This document is a solicitation for annual medical gas inspections at various Department of Veterans Affairs facilities. The solicitation seeks inspection and testing of medical gas and vacuum systems including master alarms, area alarms, zone valves, outlets and inlets, contaminant testing, and source equipment. Inspections are required at VA facilities in Augusta, Georgia from May 2023 through October 2023. The solicitation number is 36C24724Q0174 and was issued by Veterans Health Administration VISN 7. Responses are due by the date specified on SF1449. The award date will also be specified on SF1449. Pricing terms and conditions are according to the attached SF1449.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24724Q0174 0001.pdf | ||
| VAMC AUGUSTA UPTOWN 05-11-2023.pdf | ||
| 36C24724Q0174.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEDICAL GAS
TESTING & INSPECTION
VAMC AUGUSTA DOWNTOWN
AUGUSTA, GA
1-800-872-8992 www.evergreenmedical.com
05/09 -10/2023
MEDICAL GAS INSPECTION REPORT
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
Medical Facility:
City, State:
Medical Gas Contact Name:
Medical Gas Contact Dept:
Inspection Dates(s):
Territory MGR Josh Jenkins ASSE 6030 CREDENTIAL: 00062565
Lead Technician(s) Brandon Charbonneau ASSE 6030 CREDENTIAL: 12366457
Evergreen Medical Services, Inc. in accordance with applicable NFPA & CMS codes and standards has evaluated the medical piping systems indicated in this report. These systems have been found to be within applicable guidelines except as noted within this report. Any deficiencies cited are based on the most current applicable edition of NFPA 99.
Conflicts may occur when different editions of NFPA 99 have been adopted by different AHJs, and compliance occurs with one edition but not the other. Changes made to newer editions of NFPA 99 are done so to improve the system's quality, integrity, fire resistance, effectiveness, durability, and safety. Dependent on the opinion of the
AHJ(s), the newer code edition is generally acceptable as equivalent or superior to an older version(s).
Per NFPA 99 an existing system that is not in strict compliance with the applicable codes may continue to be used as long as it is not a distinct hazard to safety. Fire/Explosion hazards, labeling, manifold enclosures, medical air usage, & maintenance codes apply to new & existing facilities.
Information recorded on this report represent findings on the indicated evaluation date(s) only. Any action taken in response to recommendations included in this report should be recorded on the appropriate pages. This report should not be copied unless in entirety.
- Particulate Contaminants . . Page(s) 106-108
- Gaseous Contaminants . . . Page(s) 109
Section 7 - Source EQPT Summary . . Pg(s) 110
- Source Equipment . . . Page(s) 111-114
Section 8 - Annex . . . Page(s) 115
Section 5 - Outlets & Inlets . . . Page(s) 31-99
- Outlets & Inlets Inventory . . . Page(s) 100
JAMES JARRIEL
FACIILITIES ENGINEERING
05/09/2023 - 05/10/2023
VAMC AUGUSTA DOWNTOWN
AUGUSTA, GA
Outlets & Inlets Deficiencies . . Page(s) 101-103
Section 6 - Contaminants
- System Dew Point . . Page(s) 105
REPORT CONTENTS
Section 1 - Systems Overview . . . . Page(s) 3-5
Section 2 - Master Alarms . . . . Page(s) 6-9
- Master Alarm Inventory . . . Page(s) 10
- Master Alarm Deficiencies . . . Page(s) 11
Section 3 - Area Alarms . . . Page(s) 12-15
- Area Alarm Inventory . . . Page(s) 16
- Area Alarm Deficiencies . . . Page(s) 17
Section 4 - Zone Valves . . . . Page(s) 18-28
- Zone Valve Inventory . . . Page(s) 29
- Zone Valve Deficiencies . . . Page(s) 30 www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
GAS SYSTEMS OVERVIEW
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
MASTER ALARMS/SIGNALS (EACH SIGNAL COUNTED INDIVIDUALLY)
AREA ALARMS (EACH SYSTEM GAS COUNTED AS SEPARATE ALARM)
ZONE VALVES (EACH SYSTEM GAS COUNTED INDIVIDUALLY)
Total Master Alarm Signals
Quantity of Passing Master Alarm Signals
Quantity of Deficient Master Alarm Signals
Total Quantity of Zone Valves has remained the same from previous medical gas systems inspection.
