N/A
Trip Unit # TA9VT20SLA1
SENS
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBA-3
Date 10/28/2017
Tested By LAW
MSR LVB-022
Manufacturer GE
Frame Size 600
Circuit ID BRKR 3 PENTHOUSE
Type AK-2A-25-1
Sensor Size 600
IC 30000
.5 20 .5 20
2.5 0.15 2.5 0.15
N/A N/A N/A N/A
N/A N/A
120 128
MEG-OHMS
100 100 100
100 100 100
100 100 100
600% 17.76 17.76 17.76
150% 0.22 0.22 0.22
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments TRIP FLAGS DAMAGED. RECOMMEND RETROFIT TO NEW SOLID STATE
Voltage Rating 600
Trip Unit Type MULTILIN
Rating Plug N/A
Trip Unit # FB600
SENS
SENS
SENS
SEC.
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
SEC.
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBF-1
Date 10/28/2017
Tested By LAW
MSR LVB-023
Manufacturer GE
Frame Size 1600
Circuit ID NORTH WING RISR
Type AKU-2A-50-1
Sensor Size 1200
IC 50000
960 10-40 960 10-40
2C N/A 2C N/A
N/A N/A N/A N/A
N/A N/A
38 37
MEG-OHMS
100 100 100
100 100 100
100 100 100
200% 25.43 27.82 27.99
150% 0.18 0.15 0.12
N/A N/A N/A N/A
N/A N/A N/A
Status RETROFIT
Comments RECOMMEND RETROFITTING TO SOLID STATE. UNIT HAS OLD
OBSOLETE ELECTOR-MECHANICAL TRIP DEVICES.
Voltage Rating 600
Trip Unit Type G.E. EC-1
Rating Plug 1C-2C-3
Trip Unit # 238U685G2-AG
SENS
SENS
SEC.
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SEC.
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBA
Date 10/28/2017
Tested By LAW
MSR LVB-024
Manufacturer GE
Frame Size 1600
Circuit ID PANEL DPLS
Type AKS-10A-50
Sensor Size 1600
IC 50000
.5 N/A .5 N/A
9 N/A 9 N/A
N/A N/A N/A N/A
1.5 1.5
37 35
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
300% 4.0 4.0 4.0
150% 0.3 0.3 .3
N/A N/A N/A N/A
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type MUTPLUS
Rating Plug N/A
Trip Unit # LSI
SENS
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig SBH-1
Date 10/28/2017
Tested By LAW
MSR LVB-025
Manufacturer GE
Frame Size 1600
Circuit ID BLD POWER RISER
Type AKU-2A-50-1
Sensor Size 1200
IC 50000
1920 50-150 1920 50-150
8400 N/A 8400 N/A
N/A N/A N/A N/A
N/A N/A
64 88
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 43.1 43.1 43.1
150% 0.14 0.17 0.2
N/A N/A N/A N/A
N/A N/A N/A
Status RETROFIT
Comments RECOMMEND RETROFITTING TO SOLID STATE. UNIT HAS OLD
OBSOLETE ELECTOR-MECHANICAL TRIP DEVICES.
Voltage Rating 600
Trip Unit Type G.E. EC-1
Rating Plug 1A-2C
Trip Unit # 238U685G1-BG
N/A
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
N/A
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig CHILLER PLANT
Date 9/7/2017
Tested By LAW
MSR LVB-027
Manufacturer SIEMENS
Frame Size 3200
Circuit ID SEC MAIN T-8
Type RL-3200
Sensor Size 3200
IC 75000
B 3 B 3
3 MAX 3 MAX
25% MIN 25% MIN
N/A N/A
34 34
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 4.75 4.75 4.75
150% 0.45 0.45 0.45
150% .20 .20 .20
N/A N/A N/A
Status PASSED
Comments Electric Open-Close Switch and Ammeters inoperative.
Voltage Rating 600
Trip Unit Type STATICTRIP II (TSG)
Rating Plug N/A
Trip Unit # R-77295B-3
SENS
SENS
SENS
BAND
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 9/7/2017
Tested By LAW
MSR LVB-028
Manufacturer SIEMENS
Frame Size 1600
Circuit ID SPARE T-8
Type RLX-1600
Sensor Size 1000
IC 50000
A 1 A 1
N/A N/A N/A N/A
25% MAX 25% MAX
12 12
187 173
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 1.17 1.17 1.17
N/A N/A N/A N/A
150% 0.45 0.45 0.45
SAT SAT SAT
Status PASSED
Comments LT and GF TESTS WERE SUCCESSFUL BUT THE LT and GF INDICATORS
DID NOT POP OUT.
