36C24819Q0166

PAGE 1 OF

1. REQUISITION NO.

2. CONTRACT NO.

3. AWARD/EFFECTIVE DATE

4. ORDER NO.

5. SOLICITATION NUMBER

6. SOLICITATION ISSUE DATE

a. NAME

b. TELEPHONE NO. (No Collect Calls)

8. OFFER DUE DATE/LOCAL

TIME

9. ISSUED BY

CODE

10. THIS ACQUISITION IS

UNRESTRICTED OR

SET ASIDE:

% FOR:

SMALL BUSINESS

HUBZONE SMALL

BUSINESS

SERVICE-DISABLED

VETERAN-OWNED

SMALL BUSINESS

WOMEN-OWNED SMALL BUSINESS

(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED

SMALL BUSINESS PROGRAM

EDWOSB

8(A)

NAICS:

SIZE STANDARD:

11. DELIVERY FOR FOB DESTINA-

TION UNLESS BLOCK IS

MARKED

SEE SCHEDULE

12. DISCOUNT TERMS

13a. THIS CONTRACT IS A

RATED ORDER UNDER

DPAS (15 CFR 700)

13b. RATING

14. METHOD OF SOLICITATION

RFQ

IFB

RFP

15. DELIVER TO

CODE

16. ADMINISTERED BY

CODE

17a. CONTRACTOR/OFFEROR

CODE

FACILITY CODE

18a. PAYMENT WILL BE MADE BY

CODE

TELEPHONE NO.

DUNS:

DUNS+4:

PHONE:

FAX:

17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER 18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED

SEE ADDENDUM

19.

20.

21.

22.

23.

24.

ITEM NO.

SCHEDULE OF SUPPLIES/SERVICES

QUANTITY

UNIT

UNIT PRICE

AMOUNT

(Use Reverse and/or Attach Additional Sheets as Necessary)

25. ACCOUNTING AND APPROPRIATION DATA

26. TOTAL AWARD AMOUNT (For Govt. Use Only) 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED.

27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED

28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________

29. AWARD OF CONTRACT: REF. ___________________________________ OFFER

COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND

DATED ________________________________. YOUR OFFER ON SOLICITATION

DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY

(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE

ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED

SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:

30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER) 30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED

AUTHORIZED FOR LOCAL REPRODUCTION

(REV. 2/2012)

PREVIOUS EDITION IS NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.212

7. FOR SOLICITATION

INFORMATION CALL:

STANDARD FORM 1449

OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS

03-12-2019 Ana Regina Vazquez (ana.vazquez@va.gov)

305-575-3279 03-29-2019 2:00 p.m. EST 36C248 Department of Veterans Affairs Network Contracting Office (NCO) 8 Miami VA Healthcare System 1201 NW 16th Street Miami FL 33125

X

Y 238220 $15 Million

X

N/A

36C546

Department of Veterans Affairs Network Contracting Office 8 (NCO 8) Miami VA Healthcare System 1201 NW 16th Street Miami FL 33125

Department of Veterans Affairs Financial Services Center Customer Service P.O. Box 149971 Austin TX 78714-9971

Requirement: Damper Repair, Replacement, and Inspection

SITE VISIT

DATE: Tuesday, March 19, 2019

TIME: 9:00AM EST.

MEETING PLACE: Miami VA Healthcare System, Bruce W. Carter Medical Center, 1201 NW 16th Street, Miami, FL. – West Patio

RFI due by March 22, 2019, 4:00pm EST.

Table of Contents

SECTION A1
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS1
SECTION B - CONTINUATION OF SF 1449 BLOCKS3
B.1 CONTRACT ADMINISTRATION DATA3
B.2 PRICE/COST SCHEDULE - ITEM INFORMATION5
B.3 DELIVERY SCHEDULE5
B.4 PERFORMANCE WORK STATEMENT6
SECTION C - CONTRACT CLAUSES11
C.1 52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR EXECUTIVE ORDERS—COMMERCIAL ITEMS (OCT 2018)11
C.2 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)15
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS16
D.1 WAGE DETERMINATION16
D.2 DAMPER REPAIR LIST17
SECTION E - SOLICITATION PROVISIONS26
E.1 52.212-2 EVALUATION—COMMERCIAL ITEMS (OCT 2014)26
E.2 52.212-3 OFFEROR REPRESENTATIONS AND CERTIFICATIONS—COMMERCIAL ITEMS (NOV 2017)27
E.3 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE40
(FEB 1998)40
E.4 52.237-1 SITE VISIT (APRIL 1984)40

SECTION B - CONTINUATION OF SF 1449 BLOCKS

B.1 CONTRACT ADMINISTRATION DATA

1. Contract Administration: All contract administration matters will be handled by the following individuals:

a. CONTRACTOR:Name:
Address:
Phone:
DUNS:
TAX ID:
GOVERNMENT CONTRACT NUMBER:
b. GOVERNMENT:Ana Regina Vazquez, Contracting Officer
Miami VA Healthcare System
NCO- 8, Site Team Miami,
1201 NW 16th Street
Miami FL 33125

2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:

[X]52.232-34, Payment by Electronic Funds Transfer -
Other than Central Contractor Registration, or
[]52.232-36, Payment by Third Party

3. INVOICES: Invoices shall be submitted in arrears:

a. Quarterly []

b. Semi-Annually[]
c. Other[X]Net]

4. GOVERNMENT INVOICES: All invoices from the contractor shall be submitted electronically per 852.232-72 ELECTRONIC SUBMISSION OF PAYMENT REQUESTS (NOV 2012) enclosed in section C of this document. (See Web site at http://www.fsc.va.gov/einvoice.asp.)

a. Under this contract, unless otherwise delegated in writing to the Contracting Officer’s Representative (COR), the Contracting Officer is the only person authorized to approve changes or modify any of the requirements. The contractor shall communicate with the Contracting Officer on all matters pertaining to contract administration. Only the Contracting Officer is authorized to make commitments or issue changes which will affect price, quantity, or quality of, performance of this contract. In the event the contractor effects any such change at the direction, of any person other than the Contracting Officer, the change shall be considered to have been made without authority and no adjustment will be made in the contract price to cover any increase in costs incurred as a result thereof. The Contracting Officer is responsible for the overall administration of the contract.

b. Representatives of Contracting Officers in accordance with VAAR 852.270-1, January 2008: The Contracting Officer reserves the right to designate representative(s) to act for him/her in furnishing technical guidance and advice or generally supervise the work to be performed under this contract. Such designation will be in writing and will define the scope and limitations of the designee's authority. A copy of the designation shall be furnished to the contractor.

ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:

AMENDMENT NO DATE

________________________________
________________________________
________________________________

B.2 PRICE/COST SCHEDULE - ITEM INFORMATION

ITEM NUMBER
DESCRIPTION OF SUPPLIES SERVICES
QUANTITY
UNIT
UNIT PRICE
AMOUNT
0001
Provide applicable services, to one hundred eighty-two (182) Dampers sectors, identified in section “D”.
1.00
JB
0002
Final Inspection Report of all Medical Facility Smoke/Fire Dampers. Total of four hundred and thirty-eight (438).
1.00
JB
GRAND TOTAL
________________

B.3 DELIVERY SCHEDULE

ITEM NUMBER
QUANTITY
PERIOD OF PERFORMANCE
0001
1.00
6 MONTHS FROM TIME OF AWARD
0002
1.00
6 MONTHS FROM TIME OF AWARD

B.4 PERFORMANCE WORK STATEMENT

DAMPER REPAIR, REPLACEMENT, AND INSPECTION

1.0 INTRODUCTION

1.1 The Government requires services to the Medical Centers dampers and sectors. The service will consist of repairs, replacements, and inspections. The services will support the Bruce W. Carter Medical Center, Miami VA Healthcare System, Engineering Service. The contract is solicited as a firm fixed price.

2.0 DESCRIPTION SCOPE/OBJECTIVE

2.1 The objective of the service is to repair, replace, and inspect the medical facility’s damper system so that the system functions in accordance with its intended purpose.

2.2 The contractor shall provide all labor, equipment, tools, materials, supervision and all other items and services necessary to perform the work as defined in this Performance Work Statement (PWS).

3.0 APPLICABLE DOCUMENTS

3.1 The following laws, regulations, policies, and procedures in effect on date of contract issuance and all subsequent changes or updates may apply.

FAR
Federal Acquisition Regulation
VAAR
Veterans Administration Acquisition Regulation
NEMA
National Electrical Manufacturers Association
NEC
National Electric Code
ANSI
American National Standards Institute

ANSI/AIHA Z9.5–2012 - Laboratory Ventilation

AMCA
Air Movement and Control Association International, Inc.
SCA DOL Website
Service Contract Act (SCA) Directory of Occupations (Fifth Edition) http://www.dol.gov/whd/contracts/sca.htm
ASHRAE
HVAC Applications Handbook
Federal, State, Local, Industry, Manufacturer
All applicable federal, state, local, and industry: laws, codes, policies, procedures, standards, manufacturer’s specifications, and any other applicable doctrine for the intended performance of the equipment specified.

Other All equipment and installations(s) services shall conform to the VA master specifications (issued upon request). All equipment and installation shall conform to the recommendations of the National Fire Protection Association (NFPA), including the National Electrical Code (NEC). No departures from specification requirements will be permitted without written approval. All hardware should be installed in such a manner to minimize damage and maximize patient and employee safety. All equipment and procedures shall conform to OSHA, NEMA, and ANSI Standards as well as conform to the Standard Building Code(s) standard Mechanical Code.

3.2 GlossaryAcronyms used in this PWS are listed below for reference:
COContracting Officer
CORContracting Officer’s Representative
FARFederal Acquisition Regulation
QASPQuality Assurance Surveillance Plan
NFPANational Fire Protection Association

ASHRAE American Society of Heating, Refrigerating and Air Conditioning Engineers

I(s)Inside
O(s)Outside
ECDElectric Combination Damper
ESDElectric Smoke Damper
FDFire Damper
PCDPneumatic Combination Damper
PSDPneumatic Smoke Damper
TJCThe Joint Commission
HVACHeating, ventilation, and air conditioning
AQLAcceptance Quality Limit
OSHAOccupational Safety and Health Administration
NEMANational Emergency Management Association
ANSIAmerican National Standards Institute
NECNational Electrical Code

4.0 PERFORMANCE REQUIREMENTS

The Governments’ requirement is to correct the damper issues identified in section “D”. Total dampers sectors requiring services are one hundred and eighty-two (182). The resulting services will cover repairs, replacement, and inspections. Additionally, the Government requires the contractor to complete an overall inspection of the entire facility’s dampers and provide a written report that attests to the dampers performing in accordance with their intended control and balancing design.

4.1 Should the contractor locate issue(s) not identified herein, the contractor shall document and inform the COR. Services not identified herein shall not be repaired, unless a Contracting Officer has provided the proper approval for such.

4.1.2 The contractor shall provide services corresponding damper issues, noted in section “D” of this document in accordance with all federal, local, state or any other governing body – policy, procedure, legal or otherwise doctrine for the proper intended purpose.

4.2 TESTS/INSPECTIONS:

4.2.1The contractor shall perform corresponding tests to new and repaired dampers.
4.2.2The contractor shall complete an inspection of the entire facility’s dampers, four hundred and thirty-eight (438), and provide a written report that attests to the damper’s performance in accordance with their intended design. Test and Inspections shall be in accordance with local and state laws, and corresponding regulations as well as guidance from The Joint Commission. A list of all damper locations will be provided upon contract award.

4.3 PRIOR TO COMMENCEMENT:

4.3.1 At the Governments convenience, upon award, the contractor shall coordinate with the Government a post award site visit, all work shall commence immediately after.

4.4 REQUIRED CERTIFICATION:

4.4.1 The Contractor shall provide the HVAC certification of the person(s) performing service(s).

5.0 PERFORMANCE LOCATION AND HOURS:

5.1 Primary place of performance is the Bruce W. Carter Miami Veterans Affairs Medical Center, located at 1201 NW 16th Street, Miami, FL, 33125.

5.1.1 Government normal duty hours are from 07:30a.m. – 4:00 p.m. Monday through Friday.

5.2 All work will be subject to after hours and weekends, and possible Federal Holidays.

5.3 All work shall be coordinated with the COR and commence at the convenience of the Government.

6.0 DELIVERABLES:

6.1 The contractor shall provide any/all documentation to include inspection results and warranty for the work performed.

6.1 The contractor shall provide detailed report(s) of all inspections performed, that include the operational status, any/all finding(s), and the contractors recommendations for the equipment’s optimal operational results.

6.3 All documentation remains the sole property of the US Government.

6.4 The contractor shall submit HVAC certification(s) at the time proposals are due, submitted.

7.0 CONTRACTOR PERSONNEL AND MANAGEMENT.

7.1 Contractor Personnel. The Contractor shall be responsible for employing technically qualified personnel to perform the work specified in this PWS. The Contractor shall maintain the personnel, organization and administrative control necessary to ensure that the work delivered meets the contract specifications and requirements.

7.1.1 CONTRACTOR BADGES. Contractor personnel shall also wear a laminated contractor identification badge at all times when performing services under this Contract. The badge will contain a personal picture, name of employee, and Contractor's name. Badges shall be worn on the outer garment attached to the outer shirt or a jacket pocket by a button or clip or worn around the neck secured by an appropriate identification card lanyard.

7.2 SAFETY SECURITY REQUIREMENTS. The Contractor shall comply with all applicable federal, state and local laws and ensure performance is secure while protecting material, equipment, and supplies from damage and loss. Government security personnel shall have the express right to inspect for security violations at any time during the term of the contract.

