About this file

This federal contract opportunity notice solicits proposals for preventive maintenance, inspection, testing, and arc flash studies of the electrical power distribution system at the Lexington VA Medical Center in Kentucky. Services are required for equipment at facilities on two campuses from August 15, 2020 through December 31, 2020.

The contractor will perform scheduled preventive maintenance, including inspection and testing of switchgear, transformers, generators, protective relays, grounding systems, and other electrical equipment. Additional requirements include infrared scanning, arc flash studies with labeling, and a 4-hour power outage test. The contractor must have qualified personnel, follow all applicable safety procedures, and submit written reports. Proposals are due by June 17, 2020 with award anticipated shortly thereafter. The contract will be fixed price and services must be completed by December 31, 2020.

View the file

Other files

File Type Posted
Bowling 3 year info Part 2.pdf PDF
36C24920Q0261 0002.docx DOCX document
36C24920Q0261.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER PAGE

INFORMATION

This document contains proprietary information related to the Contracted

Inspection, Testing and Preventative Maintenance Services provided by Alset Power Grid, Inc. The unauthorized disclosure of this information may subject both the discloser and recipient of the information to contractual, civil, and/or criminal penalties as provided by law.

PROPRIETARY

VAMC Cooper Drive

Lexington, KY

November 7, 2017

Table Of Contents

PO #596C70187; Triennial Electrical Power

Inspection Services

I. TABLE OF CONTENTS

II. REPORT AND DEFICIENCIES

III. DESCRIPTION OF TEST

IV. LOW VOLTAGE CIRCUIT BREAKERS

V. MEDIUM VOLTAGE CIRCUIT BREAKERS

VI. PROTECTIVE RELAYS

VII. AIR SWITCHES

VIII. ATS’S, MCC’s

IX. OIL TRANSFORMER & FLUID REPORTS-WEIDMANN

X. GENERATOR FLUID REPORTS-OHIO CAT

XI. ARC FLASH, IR SCANNED PANELS

XII. MISC.

Total Electrical Protective System Reliability

513 Mill Ave. S.E. #111, New Philadelphia, OH 44663

1-330-795-3041 Email Address: ALSETPowergrid@msn.com

Department of VAMC (Cooper Drive) November 10, 2017

138 CD Electronics Shop

1101 Veterans Drive

Lexington, KY 40502

Attn: Mr. Herbert Sparks

Reference: PO #596C70187; Triennial Electrical Panel

Inspection Services

Dear Mr. Sparks, I. DESCRIPTION OF TESTS

The following is a description of tests and testing procedures intended for checking the insulation condition, basic electrical operation and/or timing parameters of the applicable equipment tested.

INSULATION RESISTANCE TESTING

In an Insulation resistance Test, voltage, from 100 to 5,000 Volts, supplied from a source of constant potential, is applied across the insulation (transformers, cables, circuit breakers, starters, motors, etc.). The usual potential is a megohmmeter, either hand or power operated, which indicates the insulation resistance directly on a scale calibrated in megohms. The quality of the insulation is evaluated based on the level of the insulation resistance.

DIELECTRIC ABSORPTION

In a Dielectric Absorption Test, a voltage, supplied from a source of constant potential, is applied across the insulation. The voltage is applied for an extended period of time, from 5 to 15 minutes, and periodic readings are taken of the insulation resistance or leakage current. The test data is evaluated on the basis that if insulation is in good condition, its apparent insulation resistance will increase as the test progresses.

POLARIZATION INDEX

The Polarization Index is a specialized application of the dielectric absorption test. The index is usually the ratio of insulation resistance at ten minutes to the insulation resistance at one minute. The use of PI Testing is usually confined to rotating machines, cables and transformers (on this particular job-only the 4160V motors.

HIGH POTENTIAL TESTING

A High Potential Test consists of applying voltage across insulation at or above the DC equivalent of the 60HZ operating crest voltage. This test can be applied either as a dielectric absorption test or a step-voltage test.

When applied as a step-voltage test, the maximum voltage is applied in a number of equal intervals of time. The time interval between steps should be long enough to allow the leakage current to reach stability, approximately one or two minutes. A leakage current reading is taken at the end of each interval before the voltage is raised to the next level. A linear increase in leakage current is expected and it should stabilize of decrease from the initial value at each step. A nonlinear increase in leakage current may indicate imminent failure and the test should be discontinued. This test was only applied to the systems' main buses; no cables were hi-potted.

INSULATION POWER FACTOR TESTING

The power factor of insulation is the cosine of the angle between the charging current vector and the impressed voltage vector when the insulation system is energized with an AC voltage. In other words, it is a measure of the energy component of the charging current. The term "Power Factor Testing" means any testing performed in order to determine the power factor of an insulation system. Power factor testing is a useful tool in evaluating the quality of insulation in power, distribution and instrument transformers, circuit breakers, rotating machines, cables, regulators and insulating liquids.