Voltage Rating 600
Trip Unit Type STATICTRIP II (TIG)
Rating Plug N/A
Trip Unit # R-77296A-2
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 9/7/2017
Tested By LAW
MSR LVB-029
Manufacturer SIEMENS
Frame Size 1600
Circuit ID MCC2 T-8
Type RLX-1600
Sensor Size 1600
IC 50000
C 3 C 3
NA NA NA NA
15% INT 15% INT
3 3
32 32
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 5.83 5.83 5.83
NA NA NA NA
150% .26 .26 .26
SAT SAT SAT
Status PASSED
Comments TRIPPED SATISFACTORY, GF FAULT INDICATORS DID NOT POP OUT.
Voltage Rating 600
Trip Unit Type STATICTRIP II (TSG)
Rating Plug N/A
Trip Unit # R-77296C-2
SENS
SENS
SENS
BAND
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 9/7/2017
Tested By LAW
MSR LVB-030
Manufacturer SIEMENS
Frame Size 1600
Circuit ID MCC-2 T-8
Type RLX-1600
Sensor Size 1600
IC 50000
A 3 A 3
4 MIN 4 MIN
15% MIN 15% INT
5 5
24 31
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 1.37 1.37 1.37
150% .07 .07 .07
150% .09 .09 .09
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type STATICTRIP II (TIG)
Rating Plug N/A
Trip Unit # R-77296B-3
SENS
SENS
SENS
BAND
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 9/7/2017
Tested By LAW
MSR LVB-031
Manufacturer SIEMENS
Frame Size 3200
Circuit ID TIE
Type RL-3200
Sensor Size 3200
IC 75000
E 3 E 3
3 MAX 5 MAX
25% MAX 25% MAX
NA NA
49 52
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 2.36 2.36 2.36
150% .43 .43 .43
150% .43 .43 .43
N/A N/A N/A
Status PASSED
Comments Charging Motor Toggle Switch is defective recommend replacing the switch.
Voltage Rating 600
Trip Unit Type STATICTRIP II (TSG)
Rating Plug N/A
Trip Unit # R-77295A-2
SENS
SENS
BAND
BAND
BAND
SEC
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC
SEC
SEC
SEC
SEC
SEC
SEC
SEC
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 9/7/2017
Tested By LAW
MSR LVB-032
Manufacturer SIEMENS
Frame Size 1600
Circuit ID SPARE T-7
Type RLX-1600
Sensor Size 1000
IC 50000
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A
30 28
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A
Status FAILED
Comments NO TRIP DEVICE ON THE CIRCUIT BREAKER ELEMENT.
BEFORE USING INSTALL A TRIP DEVICE & RESET.
Voltage Rating 600
Trip Unit Type NONE INSTALLED
Rating Plug N/A
Trip Unit # NONE INSTALLED
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
X
X
X
X
Pick-Up Delay
SEN ----
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
F
Date 9/7/2017
Tested By LAW
MSR LVB-033
Manufacturer SIEMENS
Frame Size 1600
Circuit ID MCC1 T-8
Type RLX-1600
Sensor Size 1600
IC 50000
A 3 A 3
3 MIN 3 MIN
15% MIN 15% MIN
NA NA
29 30
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 2.31 2.31 2.31
150% .09 .09 .09
150% .14 .14 .14
N/A N/A N/A
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type STATICTRIP II (LSG)
Rating Plug N/A
Trip Unit # R-77296C-1
SENS
SENS
BAND
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 9/7/2017
Tested By LAW
MSR LVB-034
Manufacturer SIEMENS
Frame Size 1600
Circuit ID HSB1
Type RLX-1600
Sensor Size 1600
IC 50000
F 3 F 3
N/A N/A N/A N/A
25% INT 25% INT
8 8
26 27
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 3.1 3.1 3.1
N/A N/A N/A N/A
150% 0.27 0.27 0.27
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type STATICTRIP II (TIG)
Rating Plug N/A
Trip Unit # R-77296B-2
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 9/7/2017
Tested By LAW
MSR LVB-035
Manufacturer SIEMENS
Frame Size 1600
Circuit ID CHILLER 1 T-7
Type RLX-1600
Sensor Size 1600
IC 50000
E 3 E 3
N/A N/A N/A N/A
15% INT 15% INT
5 5
43 34
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 3.1 3.1 3.1
N/A N/A N/A N/A
150% 0.32 0.32 0.32
SAT SAT SAT
Status FAILED
Comments NONE OF THE INDICATORS POP OUT. THIS UNIT PROVIDES
PROTECTION BUT NO TRIP INDICATOR ACTION.