Total Quantity of Master Alarm Signals has remained the same from previous medical gas systems inspection.
Total Quantity of Area Alarms has remained the same from previous medical gas systems inspection.
Total Area Alarms
Quantity of Passing Area Alarms
Quantity of Deficient Area Alarms
Total Zone Valves
Quantity of Passing Zone Valves
Quantity of Deficient Zone Valves
100.0%
0.0% Quantity of
Passing Area
Alarms
Quantity of
Deficient Area
Alarms
100.0%
0.0% Quantity of
Passing Zone
Valves
Quantity of
Deficient Zone
Valves
100.0%
0.0% Quantity of
Passing Master
Alarm Signals
Quantity of
Deficient Master
Alarm Signals www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
GAS SYSTEMS OVERVIEW
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
OUTLETS, INLETS & MANUFACTURED ASSEMBLIES
SYSTEM DEW POINT
PARTICULATE CONTAMINANTS
Total Quantity of Outlets, Inlets and Manufactured Assemblies has remained the same from previous medical gas systems inspection.
Total Outlets & Inlets
Quantity of Passing Outlets/Inlets
Quantity of Deficient Outlets/Inlets
Quantity of Passing Test Sites
Quantity of Deficient Test Sites
Total Particulate Contaminant Test Sites
Quantity of Passing Test Sites
Quantity of Deficient Test Sites
The Test Sites are selected in order to represent System Dew
Point in both high-use and low-use areas for the systems tested.
The Test Sites are selected in order to represent Particulate
Contaminants in both high-use and low-use areas for the systems tested.
Total Dew Point Test Sites
100.0%
0.0% Quantity of
Passing
Outlets/Inlets
Quantity of
Deficient
Outlets/Inlets
100%
0% Quantity of
Passing Test
Sites
Quantity of
Deficient Test
Sites
100%
0% Quantity of
Passing Test
Sites
Quantity of
Deficient Test
Sites www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
GAS SYSTEMS OVERVIEW
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
GASEOUS CONTAMINANTS
SOURCE EQUIPMENT
Quantity of Deficient Test Sites
Total Gaseous Contaminants Test Sites
Quantity of Passing Test Sites
The Test Sites are selected in order to represent Gaseous
Contaminants in all separate distribution and source systems.
Total Source Systems
Quantity of Passing Source Systems
Quantity of Deficient Source Systems
Total Quantity of Source Equipment has remained the same from previous medical gas systems inspection.
100%
0% Quantity of
Passing Test
Sites
Quantity of
Deficient Test
Sites
100%
0% Quantity of
Passing Source
Systems
Quantity of
Deficient Source
Systems www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
MASTER ALARMS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
M a ster A la rm P a n el
L o ca tio n
If M u ltip le P a n els
P er L o ca tio n
(e.g . "E n g in eerin g P a n el #
S y stem G a s
M a n u fa ctu rer
M o d el
C o n d itio n
M o n ito red
S w itch o r S o u rce L o ca tio n
S et P o in t
U n it o f M ea su re
In itia tin g
D ev ice
W irin g
P a n el
L a b elin g
O th er
C o m p o n en t C o n d itio n
1 Emergency Dept O2 Amico A2M Liquid Level Low O2 Bulk Enclosure 44 inH2O ✓ ✓ ✓ ✓ ✓ PASS
2 Emergency Dept O2 Amico A2M Reserve in Use O2 Bulk Enclosure 95 PSI ✓ ✓ ✓ ✓ ✓ PASS
3 Emergency Dept O2 Amico A2M Reserve Liquid Low O2 Bulk Enclosure 44 inH2O ✓ ✓ ✓ ✓ ✓ PASS
4 Emergency Dept O2 Amico A2M Reserve Pressure Low O2 Bulk Enclosure 80 PSI ✓ ✓ ✓ ✓ ✓ PASS