On transformer tests, the power factor of (1) each winding with respect to ground and (2) each winding with respect to each other winding should be obtained. In addition, tests should be made of each bushing with a rated voltage above 600 volts, either using the power factor or capacitance tap if the bushing is so equipped or by use of a "Hot-

Collar" test using a test electrode around the outside shell of the bushing.

Evaluation of the data obtained should be based on (1) industry standards for the particular type of equipment tested, (2) correlation of data obtained with test data from other similar units tested, and (3) comparison of data with previous test data on the same equipment.

PROTECTIVE DEVICE TESTING

FUSES - There is no way to test the operation of fuses on a system since this type of device destroys itself while performing its protective function. The only test that can be performed on a fuse in the field is a continuity test to determine whether or not the fuse has "blown".

LOW VOLTAGE CIRCUIT BREAKERS, GENERAL - Low voltage circuit breakers can generally be divided into tow categories depending upon the applicable industry design standards, molded case circuit breakers and low voltage power circuit breakers.

When testing circuit breaker tripping characteristics, it is recommended that the overcurrent tests be performed on individual poles at 300 percent of rated current. The reaction of the circuit breaker to this overload is indicative of its reaction throughout its entire overcurrent tripping range. This load is chosen as the test point because it is relatively easy to generate the required current in the field and the wattage per pole from line to load is large enough, so the dissipation of heat in the nonactive pole spaces is minor and does not affect the test results appreciably.

The testing of electromechanical trip devices or solid-state devices by the primary injection method requires the use of a high current test set capable of producing sufficient current at low voltage to operate each of the elements of the trip device. This test must have means of adjusting the amount of current applied to the trip device and a cycle and second timer to measure the amount of time to trip the breaker at each current setting. At least one test should be made in the range of each element of the trip device. The long time delay element should ordinarily be tested at approximately 300 percent of its setting.

The short time delay element should be tested at 150 percent to 200 percent of its setting.

The instantaneous element should be tested to assure that it does not operate at too low a current level, yet will operate at the proper level. For the test of the instantaneous element, the applied current must be symmetrical without an asymmetrical offset or random errors will be introduced.

CONTACT RESISTANCE TESTING

This test is used to test the quality of the contacts on switches and circuit breakers.

A test set designed for this purpose is available with direct scale calibration in microhms, capable of reading contact resistances of 10 microhms or less.

The contact resistance should be kept as low as possible to reduce power losses at the contacts with the resultant localized heating, which will shorten the life of both contacts and nearby insulation.

PROTECTIVE RELAY TESTING

Protective relays are used in conjunction with medium voltage circuit breakers

(above 600 volts) to sense an abnormality and cause the trouble to be isolated with minimum disturbance to the electrical system and with the least damage to the equipment at fault. They have the accuracy and sophistication demanded by the protective requirements of the primary feeder circuits and larger electrical equipment. Protective relays designed to be responsive to an abnormal excursion in current voltage, frequency, phase-angle, direction of current or power flow, etc., and with varying operation characteristics are commercial available. Each relay application requires custom engineering to satisfy the parameters of its particular intended function in the system.

TRANSFORMER TURNS RATIO AND POLARITY TESTS

The Turns Ratio Test is used to determine the number of turns in one winding of a transformer in relation to the number of turns in the other windings of the same phase of the transformer. The Polarity Test determines the vectoral relationships of the various transformer windings.

This test is useful in determining whether a transformer has any shorted turns or improper connections and, on acceptance testing, to verify nameplate information.

ULTRASONIC (CORONA DETECTION) TESTS

Perform Ultrasonic Testing on main switchgear bus and circuit breaker elements and lightning arrestors to test for corona and leaking lightning and surge arrestors.

INFRA-RED SURVEY

The infrared scanner is an instrument that provides a real-time television like image on the natural infrared energy being emitted from objects within its field of view.

This is in contrast to infrared thermometer-type devices, which view a point or single line. Infrared scanners are not cameras; they do not use infrared film. They work because any object at its temperature above absolute zero is radiating energy proportional to its temperature, and these scanners contain detector material sensitive to infrared energy.

Applied to electrical power distribution systems, infrared scanning is one of the few tests that can be performed while the system is energized and under load to determine if weaknesses exist that could lead to power failures and "surprise" electrical outages.

The above tests were performed in accordance with standard testing procedures, and calibrated testing instruments.

Sincerely yours, ALSET Power Grid, Inc.

