This is an Amendment of Solicitation/Modification of Contract (Standard Form 30) issued by the Department of Veterans Affairs Network Contracting Office 8 (NCO 8) at the Orlando VA Healthcare System. Amendment 0003, effective May 26, 2026, provides responses to bidder questions for RFQ 36C24826Q0666. The questions and answers period is closed, and all quotes are due no later than June 3, 2026 at 3:00 PM EST. A site visit roster is attached to this amendment.

The amendment clarifies specifications for two air compressor replacement projects at the Orlando VA Healthcare System. For the Dental Clinic, the provided unit must meet or exceed the specifications of the current Powerex MPT1508 (Model Number: MPT1508s5122708), which operates from a 100-amp breaker on panel C0A2HN1 at 480v/277v. For the Hospital Lab Air Compressor, the correct model number is Powerex OPT050 (Model Number: MTD0504s5122708), a dual 5HP unit (total 10HP), not the MSED4006X5 as previously listed. Bidders may propose alternative equipment if it meets or exceeds all specifications. The VA will not accept open scroll compressors; only enclosed scroll systems qualify. Hot work (welding, cutting, brazing, soldering) requires permits and adherence to internal VA safety requirements, with the vendor responsible for providing fire extinguishers, fire watch, and hot work permits. Installation should occur during the clinic's closed hours from 4:00 PM Friday to 7:00 AM Monday, with a point of contact available 24/7. Pad modifications to accommodate equipment are the vendor's responsibility, and Building Automation System (BAS) integration points are limited to those downstream of the compressor controls.

View the file

Other files

File Type Posted
Site Visit Attendees.pdf PDF
36C24826Q0666 0002.pdf PDF
36C24826Q0666 0001.pdf PDF
36C24826Q0666.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

1 4

0003 05-26-2026

36C248

Department of Veterans Affairs Network Contracting Office 8 (NCO 8) Orlando VA Healthcare System 13800 Veterans Way Orlando FL 32827

36C248

Department of Veterans Affairs Network Contracting Office 8 (NCO 8) Orlando VA Healthcare System 13800 Veterans Way Orlando FL 32827

To all Offerors/Bidders

36C24826Q0666

05-08-2026

X

X X

See CONTINUATION Page

The purpose of this amendment is to provide responses to questions.

a. The questions and answer period is hereby closed.

b. Question and responses are on the continuation page.

c. The site visit roster is attached.

CONTINUATION PAGE

RFQ 36C24826Q0666 QUESTIONS & RESPONSES

Q1. Is the bid being extended?

A1. All quotes are due no later than 06/03/2026 at 3:00 PM EST.

Q2. The model that was selected is 80 HP (total) for the dental side. Currently, the total is 45HP so the electrical side would need to be upgraded. Can I propose the same HP in a SCROLL system that would match what is there with a smaller model that could use the existing electrical panel?

A2. The current system in the Clinic Building supplying air to the Dental Clinic is a Powerex MPT1508 (Model Number: MPT1508s5122708). The provided unit must meet or exceed the specifications of the current unit.

Q 3. The Lab air compressor has the Same model number as the Dental system in the RFQ?

A3. This is a typo. The model number of the Lab Air Compressor should be:

MTD0504s5122708.

Q4. Confirm the existing electrical breaker size for the clinical dental compressor?

A4. Current power for the Dental Compressor is fed from panel C0A2HN1, 480v/277v, ckt.7/9/11. It currently has a 100amp breaker in place.

Q5. Are there ICRA requirements for hot work in both mechanical rooms housing the compressors to be changed? If so, what level will be required and who is responsible for providing?

A5. All Hot Work (Welding, Cutting, Brazing, Soldering, etc.) that is required, is by permit only. Selected vendor will be required to adhere to all internal requirements for this work. This would include the appropriate fire extinguishers, fire watch, and Hot Work Permits. The COR would be responsible for coordinating with Safety Office and others internally. The Vendor would be required to provide everything else.

Q6. Advise on what is to be seen on the BAS interface in regard to the new compressors. Share required points to be pulled in and if there are any graphic updating requirements?

A6. All points to be viewed by the BAS are after the compressor controls and individual points in the line after the system. Current control panels that are physically on the unit are not connected to the BAS.

Q7. Can we receive a copy of the site visit sign in sheet?

A7. Yes. See attached site visit roster.

Q8. Will the VA allow any other compressors that are defined as or equal?

A8. Yes. If proposed equipment meets or exceeds all the specs of the proposed unit.

Q9. The enclosed PowereX MSED400X5 compressor footprint will not fit on the equipment pad detailed in the SOW for the Hospital Lab Air Compressor as 94”x54”x84” (LxWxH).?

A9. Available equipment pad Is the available space. Any required modifications to the pad to accommodate the equipment would be the burden of the vendor or contractor performing the installation.

Q10. The MSED4006X5 is listed on page 5 of the solicitation for both the Dental air and the Laboratory air. This configuration is fine for the dental air but is much too large for the lab air (footprint and HP)?

A10. This is a typo. The model numbers should be as follows for the current, existing equipment that is being replaced:

• Dental Clinic Compressor Powerex MPT1508 (Model Number:

MPT1508s5122708)

• Hospital Lab Air Compressor Powerex OPT050 (Model Number:

MTD0504s5122708)

Q11. The existing system is a duplex 7.5HP (total 15HP). The MSED is a duplex 20 HP (total 40HP). The existing laboratory air housekeeping pad is 94"x54"x84”.

There are NO enclosed scroll packages that will fit the housekeeping pad?

A11. The existing Hospital/Lab Air Compressor Powerex OPT050 (Model Number:

MTD0504s5122708). This is a dual 5hp (total 10HP) unit.

Q12. Although we are proposing an open scroll vs an enclosed scroll, it is still a SCROLL compressor.

A12. Will NOT accept open scroll for this requirement.

Q13. The attached LSE10-20-PREMIUM-2019 that has a smaller footprint & still will not fit on the Hospital Lab Air Compressor equipment pad?

A13. The existing pad for the Hospital/Lab Air is 94"x54"x84”. Available equipment pad Is the available space. Any required modifications to the pad to accommodate the equipment would be the burden of the vendor or contractor performing the installation.

Q14. What hours do the clinics operate? Will the installation be done after hours?

A14. The clinic closed from 4:00 PM on Fridays until 7:00 AM om Mondays. That is the preferred time for installations. POC is onsite24/7 to assist.

See attached document: Site Visit Attendees.