5 Emergency Dept O2 Amico A2M High Line Pressure Inside Hospital 60 PSI ✓ ✓ ✓ ✓ ✓ PASS
6 Emergency Dept O2 Amico A2M Low Line Pressure Inside Hospital 40 PSI ✓ ✓ ✓ ✓ ✓ PASS
7 Emergency Dept MA Amico A2M High Line Pressure Mech Room 60 PSI ✓ ✓ ✓ ✓ ✓ PASS
8 Emergency Dept MA Amico A2M Low Line Pressure Mech Room 40 PSI ✓ ✓ ✓ ✓ ✓ PASS
9 Emergency Dept MA Amico A2M High Dew Point Temp Mech Room 35 ºF ✓ ✓ ✓ ✓ ✓ PASS
10 Emergency Dept MA Amico A2M Maint. Required Mech Room PPM ✓ ✓ ✓ ✓ ✓ PASS
11 Emergency Dept N2O Amico A2M Secondary in Use Manifold Room 95 PSI ✓ ✓ ✓ ✓ ✓ PASS
12 Emergency Dept N2O Amico A2M High Line Pressure Manifold Room 60 PSI ✓ ✓ ✓ ✓ ✓ PASS
MASTER ALARMS: LOCATION & SPECIFICATION FUNCTION & CONDITION
www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
MASTER ALARMS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
M a ster A la rm P a n el
L o ca tio n u ltip le P a n els
P er L o ca n g in eerin g P a n el #
S y stem G a s
M a n u fa ctu rer
M o d el
C o n d itio n
M o n ito red
S w itch o r S o u rce L o ca tio n
S et P o in t
U n it o f M ea su re
In itia tin g
D ev ice
W irin g
P a n el
L a b elin g
O th er
C o m p o n en t C o n d itio n
MASTER ALARMS: LOCATION & SPECIFICATION FUNCTION & CONDITION
13 Emergency Dept N2O Amico A2M Low Line Pressure Manifold Room 40 PSI ✓ ✓ ✓ ✓ ✓ PASS
14 Emergency Dept VAC Amico A2M Low Line Pressure Mech Room 12 inHg ✓ ✓ ✓ ✓ ✓ PASS
15 Emergency Dept VAC Amico A2M Lag Pump in Use Mech Room 16 inHg ✓ ✓ ✓ ✓ ✓ PASS
16 Emergency Dept VAC Amico A2M High Temperature Mech Room ºF ✓ ✓ ✓ ✓ ✓ PASS
17 Emergency Dept VAC Amico A2M Maint. Required Mech Room ºF ✓ ✓ ✓ ✓ ✓ PASS
18 Emergency Dept VAC Amico A2M Low Oil Level Mech Room ✓ ✓ ✓ ✓ ✓ PASS
19 Boiler Plant O2 Amico A2M Liquid Level Low O2 Bulk Enclosure 44 inH2O ✓ ✓ ✓ ✓ ✓ PASS
20 Boiler Plant O2 Amico A2M Reserve in Use O2 Bulk Enclosure 95 PSI ✓ ✓ ✓ ✓ ✓ PASS
21 Boiler Plant O2 Amico A2M Reserve Liquid Low O2 Bulk Enclosure 44 inH2O ✓ ✓ ✓ ✓ ✓ PASS
22 Boiler Plant O2 Amico A2M Reserve Pressure Low O2 Bulk Enclosure 80 PSI ✓ ✓ ✓ ✓ ✓ PASS
23 Boiler Plant O2 Amico A2M High Line Pressure Inside Hospital 60 PSI ✓ ✓ ✓ ✓ ✓ PASS
24 Boiler Plant O2 Amico A2M Low Line Pressure Inside Hospital 40 PSI ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
MASTER ALARMS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
M a ster A la rm P a n el
L o ca tio n u ltip le P a n els
P er L o ca n g in eerin g P a n el #
S y stem G a s
M a n u fa ctu rer
M o d el
C o n d itio n
M o n ito red
S w itch o r S o u rce L o ca tio n
S et P o in t
U n it o f M ea su re
In itia tin g
D ev ice
W irin g
P a n el
L a b elin g
O th er
C o m p o n en t C o n d itio n
MASTER ALARMS: LOCATION & SPECIFICATION FUNCTION & CONDITION
25 Boiler Plant MA Amico A2M High Line Pressure Mech Room 60 PSI ✓ ✓ ✓ ✓ ✓ PASS
26 Boiler Plant MA Amico A2M Low Line Pressure Mech Room 40 PSI ✓ ✓ ✓ ✓ ✓ PASS
27 Boiler Plant MA Amico A2M High Dew Point Temp Mech Room 35 ºF ✓ ✓ ✓ ✓ ✓ PASS
28 Boiler Plant MA Amico A2M Maint. Required Mech Room PSI ✓ ✓ ✓ ✓ ✓ PASS
29 Boiler Plant N2O Amico A2M Secondary in Use Manifold Room 95 PSI ✓ ✓ ✓ ✓ ✓ PASS
30 Boiler Plant N2O Amico A2M High Line Pressure Manifold Room 60 PSI ✓ ✓ ✓ ✓ ✓ PASS
31 Boiler Plant N2O Amico A2M Low Line Pressure Manifold Room 40 PSI ✓ ✓ ✓ ✓ ✓ PASS