Larry A. Wise Larry A. Wise, Field Engineer

Location LEXINGTON, KY (COOPER DRIVE

Equip Desig SBA-5

Date 10/28/2017

Tested By LAW

MSR LVB-001

Manufacturer GE

Frame Size 600

Circuit ID BRKR 5 MACH RM

Type AKU-2A-25-1

Sensor Size 300

IC 25000

1C 3 1C 3

3C INT 3C INT

N/A N/A N/A N/A

10X 10X

109 110

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

300% 36.3 36.3 36.3

150% 0.27 0.27 0.27

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type MICRO VERSA TRIP

Rating Plug N/A

Trip Unit # TA9VT20SLA1

SENS

SENS

SENS

BAND

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

B

Customer VAMC

Equip Desig SBG

Date 10/28/2017

Tested By LAW

MSR LVB-002

Manufacturer GE

Frame Size 1600

Circuit ID SBG 1 SOUTH WING

Type AK-2A-50-1

Sensor Size 1600

IC 50000

1.0 3 1.0 20

3 MAX 3 MAX

N/A N/A N/A N/A

3 3

32 41

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 29.9 29.9 29.9

150% 0.44 0.44 0.44

N/A N/A N/A N/A

N/A N/A N/A

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type GE

Rating Plug 600

Trip Unit # PRO TRIP

SENS

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBA-1

Date 10/28/2017

Tested By LAW

MSR LVB-004

Manufacturer GE

Frame Size 3000

Circuit ID MAIN

Type AK-3A-75

Sensor Size 3000

IC 65000

0.7 2.5 0.7 2.5

2.5 0.2 2.5 0.2

N/A N/A N/A N/A

N/A N/A

21 23

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 2.8 2.8 2.8

150% 0.229 0.229 0.229

N/A N/A N/A N/A

N/A N/A N/A

Status PASSED

Comments DIP SWITCH-SLI-8 SETTING=1,2,4,5,6,7,8 ON. 3 OFF

DIP SWITCH-SSI-8 SETTING=1,2,3,4,6,8 ON. 5,7 OFF

DIP SWITCH-SGI-8 SETTING=1 THRU 8 OFF

DIP SWITCH-SII-8 SETTING=1 THRU 8 OFF

Voltage Rating 600

Trip Unit Type MULTILIN

Rating Plug N/A

Trip Unit # FB600E

SENS

SENS

SEC.

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SEC.

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBA-2

Date 10/28/2017

Tested By LAW

MSR LVB-005

Manufacturer GE

Frame Size 1600

Circuit ID BRKR 2 SHOP

Type AKU-2A-50-1

Sensor Size 400

IC 50000

0.5 10 0.5 10

10 2 10 2

N/A N/A N/A

6 6

132 135

MEG-OHMS

2000 2000 SS

2000 2000 SS

2000 2000 SS

600% 18.76 18.76 18.76

150% 0.12 0.12 0.12

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type MULTILIN

Rating Plug N/A

Trip Unit # FB600

SENS

SEC.

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SEC.

BAND

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBB-1

Date 10/28/2017

Tested By LAW

MSR LVB-006

Manufacturer GE

Frame Size 3000

Circuit ID BRKR 1 MAIN

Type AKU-2A-75-1

Sensor Size 2000

IC 65000

2000 1 2000 1

4000 2 4000 2

N/A N/A N/A N/A

N/A N/A

28 27

MEG-OHMS

1000 1000 1000

1000 1000 1000

1000 1000 1000

300% 36.97 35.34 35.10

150% 0.58 0.63 0.73

N/A N/A N/A N/A

N/A N/A N/A

Status RETROFIT

Comments RECOMMEND RETROFITTING TO SOLID STATE. UNIT HAS OLD

OBSOLETE ELECTOR-MECHANICAL TRIP DEVICES.

Voltage Rating 600

Trip Unit Type G.E. EC-1B

Rating Plug 1CC-2CC

Trip Unit # 177L226DAG-30

SENS

SENS

SEC.

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SEC.

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

D

Equip Desig SBB-2

Date 10/28/2017

Tested By LAW

MSR LVB-007

Manufacturer GE

Frame Size 1600

Circuit ID BRKR 2 Radiology

Type AKU-2A-50-1

Sensor Size 600

IC 50000

0.5 3 0.5 3

1.5 INT 1200 INT

N/A N/A N/A N/A

1.5 1.5

47 45

MEG-OHMS

1000 1000 1000

1000 1000 1000

1000 1000 1000

600% 35.11 35.11 35.11

150% 0.2 0.2 0.2

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type G.E.

Rating Plug 1600

Trip Unit # PRO TRIP

SENS

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBB-3

Date 10/28/2017

Tested By LAW

MSR LVB-008

Manufacturer GE

Frame Size 1600

Circuit ID BRKR 3 PATHOLOGY

Type AK-2A-50-1

Sensor Size 800

IC 50000

.5 20 .5 20

3 0.15 3 0.15

N/A N/A N/A N/A

10 10

39 35

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 23.05 23.05 23.05

150% 0.2 0.2 0.2

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type MULTILIN

Rating Plug NA

Trip Unit # FB600E

SENS

SENS

SENS

SEC.