7.3 All information generated in performance of this contract becomes property of the Government and must be surrendered upon request and/or completion of the contract. The Contractor must protect against the destruction and/or misplacement of all information produced under this contract, unless directed under local policy to destroy. This includes both hard and soft copies of data.

7.4 The Contractor shall not release any information (including photographs, files, public announcements, statements, denials, or confirmations) on any part of the subject matter of this contract or any phase of any program hereunder without the prior written approval of the COR.

7.5 STANDARDS OF CONDUCT

7.5.1 Conduct of Personnel. Contractor personnel shall conduct themselves in a professional manner (i.e. timeliness, communication; spoken and written etc.). The Contracting Officer may require the Contractor to remove from the job site any employee working under this contract for reasons of suspected misconduct, a suspected security breach, or suspected to be under the influence of alcohol, drugs, or any other incapacitating agent. Contractor employees shall be subject to dismissal from the premises upon determination by the Contracting Officer that such action is necessary in the interests of the Government. The hospital director or designated representative has the authority to bar individuals from the Government facility. The removal from the job site or dismissal from the premises shall not relieve the Contractor of the requirement to provide sufficient personnel to perform the services as required by this performance work statement. The Government shall not reimburse the Contractor for travel and other expenses associated with the removal of personnel.

7.5.2 Contractor personnel are not authorized to carry or possess personal weapons to include, but not limited to, firearms and knives with a blade length in excess of three inches, while assigned under this contract.

7.5.3 Working Attire and Appearance. Contractor personnel shall present a professional appearance commensurate with standards delineated for Government civilian personnel acting in similar capacities.

7.5.4 The Government reserves the right to review Contractor personnel qualifications. Upon request, resumes shall be provided to the Contracting Officer prior to clearance approval, for review and acceptance by the COR. The intent is verification purpose and not for the Government to become the hiring authority.

8.0 TRAVEL - Not applicable

9.0 NON-PERSONAL SERVICE STATEMENT

9.1 Contractor employees performing services under this order will be controlled, directed, and supervised at all times by management personnel of the contractor. Contractor management shall ensure that employees properly comply with the performance work standards outlined in the PWS. Contractor employees shall perform their duties independent of, and without the supervision of, any Government official. The tasks, duties, and responsibilities set forth in the contract may not be interpreted or implemented in any manner that results in any contractor employee creating or modifying Federal policy, obligating the appropriated funds of the United States Government, overseeing the work of Federal employees, providing direct personal services to any Federal employee, or otherwise violating the prohibitions set forth in Parts 7.5 and 37.1 of the Federal Acquisition Regulation (FAR). The Government will control access to the facility and will perform the inspection and acceptance of the completed work.

10.0 PERSONNEL QUALIFICATIONS

10.1 The work history of each contractor employee must contain experience directly related to the task and functions he/she is intended to perform under this contract. The Government reserves the right, during the life of the resulting contract, to request work history on any contractor employee for the purposes of verifying compliance with the above requirements; additionally, the Government reserves the right to review resumes of contractor personnel proposed to be assigned. Personnel assigned to, or utilized by, the Contractor in performance of work shall be fully capable of performing the requirements contained in the PWS in an efficient, reliable, and professional manner.

10.2 Specific Personnel Qualifications Requirements –Personnel assigned to or utilized by the contractor in the performance of this contract shall, as a minimum be certified to work on this equipment.

10.2.1 All Contractor personnel working on this contract must have a valid permission to work in the U.S.

11.0 PERFORMANCE STANDARDS AND QUALITY MEASUREMENT

11.1 Performance standards define desired services. The Government performs surveillance to determine if the Contractor exceeds, meets, or does not meet these standards. The Government shall use these standards to determine Contractor performance and shall compare Contractor performance to the Acceptable Quality Level (AQL). The Quality Assurance Surveillance Plan (QASP) method of surveillance will be by random inspection.

11.2 The QASP and its performance objectives are as follows:

PWS Para
Performance Objective
Performance

Standard

Acceptable Quality Level
Surveillance Method
Compliance

4.0

Service issues identified in section “D” of this document.
Ensure satisfactorily all requirements are met as stated in the PWS.
98% performance level
Visual inspection and system check conducted by the COR and/or appointee.
Below AQL, non-acceptance of services. A Contract Discrepancy Report (CDR), will be issued for performance below the AQL. The Contractor will have five workdays to provide a response that includes an improvement strategy for addressing the issues. 30 days after issuing the CDR, the Contractor will be re-rated. If performance does not comply with PWS, the CO will be notified, and the performance record will be documented, and CO may pursue contract action.
6.1
The contractor to provide supporting documentation.

Documents submitted timely and supporting requirement.

97% performance level

SECTION C - CONTRACT CLAUSES

C.1 52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR EXECUTIVE ORDERS—COMMERCIAL ITEMS (OCT 2018)

(a) The Contractor shall comply with the following Federal Acquisition Regulation (FAR) clauses, which are incorporated in this contract by reference, to implement provisions of law or Executive orders applicable to acquisitions of commercial items:

(1) 52.203-19, Prohibition on Requiring Certain Internal Confidentiality Agreements or Statements (JAN 2017) (section 743 of Division E, Title VII, of the Consolidated and Further Continuing Appropriations Act, 2015 (Pub. L. 113-235) and its successor provisions in subsequent appropriations acts (and as extended in continuing resolutions)).

(2) 52.209-10, Prohibition on Contracting with Inverted Domestic Corporations (NOV 2015).

(3) 52.233-3, Protest After Award (Aug 1996) (31 U.S.C. 3553).

(4) 52.233-4, Applicable Law for Breach of Contract Claim (Oct 2004) (Public Laws 108-77 and 108-78 (19 U.S.C. 3805 note)).

(b) The Contractor shall comply with the FAR clauses in this paragraph (b) that the Contracting Officer has indicated as being incorporated in this contract by reference to implement provisions of law or Executive orders applicable to acquisitions of commercial items:

[] (1) 52.203-6, Restrictions on Subcontractor Sales to the Government (Sept 2006), with Alternate I (Oct 1995) (41 U.S.C. 4704 and 10 U.S.C. 2402).

[] (2) 52.203-13, Contractor Code of Business Ethics and Conduct (OCT 2015) (41 U.S.C. 3509).

[] (3) 52.203-15, Whistleblower Protections under the American Recovery and Reinvestment Act of 2009 (JUN 2010) (Section 1553 of Pub. L. 111-5). (Applies to contracts funded by the American Recovery and Reinvestment Act of 2009.)

[X] (4) 52.204–10, Reporting Executive Compensation and First-Tier Subcontract Awards (OCT 2016) (Pub. L. 109–282) (31 U.S.C. 6101 note).

[] (5) [Reserved] [] (6) 52.204–14, Service Contract Reporting Requirements (OCT 2016) (Pub. L. 111–117, section 743 of Div. C).