32 Boiler Plant VAC Amico A2M Low Line Pressure Mech Room 12 inHg ✓ ✓ ✓ ✓ ✓ PASS
33 Boiler Plant VAC Amico A2M Lag Pump in Use Mech Room 16 inHg ✓ ✓ ✓ ✓ ✓ PASS
34 Boiler Plant VAC Amico A2M High Temperature Mech Room ºF ✓ ✓ ✓ ✓ ✓ PASS
35 Boiler Plant VAC Amico A2M Maint. Required Mech Room ºF ✓ ✓ ✓ ✓ ✓ PASS
36 Boiler Plant VAC Amico A2M Low Oil Level Mech Room ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
MASTER ALARMS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
M a ster A la rm P a n el
L o ca tio n u ltip le P a n els
P er L o ca n g in eerin g P a n el #
S y stem G a s
M a n u fa ctu rer
M o d el
C o n d itio n
M o n ito red
S w itch o r S o u rce L o ca tio n
S et P o in t
U n it o f M ea su re
In itia tin g
D ev ice
W irin g
P a n el
L a b elin g
O th er
C o m p o n en t C o n d itio n
MASTER ALARMS: LOCATION & SPECIFICATION FUNCTION & CONDITION
37 Boiler Plant VAC Amico A2M Lag Pump in Use Mech Room 12 inHg ✓ ✓ ✓ ✓ ✓ PASS
38 6th Floor D Wing MA Amico A2M Liquid Level Low O2 Bulk Enclosure 44 inH2O ✓ ✓ ✓ ✓ ✓ PASS
39 6th Floor D Wing O2 Amico A2M Reserve in Use O2 Bulk Enclosure 95 PSI ✓ ✓ ✓ ✓ ✓ PASS
40 6th Floor D Wing MA Amico A2M High Line Pressure Inside Hospital 60 PSI ✓ ✓ ✓ ✓ ✓ PASS
41 6th Floor D Wing MA Amico A2M Low Line Pressure Inside Hospital 40 PSI ✓ ✓ ✓ ✓ ✓ PASS
42 6th Floor D Wing O2 Amico A2M High Line Pressure Inside Hospital 60 PSI ✓ ✓ ✓ ✓ ✓ PASS
43 6th Floor D Wing O2 Amico A2M Low Line Pressure Inside Hospital 40 PSI ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
MASTER ALARM INVENTORY
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
MASTER ALARM SIGNALS
BY SYSTEM GAS:
15 11 6 0 0 11 0 0 0
TOTAL
MASTER ALARM
PANELS
TOTAL MASTER ALARM SIGNALS:
MANUFACTURER
(Or Current Owner )
MODEL MASTER ALARM PANEL DESCRIPTION
O
M A
N
O
N
C O
V A
C
W A
G D
IA
O th er
Amico A2M Gray Cover with Red LED Indicators 15 11 6 0 0 11 0 0 0
TOTAL
MASTER ALARM
PANELS
MASTER ALARMS BREAKDOWN (*EACH MASTER ALARM SIGNAL COUNTED AS SEPARATE ALARM BY SYSTEM GAS BELOW) www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
MASTER ALARM DEFICIENCIES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
QTY
DEFICIENT
QTY
CORRECTED
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
N) Labeling: No Source Location
I) Panel: Incorrect Power Source
J) Panel: Incorrect Location
K) Panel: No Signal in Place (Local Alarm Only)
L) Panel: No Signal in Place (No Initiating Device/Wiring)
M) Labeling: System Gas
Connect Alarm to Life Safety Branch
Move Alarm Panel to a Proper Location
Wire Initiating Device to Master Alarm Panel(s)
Add Signal/Signal Components to Master Alarm System
Verify and Relabel System Gas
Verify and Relabel Source Location
D) Wiring: Not Independent to at Least (2) Master Panels
E) Wiring: Shared Common Conductors
F) Wiring: Not Protected
G) Panel: Visual and/or Audible Function Failed
H) Panel: Power Failure
MASTER ALARM DEFICIENCIES OVERVIEW
DEFICIENCY DESCRIPTION
A) Initiating Device: Incorrect Location
B) Initiating Device: Improper Set Point
C) Initiating Device: None in Place
CORRECTIVE ACTION NEEDED
Move Initiating Device to Proper Location and/or Install Demand Check
Adjust Alarm Set Point
Install Initiating Device
O) Labeling: No Condition Monitored
P) Other:
Verify and Relabel Condition Monitored
N/A
TOTALS:
Rewire Panels Independently to Initiating Device