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

SEC.

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBB-4

Date 10/28/2017

Tested By LAW

MSR LVB-009

Manufacturer GE

Frame Size 1600

Circuit ID BRKR 4 DIST BD

Type AK-2A-50-1

Sensor Size 800

IC 50000

1.15 12.5 1.15 12.5

2.5 0.4 2.5 0.4

N/A N/A N/A N/A

N/A N/A

43 40

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

300% 33.88 32.78 34.16

150% 0.42 0.42 0.42

N/A N/A N/A N/A

N/A N/A N/A

Status PASSED

Comments DIP SWITCH-SLI-8 SETTING 2,5,6,8 ON. 1,3,4,7 OFF.

DIP SWITCH-SSI-8 SETTING 1,2,3,4,7,8 ON. 5,6 OFF.

DIP SWITCH-SII-8 SETTING 1,2,3 ON. 4,5,6,7,8 OFF.

Voltage Rating 600

Trip Unit Type MULTILIN

Rating Plug N/A

Trip Unit # FB600

SENS

SENS

SEC.

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SEC.

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBB-5

Date 10/28/2017

Tested By LAW

MSR LVB-010

Manufacturer GE

Frame Size 1600

Circuit ID BRKR 5 KITCHEN

Type AKU-2A-50-1

Sensor Size 400

IC 50000

560 N/A 560 N/A

2000 N/A 2000 N/A

N/A N/A N/A N/A

N/A N/A

80 76

MEG-OHMS

100 100 100

100 100 100

100 100 100

300% 107.24 102.34 97.73

150% 0.238 0.29 0.229

N/A N/A N/A N/A

N/A N/A N/A

Status RETROFIT

Comments RECOMMEND RETROFITTING TO SOLID STATE. UNIT HAS OLD

OBSOLETE ELECTOR-MECHANICAL TRIP DEVICES.

Voltage Rating 600

Trip Unit Type G.E. EC-1

Rating Plug 1A-2C

Trip Unit # 238U685G1-EG

SENS

SENS

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBC-4

Date 10/1/2017

Tested By LAW

MSR LVB-012

Manufacturer GE

Frame Size 600

Circuit ID BRKR 4 RES PATH

Type AK-2A-25-1

Sensor Size 300

IC 25000

0.7 20 0.7 20

4 0.2 0.2 0.2

N/A N/A N/A N/A

N/A N/A

107 161

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 20.59 20.59 20.59

150% 0.258 0.258 0.258

N/A N/A N/A N/A

N/A N/A N/A

Status PASSED

Comments Replace due to age, the obsolence availabilty parts.

DIP SWITCH-SLI-8 SETTING=1,2,4,8 ON. 3,5,6,7 OFF

DIP SWITCH-SSI-8 SETTING=3,4,6,8 ON. 1,2,5,7 OFF

DIP SWITCH-SII-8 SETTING=1,2 ON. 3,4,5,6,7,8 OFF

Voltage Rating 600

Trip Unit Type MULTILIN

Rating Plug N/A

Trip Unit # FB600

SENS

SENS

SEC.

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SEC.

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBC-5

Date 10/1/2017

Tested By LAW

MSR LVB-013

Manufacturer GE

Frame Size 600

Circuit ID BRKR 5 PATH LAB

Type AK-2A-25-1

Sensor Size 600

IC 25000

0.5 20 0.5 20

3 0.2 3 0.2

N/A N/A N/A N/A

N/A N/A

15 70

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 18.2 18.25 18.79

150% 0.21 0.21 0.21

N/A N/A N/A N/A

N/A N/A N/A

Status PASSED

Comments Replace due to age, the obsolence availabilty parts.

DIP SWITCH-SLI-8 SETTING=1,2,3,4,8 ON. 5,6,7 OFF

DIP SWITCH-SSI-8 SETTING=2,3,4,6,8 ON. 1,5,7 OFF

DIP SWITCH-SII-8 SETTING=1,3 ON. 2,4,5,6,7,8 OFF

TRIP BUTTON STICKS, NEEDED WORK TO RESET & CLOSE.

Voltage Rating 600

Trip Unit Type MULTILIN

Rating Plug NA

Trip Unit # FB600

SENS

SENS

SEC.

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SEC.

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBB-6

Date 10/28/2017

Tested By LAW

MSR LVB-014

Manufacturer GE

Frame Size 600

Circuit ID BRKR 6, RM CLOSE

Type AKU-7A-25-1

Sensor Size 300

IC 200000

1.1 3 1.1 3

N/A N/A N/A N/A

N/A N/A N/A N/A

10 10

155 172

MEG-OHMS

100 100 100

100 100 100

100 100 100

600% 11.42 11.42 11.42

N/A N/A N/A N/A

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments 1200 AMPTRAP, TYPE BG, IC 200,000 A.