[] (7) 52.204–15, Service Contract Reporting Requirements for Indefinite-Delivery Contracts (OCT 2016) (Pub. L. 111–117, section 743 of Div. C).

[] (8) 52.209-6, Protecting the Government's Interest When Subcontracting with Contractors Debarred, Suspended, or Proposed for Debarment. (OCT 2015) (31 U.S.C. 6101 note).

[] (9) 52.209-9, Updates of Publicly Available Information Regarding Responsibility Matters (Jul 2013) (41 U.S.C. 2313).

[] (10) [Reserved] [] (11)(i) 52.219-3, Notice of HUBZone Set-Aside or Sole-Source Award (NOV 2011) (15 U.S.C. 657a).

[] (ii) Alternate I (NOV 2011) of 52.219-3.

[X] (12)(i) 52.219-4, Notice of Price Evaluation Preference for HUBZone Small Business Concerns (OCT 2014) (if the offeror elects to waive the preference, it shall so indicate in its offer) (15 U.S.C. 657a).

[] (ii) Alternate I (JAN 2011) of 52.219-4.

[] (13) [Reserved] [X] (14)(i) 52.219-6, Notice of Total Small Business Set-Aside (NOV 2011) (15 U.S.C. 644).

[] (ii) Alternate I (NOV 2011).

[] (iii) Alternate II (NOV 2011).

[] (15)(i) 52.219-7, Notice of Partial Small Business Set-Aside (June 2003) (15 U.S.C. 644).

[] (ii) Alternate I (Oct 1995) of 52.219-7.

[] (iii) Alternate II (Mar 2004) of 52.219-7.

[X] (16) 52.219-8, Utilization of Small Business Concerns (NOV 2016) (15 U.S.C. 637(d)(2) and (3)).

[] (17)(i) 52.219-9, Small Business Subcontracting Plan (JAN 2017) (15 U.S.C. 637(d)(4)).

[] (ii) Alternate I (NOV 2016) of 52.219-9.

[] (iii) Alternate II (NOV 2016) of 52.219-9.

[] (iv) Alternate III (NOV 2016) of 52.219-9.

[] (v) Alternate IV (NOV 2016) of 52.219-9.

[] (18) 52.219-13, Notice of Set-Aside of Orders (NOV 2011) (15 U.S.C. 644(r)).

[] (19) 52.219-14, Limitations on Subcontracting (JAN 2017) (15 U.S.C. 637(a)(14)).

[] (20) 52.219-16, Liquidated Damages—Subcontracting Plan (Jan 1999) (15 U.S.C. 637(d)(4)(F)(i)).

[] (21) 52.219-27, Notice of Service-Disabled Veteran-Owned Small Business Set-Aside (NOV 2011) (15 U.S.C. 657f).

[X] (22) 52.219-28, Post Award Small Business Program Re-representation (Jul 2013) (15 U.S.C 632(a)(2)).

[] (23) 52.219-29, Notice of Set-Aside for, or Sole Source Award to, Economically Disadvantaged Women-Owned Small Business Concerns (DEC 2015) (15 U.S.C. 637(m)).

[] (24) 52.219-30, Notice of Set-Aside for, or Sole Source Award to, Women-Owned Small Business Concerns Eligible Under the Women-Owned Small Business Program (DEC 2015) (15 U.S.C. 637(m)).

[X] (25) 52.222-3, Convict Labor (June 2003) (E.O. 11755).

[] (26) 52.222–19, Child Labor—Cooperation with Authorities and Remedies (OCT 2016) (E.O. 13126).

[X] (27) 52.222-21, Prohibition of Segregated Facilities (APR 2015).

[X] (28) 52.222–26, Equal Opportunity (SEP 2016) (E.O. 11246).

[] (29) 52.222-35, Equal Opportunity for Veterans (OCT 2015) (38 U.S.C. 4212).

[X] (30) 52.222-36, Equal Opportunity for Workers with Disabilities (JUL 2014) (29 U.S.C. 793).

[] (31) 52.222-37, Employment Reports on Veterans (FEB 2016) (38 U.S.C. 4212).

[] (32) 52.222-40, Notification of Employee Rights Under the National Labor Relations Act (DEC 2010) (E.O. 13496).

[X] (33)(i) 52.222-50, Combating Trafficking in Persons (MAR 2015) (22 U.S.C. chapter 78 and E.O. 13627).

[] (ii) Alternate I (MAR 2015) of 52.222-50 (22 U.S.C. chapter 78 and E.O. 13627).

[] (34) 52.222-54, Employment Eligibility Verification (OCT 2015). (E. O. 12989). (Not applicable to the acquisition of commercially available off-the-shelf items or certain other types of commercial items as prescribed in 22.1803.)

[] (35) 52.222-59, Compliance with Labor Laws (Executive Order 13673) (OCT 2016). (Applies at $50 million for solicitations and resultant contracts issued from October 25, 2016 through April 24, 2017; applies at $500,000 for solicitations and resultant contracts issued after April 24, 2017).

Note to paragraph (b)(35): By a court order issued on October 24, 2016, 52.222-59 is enjoined indefinitely as of the date of the order. The enjoined paragraph will become effective immediately if the court terminates the injunction. At that time, DoD, GSA, and NASA will publish a document in the Federal Register advising the public of the termination of the injunction.

[] (36) 52.222-60, Paycheck Transparency (Executive Order 13673) (OCT 2016).

[] (37)(i) 52.223-9, Estimate of Percentage of Recovered Material Content for EPA-Designated Items (May 2008) (42 U.S.C.6962(c)(3)(A)(ii)). (Not applicable to the acquisition of commercially available off-the-shelf items.)

[] (38) 52.223-11, Ozone-Depleting Substances and High Global Warming Potential Hydrofluorocarbons (JUN 2016) (E.O. 13693).

[] (39) 52.223-12, Maintenance, Service, Repair, or Disposal of Refrigeration Equipment and Air Conditioners (JUN 2016) (E.O. 13693).

[] (ii) Alternate I (MAY 2008) of 52.223-9 (42 U.S.C. 6962(i)(2)(C)). (Not applicable to the acquisition of commercially available off-the-shelf items.)

[] (40)(i) 52.223-13, Acquisition of EPEAT®-Registered Imaging Equipment (JUN 2014) (E.O.s 13423 and 13514).

[] (ii) Alternate I (OCT 2015) of 52.223-13.

[] (41)(i) 52.223-14, Acquisition of EPEAT®-Registered Televisions (JUN 2014) (E.O.s 13423 and 13514).

[] (ii) Alternate I (JUN 2014) of 52.223-14.

[] (42) 52.223-15, Energy Efficiency in Energy-Consuming Products (DEC 2007)(42 U.S.C. 8259b).

[] (43)(i) 52.223-16, Acquisition of EPEAT®-Registered Personal Computer Products (OCT 2015) (E.O.s 13423 and 13514).

[] (ii) Alternate I (JUN 2014) of 52.223-16.

