PHASE ONE-RFI Tracking Log.pdf
PDF 90 KB Posted
- Solicitation number
- 36C24823R0014
About this file
This document provides details for a federal solicitation seeking design-build services to address deficiencies at the Lake Nona Central Energy Plant. The Department of Veterans Affairs VISN 8 is soliciting proposals for a design-build project to repair and replace the roof system, ventilation system, and other deficiencies. The period of performance is 375 calendar days with a place of performance at the Orlando VA Healthcare System. The magnitude of the project is estimated between $2 million to $5 million. Offerors must be registered in SAM and VetBiz as a verified Service-Disabled Veteran-Owned Small Business. The solicitation will use a two-phase selection process and trade-off source selection method in accordance with FAR Parts 15 and 36.6. The point of contact is provided for any questions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24823R0014 0001.docx | DOCX document | |
| ATTACHMENT F - Past Performance Questionnaire.docx | DOCX document | |
| ATTACHMENT C - LIMITATION ON SUBCONTRACTING CERTIFICATION.pdf | ||
| ATTACHMENT E - Experience Information Sheet.pdf | ||
| ATTACHMENT A - DBA WD FL20220218 07.22.2022.pdf | ||
| ATTACHMENT B - Contract Progress Schedule.docx | DOCX document | |
| ATTACHMENT D - EMR.pdf | ||
| 36C24823R0014.docx | DOCX document | |
| SOLICITATION 36C24823R0014.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Request for Information (RFI) Tracking Log
Solicitation# 36C24823R0014 Project# 675-23-104
‘Design-Build Address Lake Nona Central Energy Plant (CEP) Deficiencies’ Phase One – Questions and Answers
November 22, 2022
RFI Tracking Log – Amendment 0002
RFI
NBR. QUESTIONS & ANSWERS SUBMITTED
BY
DATE
RECEIVED
1. Please provide a copy of the most recent FCA report for deficiency number 312826 (CEP Roofing) and number 382839 (CEP Exhaust Fan) and any other deficiencies relevant to the project.
KEE Solutions 11/22/2022
VA
Response
This report is not available. However, below is the description of findings.
Deficiency No. 312826 (CEP Roof) Description of Findings
Modified roof system in poor condition. Roof slope with insufficient cricketing ponds water against parapet walls. Additionally, the roof above the boiler plant is pock marked and damaged due to likely debris at significant level. This may lead to roof leakage prematurely. Replacement is necessary.
Deficiency No. 382839 (CEP Exhaust Fan) Description of Findings
Ventilation is provided by supply fans in lieu of exhaust fans, which affects the boiler operation and holds doors open within the secured facility.