Voltage Rating 600

Trip Unit Type MICRO VERSA TRIP

Rating Plug 150

Trip Unit # RMS-9

SENS

SENS

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBC-3

Date 10/1/2017

Tested By LAW

MSR LVB-015

Manufacturer GE

Frame Size 1600

Circuit ID BRKR 3 CRIT RIS

Type AKU-2A-50

Sensor Size 1600

IC 50000

0.8X 2 0.8X 2

4C MAX 4C MAX

N/A N/A N/A N/A

15X 15X

36 30

MEG-OHMS

1000 175 460

290 1450 250

560 855 559

600% 5.72 5.72 5.72

150% 0.39 0.39 0.39

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments NEW REBUILT.

Voltage Rating 600

Trip Unit Type MICRO VERSA TRIP

Rating Plug 150

Trip Unit # RMS-9

SENS

SENS

SENS

BAND

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBC-2

Date 10/1/2017

Tested By LAW

MSR LVB-016

Manufacturer GE

Frame Size 1600

Circuit ID BRKR 2 SERV RM (MCC)

Type AK-2A-50-1

Sensor Size 800

IC 50000

0.6 15 0.6 15

5 0.2 0.2 N/A

N/A N/A N/A N/A

N/A N/A

42 50

MEG-OHMS

705 678 750

285 532 341

511 705 486

600% 12.914 12.914 12.914

150% 0.3 0.28 0.27

N/A N/A N/A N/A

N/A N/A N/A

Status PASSED

Comments DIP SWITCH-SLI-8 SETTING=1,3,4,6,8 ON; 2,5,7 OFF.

DIP SWITCH-SSI-8 SETTING=2,4,6,8 ON; 1,3,5,7 OFF.

DIP SWITCH-SII-8 SETTING=INST. AND GF DISABLED.

Voltage Rating 600

Trip Unit Type MULTILIN

Rating Plug N/A

Trip Unit # FB600E

SENS

SENS

SEC.

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SEC.

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBD-1

Date 10/28/2017

Tested By LAW

MSR LVB-017

Manufacturer GE

Frame Size 1600

Circuit ID SBD BRKR 1 CRITICAL

Type AKU-2A-50-1

Sensor Size 1600

IC 50000

E TB#4 E TB#4

3 TB#2 3 TB#2

N/A N/A N/A N/A

N/A N/A

58 53

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

300% 2.24 2 2

150% 0.5 0.5 0.5

N/A N/A N/A N/A

N/A N/A N/A

Status RETROFIT

Comments BREAKER WOULD NOT RECLOSE. TRIP BAR & ROLLERS NEEDED

LUBRICATION. RECOMMEND RETROFITTING THE OBSELETE LTS TRIP

BOX & ACTUATOR.

Voltage Rating 600

Trip Unit Type SIEMENS LTS

Rating Plug N/A

Trip Unit # 2010-6-4

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBD-2

Date 10/28/2017

Tested By LAW

MSR LVB-018

Manufacturer GE

Frame Size 1600

Circuit ID SBD BRKR 2 EMERG.

Type AKU-2A-50-1

Sensor Size 1600

IC 50000

B TB#3 B TB#3

3 TB#2 3 TB#2

N/A N/A N/A N/A

N/A N/A

37 43

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 3 3 3

150% 0.26 0.26 0.26

N/A N/A N/A N/A

N/A N/A N/A

Status RETROFIT

Comments BREAKER WOULD NOT RECLOSE. TRIP BAR & ROLLERS NEEDED

LUBRICATION. RECOMMEND RETROFITTING THE OBSELETE LTS TRIP

BOX & ACTUATOR.

Voltage Rating 600

Trip Unit Type SIEMENS LTS

Rating Plug N/A

Trip Unit # 2010-6-3

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBE-2

Date 10/1/2017

Tested By LAW

MSR LVB-019

Manufacturer GE

Frame Size 1600

Circuit ID BRKR 2 EMRG RIS

Type AKU-2A-50

Sensor Size 1600

IC 50000

0.8X 2 0.8X 2

7C MAX 7C MAX

N/A N/A N/A N/A

15 15

32 31

MEG-OHMS

775 320 220

420 520 1240

960 1240 480

600% 5.72 5.72 5.72

150% 0.39 0.39 0.39

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments New Rebuilt. Trip Flags do not pop out.