[X] (44) 52.223-18, Encouraging Contractor Policies to Ban Text Messaging While Driving (AUG 2011) [] (45) 52.223-20, Aerosols (JUN 2016) (E.O. 13693).

[] (46) 52.223-21, Foams (JUN 2016) (E.O. 13693).

[] (47) (i) 52.224-3, Privacy Training (JAN 2017) (5 U.S.C. 552a).

[] (ii) Alternate I (JAN 2017) of 52.224-3.

[] (48) 52.225-1, Buy American—Supplies (MAY 2014) (41 U.S.C. chapter 83).

[] (49)(i) 52.225-3, Buy American—Free Trade Agreements—Israeli Trade Act (MAY 2014) (41 U.S.C. chapter 83, 19 U.S.C. 3301 note, 19 U.S.C. 2112 note, 19 U.S.C. 3805 note, 19 U.S.C. 4001 note, Pub. L. 103-182, 108-77, 108-78, 108-286, 108-302, 109-53, 109-169, 109-283, 110-138, 112-41, 112-42, and 112-43.

[] (ii) Alternate I (MAY 2014) of 52.225-3.

[] (iii) Alternate II (MAY 2014) of 52.225-3.

[] (iv) Alternate III (MAY 2014) of 52.225-3.

[] (50) 52.225–5, Trade Agreements (OCT 2016) (19 U.S.C. 2501, et seq., 19 U.S.C. 3301 note).

[X] (51) 52.225-13, Restrictions on Certain Foreign Purchases (JUN 2008) (E.O.'s, proclamations, and statutes administered by the Office of Foreign Assets Control of the Department of the Treasury).

[] (52) 52.225–26, Contractors Performing Private Security Functions Outside the United States (OCT 2016) (Section 862, as amended, of the National Defense Authorization Act for Fiscal Year 2008; 10 U.S.C. 2302 Note).

[] (53) 52.226-4, Notice of Disaster or Emergency Area Set-Aside (Nov 2007) (42 U.S.C. 5150).

[] (54) 52.226-5, Restrictions on Subcontracting Outside Disaster or Emergency Area (Nov 2007) (42 U.S.C. 5150).

[] (55) 52.232-29, Terms for Financing of Purchases of Commercial Items (Feb 2002) (41 U.S.C. 4505, 10 U.S.C. 2307(f)).

[] (56) 52.232-30, Installment Payments for Commercial Items (JAN 2017) (41 U.S.C. 4505, 10 U.S.C. 2307(f)).

[] (57) 52.232-33, Payment by Electronic Funds Transfer—System for Award Management (Jul 2013) (31 U.S.C. 3332).

[X] (58) 52.232-34, Payment by Electronic Funds Transfer—Other than System for Award Management (Jul 2013) (31 U.S.C. 3332).

[] (59) 52.232-36, Payment by Third Party (MAY 2014) (31 U.S.C. 3332).

[] (60) 52.239-1, Privacy or Security Safeguards (Aug 1996) (5 U.S.C. 552a).

[] (61) 52.242-5, Payments to Small Business Subcontractors (JAN 2017)(15 U.S.C. 637(d)(12)).

[] (62)(i) 52.247-64, Preference for Privately Owned U.S.-Flag Commercial Vessels (Feb 2006) (46 U.S.C. Appx. 1241(b) and 10 U.S.C. 2631).

[] (ii) Alternate I (Apr 2003) of 52.247-64.

(c) The Contractor shall comply with the FAR clauses in this paragraph (c), applicable to commercial services, that the Contracting Officer has indicated as being incorporated in this contract by reference to implement provisions of law or Executive orders applicable to acquisitions of commercial items:

[] (1) 52.222-17, Non-displacement of Qualified Workers (MAY 2014) (E.O. 13495).

[X] (2) 52.222-41, Service Contract Labor Standards (MAY 2014) (41 U.S.C. chapter 67).

[] (3) 52.222-42, Statement of Equivalent Rates for Federal Hires (MAY 2014) (29 U.S.C. 206 and 41 U.S.C. chapter 67).

[] (4) 52.222-43, Fair Labor Standards Act and Service Contract Labor Standards—Price Adjustment (Multiple Year and Option Contracts) (MAY 2014) (29 U.S.C. 206 and 41 U.S.C. chapter 67).

[X] (5) 52.222-44, Fair Labor Standards Act and Service Contract Labor Standards—Price Adjustment (MAY 2014) (29 U.S.C 206 and 41 U.S.C. chapter 67).

[X] (6) 52.222-51, Exemption from Application of the Service Contract Labor Standards to Contracts for Maintenance, Calibration, or Repair of Certain Equipment—Requirements (MAY 2014) (41 U.S.C. chapter 67).

[] (7) 52.222-53, Exemption from Application of the Service Contract Labor Standards to Contracts for Certain Services—Requirements (MAY 2014) (41 U.S.C. chapter 67).

[X] (8) 52.222-55, Minimum Wages Under Executive Order 13658 (DEC 2015).

[X] (9) 52.222-62, Paid Sick Leave Under Executive Order 13706 (JAN 2017) (E.O. 13706).

[] (10) 52.226-6, Promoting Excess Food Donation to Nonprofit Organizations (MAY 2014) (42 U.S.C. 1792).

[X] (11) 52.237-11, Accepting and Dispensing of $1 Coin (SEP 2008) (31 U.S.C. 5112(p)(1)).

(d) Comptroller General Examination of Record. The Contractor shall comply with the provisions of this paragraph (d) if this contract was awarded using other than sealed bid, is in excess of the simplified acquisition threshold, and does not contain the clause at 52.215-2, Audit and Records—Negotiation.

(1) The Comptroller General of the United States, or an authorized representative of the Comptroller General, shall have access to and right to examine any of the Contractor's directly pertinent records involving transactions related to this contract.

(2) The Contractor shall make available at its offices at all reasonable times the records, materials, and other evidence for examination, audit, or reproduction, until 3 years after final payment under this contract or for any shorter period specified in FAR Subpart 4.7, Contractor Records Retention, of the other clauses of this contract. If this contract is completely or partially terminated, the records relating to the work terminated shall be made available for 3 years after any resulting final termination settlement. Records relating to appeals under the disputes clause or to litigation or the settlement of claims arising under or relating to this contract shall be made available until such appeals, litigation, or claims are finally resolved.

(3) As used in this clause, records include books, documents, accounting procedures and practices, and other data, regardless of type and regardless of form. This does not require the Contractor to create or maintain any record that the Contractor does not maintain in the ordinary course of business or pursuant to a provision of law.

(e)(1) Notwithstanding the requirements of the clauses in paragraphs (a), (b), (c), and (d) of this clause, the Contractor is not required to flow down any FAR clause, other than those in this paragraph (e)(1) in a subcontract for commercial items. Unless otherwise indicated below, the extent of the flow down shall be as required by the clause—

(i) 52.203-13, Contractor Code of Business Ethics and Conduct (OCT 2015) (41 U.S.C. 3509).

