36C24818R0587-001.docx

DOCX document 14 KB Posted

Attached to
A-E Design - Correct Architectural FCA Deficiencies - Roofs Federal contract opportunity
Solicitation number
36C24818R0587
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

36C24818R0587 36C24818R0587_1.docx

View the file

Other files for this federal contract opportunity

Other files attached to A-E Design - Correct Architectural FCA Deficiencies - Roofs, newest first.
File Type Posted
36C24818R0587-000.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FedBizOpps Modification to a Previous Notice

CLASSIFICATION CODE

SUBJECT

CONTRACTING OFFICE'S

ZIP-CODE

SOLICITATION NUMBER

BASE NOTICE TYPE

RESPONSE DATE (MM-DD-YYYY)

ARCHIVE

DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS

SET-ASIDE

NAICS CODE

CONTRACTING OFFICE

ADDRESS

POINT OF CONTACT

(POC Information Automatically Filled from User Profile Unless Entered)

DESCRIPTION

See Attachment

AGENCY'S URL

URL DESCRIPTION

AGENCY CONTACT'S EMAIL

ADDRESS

EMAIL DESCRIPTION

ADDRESS

POSTAL CODE

COUNTRY

ADDITIONAL INFORMATION

GENERAL INFORMATION

PLACE OF PERFORMANCE

* = Required Field FedBizOpps Modification to a Previous Notice Rev. March 2010 C A-E Design - Correct Architectural FCA Deficiencies - Roofs 33744 36C24818R0587 05-07-2018 N 541310 Department of Veterans Affairs Network Contracting Office 8 (248) Room 326, Bldg. 2 10,000 Bay Pines Blvd Bay Pines FL 33744 Rachel Reed Contracting Officer Department of Veterans Affairs Bay Pines VA Healthcare System (BPVAHCS) 10,000 Bay Pines Blvd.

Bay Pines, FL 33744

USA

Rachel.Reed@va.gov Contracting Officer THE PURPOSE OF THIS MODIFICATION TO PREVIOUS SOURCES SOUGHT NOTICE IS TO RESPOND TO QUESTIONS RECEIVED FROM INDUSTRY.

1. We came across the below verbiage in the solicitation document: “all projects identified on the SF 330 must be completed by the office/branch/individual team member performing the work under this contract”. Are subconsultants allowed to include projects within the SF330? Or is the prime firm the only one considered when providing projects?

RESPONSE: Yes, any sub-consultant can include projects.

2. Does the existing installation carry a UL Master Label certificate for the existing lightning protection system (LPS) installation? If so, is recertification of the reinstallation desired?

RESPONSE: Not all buildings in the scope have LPS. All buildings will need a UL Master Label certificate and it is best to assume that none are certified at this time.

3. Is the LPS getting replaced in its entirety under this scope of work?

RESPONSE: Yes.

4. Will NOA (Notification of Acceptance) rated roof enclosures be required for protection against air-borne wind debris for re-installation of existing roof mounted equipment?

RESPONSE: No. No enclosures will be required for roof mounted equipment.