Voltage Rating 600

Trip Unit Type MICRO VERSA TRIP

Rating Plug 150

Trip Unit # RMS-9

SENS

SENS

SENS

BAND

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBE-3

Date 10/1/2017

Tested By LAW

MSR LVB-020

Manufacturer GE

Frame Size 600

Circuit ID SBE 3, HEMG-1

Type AKU-2A-25-1

Sensor Size 1100

IC 25000

160 30-90 160 30-90

600 N/A 600 N/A

N/A N/A N/A N/A

0 0

266 298

MEG-OHMS

1486 2000 2000

2000 2000 1200

2000 1500 2000

300% 200.43 N/A N/A

150% 0.16 0.17 N/A

N/A N/A N/A N/A

N/A N/A N/A

Status RETROFIT

Comments REPLACE TRIP DEVICES, RETROFIT TRIP DEVICES TO SOLID STATE.

Voltage Rating 600

Trip Unit Type G.E. EC-1

Rating Plug 1A-2C

Trip Unit # 238U685G1-LF

SENS

SENS

SENS

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBE-4

Date 10/1/2017

Tested By LAW

MSR LVB-021

Manufacturer GE

Frame Size 600

Circuit ID BRKR 4 RAD FAN & HEMG EMRG

Type AKU-2A-25-1

Sensor Size 200

IC 30000

1.0 3 1.0 3

4C MIN N/A N/A

N/A N/A N/A N/A

10X 10X

182 142

MEG-OHMS

2000 200 500

2000 300 280

2000 500 1160

600% 16.4 16.4 16.4

150% 0.14 0.14 0.14

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type MICRO VERSA TRIP

Rating Plug N/A

Trip Unit # TA9VT20SLA1

SENS

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBA-3

Date 10/28/2017

Tested By LAW

MSR LVB-022

Manufacturer GE

Frame Size 600

Circuit ID BRKR 3 PENTHOUSE

Type AK-2A-25-1

Sensor Size 600

IC 30000

.5 20 .5 20

2.5 0.15 2.5 0.15

N/A N/A N/A N/A

N/A N/A

120 128

MEG-OHMS

100 100 100

100 100 100

100 100 100

600% 17.76 17.76 17.76

150% 0.22 0.22 0.22

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments TRIP FLAGS DAMAGED. RECOMMEND RETROFIT TO NEW SOLID STATE

Voltage Rating 600

Trip Unit Type MULTILIN

Rating Plug N/A

Trip Unit # FB600

SENS

SENS

SENS

SEC.

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

SEC.

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBF-1

Date 10/28/2017

Tested By LAW

MSR LVB-023

Manufacturer GE

Frame Size 1600

Circuit ID NORTH WING RISR

Type AKU-2A-50-1

Sensor Size 1200

IC 50000

960 10-40 960 10-40

2C N/A 2C N/A

N/A N/A N/A N/A

N/A N/A

38 37

MEG-OHMS

100 100 100

100 100 100

100 100 100

200% 25.43 27.82 27.99

150% 0.18 0.15 0.12

N/A N/A N/A N/A

N/A N/A N/A

Status RETROFIT

Comments RECOMMEND RETROFITTING TO SOLID STATE. UNIT HAS OLD

OBSOLETE ELECTOR-MECHANICAL TRIP DEVICES.

Voltage Rating 600

Trip Unit Type G.E. EC-1

Rating Plug 1C-2C-3

Trip Unit # 238U685G2-AG

SENS

SENS

SEC.

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SEC.

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBA

Date 10/28/2017

Tested By LAW

MSR LVB-024

Manufacturer GE

Frame Size 1600

Circuit ID PANEL DPLS

Type AKS-10A-50

Sensor Size 1600

IC 50000

.5 N/A .5 N/A

9 N/A 9 N/A

N/A N/A N/A N/A

1.5 1.5

37 35

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

300% 4.0 4.0 4.0

150% 0.3 0.3 .3

N/A N/A N/A N/A

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type MUTPLUS

Rating Plug N/A

Trip Unit # LSI

SENS

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig SBH-1

Date 10/28/2017

Tested By LAW

MSR LVB-025

Manufacturer GE

Frame Size 1600

Circuit ID BLD POWER RISER

Type AKU-2A-50-1

Sensor Size 1200

IC 50000

1920 50-150 1920 50-150

8400 N/A 8400 N/A

N/A N/A N/A N/A

N/A N/A

64 88

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 43.1 43.1 43.1

150% 0.14 0.17 0.2

N/A N/A N/A N/A

N/A N/A N/A

Status RETROFIT

Comments RECOMMEND RETROFITTING TO SOLID STATE. UNIT HAS OLD

OBSOLETE ELECTOR-MECHANICAL TRIP DEVICES.

Voltage Rating 600

Trip Unit Type G.E. EC-1

Rating Plug 1A-2C

Trip Unit # 238U685G1-BG

N/A

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

N/A

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig CHILLER PLANT

Date 9/7/2017

Tested By LAW

MSR LVB-027

Manufacturer SIEMENS

Frame Size 3200

Circuit ID SEC MAIN T-8

Type RL-3200

Sensor Size 3200

IC 75000

B 3 B 3

3 MAX 3 MAX

25% MIN 25% MIN

N/A N/A

34 34

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 4.75 4.75 4.75

150% 0.45 0.45 0.45

150% .20 .20 .20

N/A N/A N/A

Status PASSED

Comments Electric Open-Close Switch and Ammeters inoperative.