(ii) 52.203-19, Prohibition on Requiring Certain Internal Confidentiality Agreements or Statements (JAN 2017) (section 743 of Division E, Title VII, of the Consolidated and Further Continuing Appropriations Act, 2015 (Pub. L. 113-235) and its successor provisions in subsequent appropriations acts (and as extended in continuing resolutions)).

(iii) 52.219-8, Utilization of Small Business Concerns (NOV 2016) (15 U.S.C. 637(d)(2) and (3)), in all subcontracts that offer further subcontracting opportunities.

(iv) 52.222-17, No displacement of Qualified Workers (MAY 2014) (E.O. 13495). Flow down required in accordance with paragraph (l) of FAR clause 52.222-17.

(v) 52.222-21, Prohibition of Segregated Facilities (APR 2015).

(vi) 52.222–26, Equal Opportunity (SEP 2016) (E.O. 11246).

(vii) 52.222-35, Equal Opportunity for Veterans (OCT 2015) (38 U.S.C. 4212).

(viii) 52.222-36, Equal Opportunity for Workers with Disabilities (JUL 2014) (29 U.S.C. 793).

(ix) 52.222-37, Employment Reports on Veterans (FEB 2016) (38 U.S.C. 4212).

(x) 52.222-40, Notification of Employee Rights Under the National Labor Relations Act (DEC 2010) (E.O. 13496). Flow down required in accordance with paragraph (f) of FAR clause 52.222-40.

(xi) 52.222-41, Service Contract Labor Standards (MAY 2014) (41 U.S.C. chapter 67).

(xii)(A) 52.222-50, Combating Trafficking in Persons (MAR 2015) (22 U.S.C. chapter 78 and E.O. 13627).

(B) Alternate I (MAR 2015) of 52.222-50 (22 U.S.C. chapter 78 and E.O. 13627).

(xiii) 52.222-51, Exemption from Application of the Service Contract Labor Standards to Contracts for Maintenance, Calibration, or Repair of Certain Equipment—Requirements (MAY 2014) (41 U.S.C. chapter 67).

(xiv) 52.222-53, Exemption from Application of the Service Contract Labor Standards to Contracts for Certain Services—Requirements (MAY 2014) (41 U.S.C. chapter 67).

(xv) 52.222-54, Employment Eligibility Verification (OCT 2015) (E. O. 12989).

(xvi) 52.222-55, Minimum Wages Under Executive Order 13658 (DEC 2015).

(xvii) 52.222-59, Compliance with Labor Laws (Executive Order 13673) (OCT 2016) (Applies at $50 million for solicitations and resultant contracts issued from October 25, 2016 through April 24, 2017; applies at $500,000 for solicitations and resultant contracts issued after April 24, 2017).

Note to paragraph (e)(1)(xvii): By a court order issued on October 24, 2016, 52.222-59 is enjoined indefinitely as of the date of the order. The enjoined paragraph will become effective immediately if the court terminates the injunction. At that time, DoD, GSA, and NASA will publish a document in the Federal Register advising the public of the termination of the injunction.

(xviii) 52.222-60, Paycheck Transparency (Executive Order 13673) (OCT 2016)).

(xix) 52.222-62 Paid Sick Leave Under Executive Order 13706 (JAN 2017) (E.O. 13706).

(xx)(A) 52.224-3, Privacy Training (JAN 2017) (5 U.S.C. 552a).

(B) Alternate I (JAN 2017) of 52.224-3.

(xxi) 52.225–26, Contractors Performing Private Security Functions Outside the United States (OCT 2016) (Section 862, as amended, of the National Defense Authorization Act for Fiscal Year 2008; 10 U.S.C. 2302 Note).

(xxii) 52.226-6, Promoting Excess Food Donation to Nonprofit Organizations (MAY 2014) (42 U.S.C. 1792). Flow down required in accordance with paragraph (e) of FAR clause 52.226-6.

(xxiii) 52.247-64, Preference for Privately Owned U.S.-Flag Commercial Vessels (Feb 2006) (46 U.S.C. Appx. 1241(b) and 10 U.S.C. 2631). Flow down required in accordance with paragraph (d) of FAR clause 52.247-64.

(2) While not required, the Contractor may include in its subcontracts for commercial items a minimal number of additional clauses necessary to satisfy its contractual obligations.

(End of Clause)

C.2 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)

This contract incorporates one or more clauses by reference, with the same force and effect as if they were given in full text. Upon request, the Contracting Officer will make their full text available. Also, the full text of a clause may be accessed electronically at this/these address(es):

http://www.acquisition.gov/far/index.html http://www.va.gov/oal/library/vaar/

(End of Clause)

Page 1 of

Page 1 of

FAR Number
Title
Date
52.212-4
CONTRACT TERMS AND CONDITIONS—COMMERCIAL ITEMS
OCT 2018
52.219-4
LIMITATIONS ON SUBCONTRACTING
JAN 2017
52.228-5
INSURANCE—WORK ON A GOVERNMENT INSTALLATION
JAN 1997
52.236-9
PROTECTION OF EXISTING VEGETATION, STRUCTURES, EQUIPMENT, UTILITIES, AND IMPROVEMENTS
APR 1984
52.236-12
CLEANING UP
APR 1984
852.203-70
COMMERCIAL ADVERTISING
MAY 2018
852.215-70
SERVICE-DISABLED VETERAN-OWNED AND VETERAN-OWNED SMALL BUSINESS EVALUATION FACTORS (DEVIATION)
JUL 2016
852.232-72
ELECTRONIC SUBMISSION OF PAYMENT REQUESTS
NOV 2018
852.237-70
CONTRACTOR RESPONSIBILITIES
APR 1984

SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS

Page 1 of

D.1 WAGE DETERMINATION

The DOL Wage Determination for the specific locality applies to this solicitation and any contract awarded is available at www.wdol.gov. Please note the listing below is not all inclusive wage determination of each area of performance. It is the contractor’s responsibility to obtain and evaluate each wage determination locality.

WD 15-4543 (Rev.-10) was first posted on www.wdol.gov on 01/01/2019 https://wdol.gov/sca.aspx

D.2 DAMPER REPAIR LIST

Damper Repair List - Miami VA Health Care - Miami, FL
LEGEND:
EFD: Electric Fire Damper
ECD: Electric Combination Damper
PCD: Pneumatic Combination Damper
ESD: Electric Smoke Damper
FD: Fire Damper
PSD: Pneumatic Smoke Damper

FRFD: Fire Rated Flanged Door

Building
Floor
Location
Damper Type
Damper ID
Diagnosis
1
7
5
I/S Mechanical Room 18 (DTF)
FD
1107
Dampers 1106 through 1109 are in the same duct.

· 1107 has a broken spring.

· 1108 and 1109 can't be reached through current door.