MISSING A FRAME ALIGNMENT SPRING ON LEFT SIDE, DOES NOT
AFFECT PROTECTION.
Operating Closing Mechanism operates sluggish. Repair or replace the breaker.
Voltage Rating 600
Trip Unit Type STATICTRIP II (TIG)
Rating Plug N/A
Trip Unit # R-77296B-1
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 9/7/2017
Tested By LAW
MSR LVB-036
Manufacturer SIEMENS
Frame Size 3200
Circuit ID SEC MAIN T-7
Type RL-3200
Sensor Size 3200
IC 50000
D 2.51 D 2.51
5 MAX 5 MAX
25% MAX 25% MAX
NA NA
28 25
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 2.51 2.41 2.51
150% .40 .40 .40
150% 0.47 0.47 0.47
N/A N/A N/A
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type STATICTRIP II (TSG)
Rating Plug N/A
Trip Unit # R-77295A-1
SENS
SENS
BAND
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Equip Desig MAIN Bldg. Swbd.
Date 10/28/2017
Tested By LAW
MSR LVB-037
Manufacturer SIEMENS
Frame Size 2000
Circuit ID SEC MAIN T-5
Type RL-2000
Sensor Size 2000
IC 75000
E2000 1 E2000 1
3 INT 3 INT
25% MAX 25% MAX
N/A N/A
20 22
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 4.14 4.14 4.14
150% 0.25 0.25 0.25
150% 0.42 0.42 0.42
N/A N/A N/A
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type STATICTRIP II (TSG)
Rating Plug N/A
Trip Unit # R-77299A-1 LSG
SENS
SENS
BAND
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 10/28/2017
Tested By LAW
MSR LVB-038
Manufacturer SIEMENS
Frame Size 800
Circuit ID NORMAL PWR & LTG A&B
Type RLX-800
Sensor Size 800
IC 25000
E 800 1 E 800 1
N/A N/A N/A N/A
100% MIN 100% MIN
3 3
24 29
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 4.0 4.0 4.0
N/A N/A N/A N/A
150% .18 .18 .18
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600
Trip Unit Type STATICTRIP II (TIG)
Rating Plug N/A
Trip Unit # R-77300C-1 LIG
SENS
SENS
BAND
BAND
SEC.
Job Number LXVAMC-17
Job Information
Nameplate Information
Trip Unit Settings
Ground Fault
Instantaneous
Long Time
Short Time
X
X
X
X
Pick-Up Delay
As Found As Left
SEN
SENS
SENS
BAND
X
X
X
X
Pick-Up Delay
SEN BAND
Contact Resistance
Micro - Ohms at Amps A B C
Insulation Resistance
A-B B-C C-A
A-Gnd B-Gnd C-Gnd
A B C
Breaker Closed
Breaker Open
Trip Unit Test Values
Ground Fault
Instantaneous
Long Time
Short Time
Test Current A B C
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
SEC.
Amps Amps Amps
ALSET Power Grid Co.
Low Voltage Circuit Breaker Report
Additional Information
A - Excellent Condition
B - Normal Wear Observed
C - Under Observation
D - Repair Required
F - Use Not Recommended
Date 10/28/2017
Tested By LAW
MSR LVB-039
Manufacturer SIEMENS
Frame Size 800
Circuit ID MCC-4N (P-R2)
Type RLX-800
Sensor Size 800
IC 25000
A 1 A 1
N/A N/A N/A N/A
15% MIN 15% MIN
3 3
30 27
MEG-OHMS
2000 2000 2000
2000 2000 2000
2000 2000 2000
600% 4.78 4.78 4.78
N/A N/A N/A N/A
150% .11 .11 .11
SAT SAT SAT
Status PASSED
Comments
Voltage Rating 600