Voltage Rating 600

Trip Unit Type STATICTRIP II (TSG)

Rating Plug N/A

Trip Unit # R-77295B-3

SENS

SENS

SENS

BAND

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 9/7/2017

Tested By LAW

MSR LVB-028

Manufacturer SIEMENS

Frame Size 1600

Circuit ID SPARE T-8

Type RLX-1600

Sensor Size 1000

IC 50000

A 1 A 1

N/A N/A N/A N/A

25% MAX 25% MAX

12 12

187 173

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 1.17 1.17 1.17

N/A N/A N/A N/A

150% 0.45 0.45 0.45

SAT SAT SAT

Status PASSED

Comments LT and GF TESTS WERE SUCCESSFUL BUT THE LT and GF INDICATORS

DID NOT POP OUT.

Voltage Rating 600

Trip Unit Type STATICTRIP II (TIG)

Rating Plug N/A

Trip Unit # R-77296A-2

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 9/7/2017

Tested By LAW

MSR LVB-029

Manufacturer SIEMENS

Frame Size 1600

Circuit ID MCC2 T-8

Type RLX-1600

Sensor Size 1600

IC 50000

C 3 C 3

NA NA NA NA

15% INT 15% INT

3 3

32 32

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 5.83 5.83 5.83

NA NA NA NA

150% .26 .26 .26

SAT SAT SAT

Status PASSED

Comments TRIPPED SATISFACTORY, GF FAULT INDICATORS DID NOT POP OUT.

Voltage Rating 600

Trip Unit Type STATICTRIP II (TSG)

Rating Plug N/A

Trip Unit # R-77296C-2

SENS

SENS

SENS

BAND

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 9/7/2017

Tested By LAW

MSR LVB-030

Manufacturer SIEMENS

Frame Size 1600

Circuit ID MCC-2 T-8

Type RLX-1600

Sensor Size 1600

IC 50000

A 3 A 3

4 MIN 4 MIN

15% MIN 15% INT

5 5

24 31

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 1.37 1.37 1.37

150% .07 .07 .07

150% .09 .09 .09

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type STATICTRIP II (TIG)

Rating Plug N/A

Trip Unit # R-77296B-3

SENS

SENS

SENS

BAND

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 9/7/2017

Tested By LAW

MSR LVB-031

Manufacturer SIEMENS

Frame Size 3200

Circuit ID TIE

Type RL-3200

Sensor Size 3200

IC 75000

E 3 E 3

3 MAX 5 MAX

25% MAX 25% MAX

NA NA

49 52

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 2.36 2.36 2.36

150% .43 .43 .43

150% .43 .43 .43

N/A N/A N/A

Status PASSED

Comments Charging Motor Toggle Switch is defective recommend replacing the switch.

Voltage Rating 600

Trip Unit Type STATICTRIP II (TSG)

Rating Plug N/A

Trip Unit # R-77295A-2

SENS

SENS

BAND

BAND

BAND

SEC

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC

SEC

SEC

SEC

SEC

SEC

SEC

SEC

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 9/7/2017

Tested By LAW

MSR LVB-032

Manufacturer SIEMENS

Frame Size 1600

Circuit ID SPARE T-7

Type RLX-1600

Sensor Size 1000

IC 50000

N/A N/A N/A N/A

N/A N/A N/A N/A

N/A N/A N/A N/A

N/A N/A

30 28

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

N/A N/A N/A N/A

N/A N/A N/A N/A

N/A N/A N/A N/A

N/A N/A N/A

Status FAILED

Comments NO TRIP DEVICE ON THE CIRCUIT BREAKER ELEMENT.

BEFORE USING INSTALL A TRIP DEVICE & RESET.

Voltage Rating 600

Trip Unit Type NONE INSTALLED

Rating Plug N/A

Trip Unit # NONE INSTALLED

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

X

X

X

X

Pick-Up Delay

SEN ----

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

F

Date 9/7/2017

Tested By LAW

MSR LVB-033

Manufacturer SIEMENS

Frame Size 1600

Circuit ID MCC1 T-8

Type RLX-1600

Sensor Size 1600

IC 50000

A 3 A 3

3 MIN 3 MIN

15% MIN 15% MIN

NA NA

29 30

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 2.31 2.31 2.31

150% .09 .09 .09

150% .14 .14 .14

N/A N/A N/A

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type STATICTRIP II (LSG)