· 1108 has a twisted spring and it doesn't close.

· 1109 closed about 90 percent. The springs are rusty, and it won't fully close.

2
7
5
I/S Mechanical Room 18 (DTF)
FD
1108
3
7
5
I/S Mechanical Room 18 (DTF)
FD
1109
4
7
5
I/S Mechanical Room 18 (DTF)
FD
1111
Dampers 1110 through 1113 are in the same duct.

· 1111 through 1113 all have broken springs.

5
7
5
I/S Mechanical Room 18 (DTF)
FD
1112
6
7
5
I/S Mechanical Room 18 (DTF)
FD
1113
7
7
5
I/S Mechanical Room 18 (DTF)
FD
1114
Dampers 1114 through 1117 are in the same duct.

· 1114 doesn't close fully.

8
7
3
I/S Storage Room 326 (DTF)
FD
1144
Dampers 1139 through 1144 are in the same duct.

· Back left damper doesn't fully close. Scrapes against track.

9
7
1
I/S Electrical Room front wall
FD
397
Large gap on bottom between duct and damper.

· issue can be fixed without replacing with a new damper.

10
10
4
I/S Room NH441 left wall
PSD
350
· No air, and linkage disconnected.
11
10
4
I/S Room NH461 back wall
PCD
373
· No air, and linkage disconnected.
12
10
4
I/S Room M4 1 10 (DTF)
FD
1137
1137 and 1138 are in the same duct.

· Both have broken springs and the dampers won't close.

13
10
4
I/S Room M4 1 10 (DTF)
FD
1138
1137 and 1138 are in the same duct.

· Both have broken springs and the dampers won't close.

14
10
3
Above D/D's by Room CLC316
PSD
353
· No air.
15
10
3
I/S Room NH361
PSD
358
· No air.
16
10
3
I/S Room CLC341
PSD
360
· No air.
17
10
2
Above D/D's by Room CLC212
ESD
362
· Motor is not connected to the damper and the damper is more than 24" from a wall.
18
10
2
O/S Reef Cafe CLC263 above door
ESD
369
· No power to Motor.
19
10
2
I/S Soiled Utility Room CLC260
ESD
371
· No power to Motor.
20
10
2
I/S Mechanical Room M2 3 10 (DTF)
FD
1197
· Spring is broken.
21
10
2
I/S Room CLC 241 left wall
ESD
1210
· Has power. Bad multi products motor, UL6 2781A.
22
10
1
Above D/D's by Room CLC120
ESD
377
· No power to Motor.
23
10
1
Above D/D's by Room CLC120
ESD
378
· Damper has a wire tie wrapped around it so it won't close.
24
10
1
I/S Room CLC161
ESD
381
· Has power, but damper is closed. Bad motor. M436A 1116
25
10
1
I/S Room CLC141
ESD
382
· Has power, but damper is closed.

· Bad motor. M436A 1116

26
10
1
I/S Room CLC118 back wall
ESD
1161
· Has power. Didn't move when electrician removed power.

· Bad motor M436A 1116

27
10
1
O/S Mechanical Room M1 410
FD
1175
· Access door is blocked by pipes. No other place for another door.
28
10
1
I/S AHU 3 Room
PSD
1177
· Linkage is disconnected.
29
10
1
I/S AHU 3 Room
PSD
1178
· Linkage is disconnected.
30
Main
14
I/S Elevator Machine Room
PSD
1012
· Damper does not fully close.
31
Main
13
O/S on Roof (DTF)
FD
1000
· Damper is not in the plane of the floor/wall.
32
Main
13
O/S on Roof (DTF)
FD
1001
· Damper is not in the plane of the floor/wall.
33
Main
13
O/S on Roof (DTF)
FD
1002
· Damper is not in the plane of the floor/wall.
34
Main
13
O/S on Roof (DTF)
FD
1003
· Damper is not in the plane of the floor/wall.
35
Main
13
O/S on Roof (DTF)
FD
1004
· Damper is not in the plane of the floor/wall.
36
Main
13
O/S on Roof (DTF)
FD
1005
· Damper is not in the plane of the floor/wall.
37
Main
13
O/S on Roof (DTF)
FD
1006
· Damper is not in the plane of the floor/wall.
38
Main
12
D/D's by Room A1201
PCD
112
· Does not close when link is removed;

· and would not re open with air.

39
Main
12
Across from Room B1237
FD
115
· Manual damper in front of Fire Damper.

· Issuing reaching

40
Main
12
Across from Room B1237
FD
116
· Damper is rusty. Link removed, and the damper didn't move. Tight area to replace apparatus.
41
Main
12
I/S Room B1209
FD
154
· Gravity damper seems to be installed upside down. Tight areas to replace damper.
42
Main
12
I/S Restroom B1201 Shaft
FD
1010
· Door installed seems to be on the wrong side, possible issue installing door on the opposite side since there is a shaft there.
43
Main
11
I/S Room B1114
PCD
118
· Linkage snapped.
44
Main
11
Across from Room B1138
FD
1015
· Door could be installed on wrong side of the wall and there could be an issue reaching link through the current door. Possible limitations for installing a larger door. (On the other side there is a shaft).
45
Main
11
I/S Room B1114
PCD
1016
· Linkage snapped.
46
Main
11
I/S Room B1113.A
PCD
1017
· No air.
47
Main
10
Above D/D's by Room A1001
PCD
130
· Linkage is unhooked tight area.
48
Main
10
Across from Room B1008
FD
131
· Damper locks on opposite side, shaft on other on side of the wall. If the damper closes there is a possibility it cannot reopen.
49
Main
10
Across from Room B1008
PCD
133
· Seems that there is no linkage connecting the pump to the shaft.

(No information on the pump to order a new one.)

· Has air and would function with a new pump/linkage.

50
Main
10
I/S Room B1015
PCD
1021
· Linkage is snapped off. Tight space to replace pump/linkage.
51
Main
10
I/S Room B1015
PCD
1022
· Linkage is disconnected.
52
Main
9
Across from Room B938
FD
137
· Damper is rusty and doesn't move when the link is removed.
53
Main
9
I/S Soiled Utility Room B915
PCD
141
· Linkage is either snapped or disconnected.
54
Main
9
I/S Patient Education Center C901
PCD
159
· Pump doesn’t seem to be connected and the damper is being held open with a wire tie. Damper should work if the pump and linkage are hooked back up.
55
Main
8
I/S Storage Room by Waiting Area C814
PCD
148
· Damper does not function properly.
56
Main
8
I/S Storage Room by Waiting Area C814
PCD
149
· Linkage is disconnected, and dampers seem to be held open with springs.
57
Main
8
I/S Recreation Therapy Staff Room B815
PCD
1032
· Linkage is disconnected. Damper fail.
58
Main
8
I/S Recreation Therapy Staff Room B815
PCD
1033
· Linkage is disconnected. Damper fail.
59
Main
8
I/S Recreation Therapy Staff Room B815
PCD
1034
· Linkage is disconnected. Damper fail.
60
Main
7
I/S C701 Pain Clinic Check In
PCD
1082
· Linkage and pump is disconnected from the shaft. Use of a wire tie keeps it opened.
61
Main
7
I/S C701 Pain Clinic Check In
PCD
1083
· Damper needs to be adjusted. Doesn't close or open as it should. Tight fit.
62
Main
6
Across from Room B639
FD
156
· Damper is rusty and doesn't fully close. Has a 4x8" door and it's a 30" duct. Can't clean or see why it won't close. Tight area to replace damper.
63
Main
6
I/S Break Room by C601A
PCD
171
· Linkage needs to be adjusted, tight fit.
64
Main
6
I/S Break Room by C601A
PCD
172
· Linkage and pump are disconnected from the shaft.
65
Main
6
I/S Break Room by C601A
PCD
175
· Broken bar type fusible links. Hinged access panel in ceiling hits shelving.

