UNTAGGED-07C HVAC Specification Addendum.pdf
PDF 123 KB Posted
- Attached to
- FY26: NRM (PROJ: 573-21-705) BB - Replace Deteriorated AHU 21, 22, 23 and 24 Gainesville FL
- Solicitation number
- 36C24826R0039
About this file
This Specification Addendum details technical preferences for the Renovate 3D Cardiology Service project at Malcom Randall VAMC in Gainesville, FL. The document provides specific material and construction recommendations across multiple technical specifications sections, with a strong emphasis on material choices and system design. Key preferences include brass fittings, galvanized steel covers for chill water pumps, aluminum frames and blades for control elements, fan wall/fan array construction for redundancy, direct drive motors for fans, digital air flow monitoring, and aluminum or stainless steel for air outlets and inlets. The VA consistently shows a preference for materials and designs that enhance durability, performance, and system reliability, with specific considerations for different use cases such as operating rooms.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| UNTAGGED-07A GNV AHUs 20s- Bid Documents for Construction - Drawings.pdf | ||
| UNTAGGED-07 GNV AHUs 20s- Bid Documents for Construction - Specifications.pdf | ||
| UNTAGGED-05 SOW 573-21-705.docx | DOCX document | |
| S01 Sources Sought Final 36C24826R0039.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATION ADDENDUM
Renovate 3D for Cardiology Service
Malcom Randall VAMC Gainesville, FL
22 11 00 - 8
2.5 DIELECTRIC FITTINGS:
• VA Prefers brass fittings not Dielectric
23 07 11 - 17
3.2 INSULATION INSTALLATION
A.2.D CHILL WATER PUMPS:
• VA prefers Galvanized Steel covers lined with insulation for chill water pumps NOT aluminum.
23 09 23 - 36
2.9 FINAL CONTROL ELEMENTS AND OPERATORS
• VA Prefers Aluminum for frame and blade material (paragraphs C.2 and C.3)
23 09 23 - 38
2.10 AIR FLOW CONTROL
• VA would like an air flow monitor with digital readout at monitor.
23 34 00 - 4
2.1 FAN SECTION (CABINET FAN)
• VA prefers a fan wall/fan array construction utilizing multiple small fans to provide a measure of redundancy in the event of failure.
2.2 CENTRIFUGAL FANS
• VA prefers direct drive motors if possible.
• Utility Fans should have access door and belt tensioner
23 37 00 - 2
2.2 AIR OUTLETS AND INLETS
• VA prefers aluminum or stainless steel for air outlets and inlets based on use case (ex:
stainless for operating rooms). Do not use non-stainless steel for outlets and inlets.
23 74 13 - 2
1.4 SUBMITTALS
• VA prefers a fan wall/fan array construction utilizing multiple small fans to provide a measure of redundancy in the event of failure.
23 74 13 - 6
2.1 ROOF TOP AIR HANDLING UNITS
• All 100% outside air units shall be constructed of aluminum
File details come from the government source that posted it. Updated .