Rating Plug N/A

Trip Unit # R-77296C-1

SENS

SENS

BAND

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 9/7/2017

Tested By LAW

MSR LVB-034

Manufacturer SIEMENS

Frame Size 1600

Circuit ID HSB1

Type RLX-1600

Sensor Size 1600

IC 50000

F 3 F 3

N/A N/A N/A N/A

25% INT 25% INT

8 8

26 27

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 3.1 3.1 3.1

N/A N/A N/A N/A

150% 0.27 0.27 0.27

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type STATICTRIP II (TIG)

Rating Plug N/A

Trip Unit # R-77296B-2

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 9/7/2017

Tested By LAW

MSR LVB-035

Manufacturer SIEMENS

Frame Size 1600

Circuit ID CHILLER 1 T-7

Type RLX-1600

Sensor Size 1600

IC 50000

E 3 E 3

N/A N/A N/A N/A

15% INT 15% INT

5 5

43 34

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 3.1 3.1 3.1

N/A N/A N/A N/A

150% 0.32 0.32 0.32

SAT SAT SAT

Status FAILED

Comments NONE OF THE INDICATORS POP OUT. THIS UNIT PROVIDES

PROTECTION BUT NO TRIP INDICATOR ACTION.

MISSING A FRAME ALIGNMENT SPRING ON LEFT SIDE, DOES NOT

AFFECT PROTECTION.

Operating Closing Mechanism operates sluggish. Repair or replace the breaker.

Voltage Rating 600

Trip Unit Type STATICTRIP II (TIG)

Rating Plug N/A

Trip Unit # R-77296B-1

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 9/7/2017

Tested By LAW

MSR LVB-036

Manufacturer SIEMENS

Frame Size 3200

Circuit ID SEC MAIN T-7

Type RL-3200

Sensor Size 3200

IC 50000

D 2.51 D 2.51

5 MAX 5 MAX

25% MAX 25% MAX

NA NA

28 25

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 2.51 2.41 2.51

150% .40 .40 .40

150% 0.47 0.47 0.47

N/A N/A N/A

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type STATICTRIP II (TSG)

Rating Plug N/A

Trip Unit # R-77295A-1

SENS

SENS

BAND

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Equip Desig MAIN Bldg. Swbd.

Date 10/28/2017

Tested By LAW

MSR LVB-037

Manufacturer SIEMENS

Frame Size 2000

Circuit ID SEC MAIN T-5

Type RL-2000

Sensor Size 2000

IC 75000

E2000 1 E2000 1

3 INT 3 INT

25% MAX 25% MAX

N/A N/A

20 22

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 4.14 4.14 4.14

150% 0.25 0.25 0.25

150% 0.42 0.42 0.42

N/A N/A N/A

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type STATICTRIP II (TSG)

Rating Plug N/A

Trip Unit # R-77299A-1 LSG

SENS

SENS

BAND

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 10/28/2017

Tested By LAW

MSR LVB-038

Manufacturer SIEMENS

Frame Size 800

Circuit ID NORMAL PWR & LTG A&B

Type RLX-800

Sensor Size 800

IC 25000

E 800 1 E 800 1

N/A N/A N/A N/A

100% MIN 100% MIN

3 3

24 29

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 4.0 4.0 4.0

N/A N/A N/A N/A

150% .18 .18 .18

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600

Trip Unit Type STATICTRIP II (TIG)

Rating Plug N/A

Trip Unit # R-77300C-1 LIG

SENS

SENS

BAND

BAND

SEC.

Job Number LXVAMC-17

Job Information

Nameplate Information

Trip Unit Settings

Ground Fault

Instantaneous

Long Time

Short Time

X

X

X

X

Pick-Up Delay

As Found As Left

SEN

SENS

SENS

BAND

X

X

X

X

Pick-Up Delay

SEN BAND

Contact Resistance

Micro - Ohms at Amps A B C

Insulation Resistance

A-B B-C C-A

A-Gnd B-Gnd C-Gnd

A B C

Breaker Closed

Breaker Open

Trip Unit Test Values

Ground Fault

Instantaneous

Long Time

Short Time

Test Current A B C

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

SEC.

Amps Amps Amps

ALSET Power Grid Co.

Low Voltage Circuit Breaker Report

Additional Information

A - Excellent Condition

B - Normal Wear Observed

C - Under Observation

D - Repair Required

F - Use Not Recommended

Date 10/28/2017

Tested By LAW

MSR LVB-039

Manufacturer SIEMENS

Frame Size 800

Circuit ID MCC-4N (P-R2)

Type RLX-800

Sensor Size 800

IC 25000

A 1 A 1

N/A N/A N/A N/A

15% MIN 15% MIN

3 3

30 27

MEG-OHMS

2000 2000 2000

2000 2000 2000

2000 2000 2000

600% 4.78 4.78 4.78

N/A N/A N/A N/A

150% .11 .11 .11

SAT SAT SAT

Status PASSED

Comments

Voltage Rating 600