· Shelves might need to be moved to get better access to the duct area and replace the broken links.

66
Main
6
I/S B616 Soiled Utility Room
PCD
408
· Pump and linkage are disconnected from the shaft.
67
Main
6
I/S B616 Soiled Utility Room
PCD
409
· Damper closes but cannot reopen. Tight area. Should be able to fix with adjustments to the linkage.
68
Main
6
Above D/D's by Soiled Utility Room B616
PCD
1084
· Pump and linkage are disconnected, and the damper is propped open.
69
Main
5
I/S Medication Room by Nurse Station
PCD
180
· No air, and the linkage is disconnected.
70
Main
5
I/S Room B512
FD
1091
· Damper is not at the wall.
71
Main
4
Above D/D's by Room A401
PCD
182
· No air.
72
Main
4
I/S Room B412 back wall
FD
194
· Fire damper locks on opposite side. If it closes it is hard to reopen. On the other side there is a shaft.
73
Main
4
I/S Shaft Behind Restroom B401
PCD
1097
· Possibly needs 14x14 FRFD;

· and a 12" access door on opposite side of the wall.

The pump is on the opposite side and to test one needs to get the pneumatic line.

74
Main
4
Above D/D's by Office B437
PCD
1166
Access door is blocked by pipes.

· Issue with placing a door.

75
Main
4
Above D/D's by Office B437
PCD
1167
Has access door but it is currently blocked by pipes.

· Requires a 7-9" round door.

76
Main
3
I/S Room C302B24
ECD
195
· No power.
77
Main
3
I/S Room C302B24
ECD
196
· No power.
78
Main
3
O/S Room C302B24
ECD
197
· No power.

· Needs 24" round door.

79
Main
3
I/S Room M3 161
ECD
198
· No power.
80
Main
3
O/S Mechanical Room C302B25
ECD
199
· No power, and motor is old. Motor UL6 2781A
81
Main
3
O/S Mechanical Room C302B25
ECD
200
· No power, and motor is old. Motor UL6 2781A
82
Main
3
I/S Mechanical Room on Roof (DTF)
FD
232
· Damper is not at the floor.
83
Main
3
On Roof (DTF)
PSD
1035
· No air and the shaft are rusted, might not pass an inspection.
84
Main
3
On Roof (DTF)
PSD
1036
· No air and the shaft are rusted, might not pass an inspection.
85
Main
3
On Roof (DTF)
FD
1037
· Damper is not at the floor.
86
Main
3
On Roof (DTF)
FD
1038
· Damper is not at the floor.
87
Main
3
On Roof (DTF)
PCD
1039
· No air and the linkage are disconnected.
88
Main
3
On Roof (DTF)
PCD
1040
· No air and the linkage are disconnected.
89
Main
3
On Roof (DTF)
PCD
1041
· No air and the linkage are disconnected.
90
Main
3
On Roof (DTF)
FD
1042
· Damper is not at the floor.
91
Main
3
On Roof (DTF)
FD
1043
· Damper is not at the floor.
92
Main
3
On Roof (DTF)
FD
1044
· Damper is not at the floor.
93
Main
3
On Roof (DTF)
FD
1045
· Damper is not at the floor.
94
Main
3
On Roof (DTF)
FD
1046
· Damper is not at the floor.
95
Main
3
On Roof (DTF)
FD
1047
· Damper is not at the floor.
96
Main
3
On Roof (DTF)
ESD
1048
· No power and damper have a very large gap. (2" plus)
97
Main
3
On Roof (DTF)
FD
1049
· Damper is not at the floor.
98
Main
3
On Roof (DTF)
FD
1050
· Damper is not at the floor.
99
Main
3
On Roof (DTF)
FD
1051
· Damper is not at the floor.
100
Main
3
On Roof (DTF)
ESD
1052
· No power.
101
Main
3
I/S Mechanical Room on Roof (DTF)
FD
1053
· Damper is not at the floor.
102
Main
3
I/S Mechanical Room C302B25
ECD
1081
· Needs new motor. Multipurpose UL6 2781A
103
Main
3
Above D/D's by Radiation Safety C302B23
ECD
1158
· No power.
104
Main
3
Above D/D's by Radiation Safety C302B23
ECD
1159
· No power.
105
Main
3
I/S Room C302B23 above door
ECD
1221
· No power.
106
Main
2
O/S Room 2A150C12 above door
FD
1198
Same duct as damper 236.

· Needs (1) custom 26x16 door.

107
Main
2
O/S Room 2A150C12 above door
FD
236
108
Main
2
O/S Room A207L
FD
241
Current door is blocked by pipes.

· Needs additional 14x14.

Tight fit.

109
Main
2
I/S Room A207H
FD
242
· At least 10 tiles/ceiling grid may have to be removed to inspect damper.
110
Main
2
I/S Gift Shop Storage Room B208
FD
243
· Has a 10" FRFD hard to reach damper, and a larger FRFD might not fit since the ceiling is reinforced with concrete.
111
Main
2
I/S Release of Medical Information 2E100
ECD
244
· No power.
112
Main
2
I/S Mechanical Room 2B135 (DTF)
PCD
1179
· Linkage is disconnected.
113
Main
2
I/S Mechanical Room 2B135 (DTF)
PCD
1180
· Linkage is disconnected.
114
Main
2
I/S Mechanical Room 2B135 (DTF)
PCD
1181
· Linkage is disconnected.
115
Main
2
I/S Mechanical Room 2B135 (DTF)
PCD
1182
· Linkage is disconnected.
116
Main
2
I/S Mechanical Room 2B135 (DTF)
PCD
1183
· Installed 8x8 access door. Damper fail.

· No air.

117
Main
2
Above D/D's by Room 2C151
ECD
1186
· No power to Motor.
118
Main
2
Above D/D's by Room 2C151
ECD
1187
· No power to Motor.
119
Main
2
I/S Eye Glasses A200
PCD
1225
· No air.
120
Main
2
I/S Dishwashing B218A above D/D's