Rewire Panels Independently to Initiating Device With Correct Number of
Conductors
Protect Master Alarm Wiring
Repair/Replace Annunciator Module/Alarm Panel
Repair/Replace Power Supply www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
AREA ALARMS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
A la rm P h y sica l L o ca tio n
A rea
/Z o n e M o n ito red
S y stem G a s
M a n u fa ctu rer
M o d el
P ressu re R ea d in g
(P o sitive in P
S I/N eg a tive in In
/H g
H ig h P ressu re A la rm
S ettin g
(P o sitive in P
S I/N eg a tive in In
/H g
L o w P ressu re A la rm
S ettin g
(P o sitive in P
S I/N eg a tive in In
/H g
A la rm S et P o in ts
T ra n sd u cer L o ca tio n
T ra n sd u cer F u n ctio n
A la rm L o ca tio n
P a n el F u n ctio n
M o d u le F u n ctio n
L a b elin g
O th er
C o m p o n en t C o n d itio n
1 6A Nurses Desk 101, 103,105, 107, 109, 111,113,1115, 117, 121 O2 Powerex MedTouch 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
2 6A Nurses Desk 101, 103,105, 107, 109, 111,113,1115, 117, 121 MA Powerex MedTouch 45 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
3 6A Nurses Desk 101, 103,105, 107, 109, 111,113,1115, 117, 121 VAC Powerex MedTouch 23 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
4 6A Nurses Desk 123, 127, 129, 131, 133, 135, 137, 139, 141, 143 O2 Powerex MedTouch 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
5 6A Nurses Desk 123, 127, 129, 131, 133, 135, 137, 139, 141, 143 MA Powerex MedTouch 45 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
6 6A Nurses Desk 123, 127, 129, 131, 133, 135, 137, 139, 141, 143 VAC Powerex MedTouch 24 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
7 6D Nurses Desk 6D 110-112, 114-119 &
120A O2 Amico A2A 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
8 6D Nurses Desk 6D 110-112, 114-119 &
120A MA Amico A2A 44 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
9 6D Nurses Desk 6D 110-112, 114-119 &
120A VAC Amico A2A 24 32 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
10 6D Nurses Desk 6D 140A-6D149 O2 Amico A2A 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
11 6D Nurses Desk 6D 140A-6D149 MA Amico A2A 44 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
12 6D Nurses Desk 6D 140A-6D149 VAC Amico A2A 24 32 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
AREA ALARMS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
A la rm P h y sica l L o ca tio n
A rea
/Z o n e M o n ito red
S y stem G a s
M a n u fa ctu rer
M o d el
P ressu re R ea d sitive in P
S I/N eg a tive in In
/H g
H ig h P ressu re A la rm
S ettin g
(P o sitive in P
S I/N eg a tive in In
/H g
L o w P ressu re A la rm
S ettin g
(P o sitive in P
S I/N eg a tive in In
/H g
A la rm S et P o in ts
T ra n sd u cer L o ca tio n
T ra n sd u cer F u n ctio n
A la rm L o ca tio n
P a n el F u n ctio n
M o d u le F u n ctio n
L a b elin g
O th er
C o m p o n en t C o n d itio n
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
13 3A OR Nurses Desk OR Holding O2 Amico A2A 52 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
14 3A OR Nurses Desk OR Holding MA Amico A2A 45 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
15 3A OR Nurses Desk OR Holding VAC Amico A2A 20 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
16 3A OR Nurses Desk OR Suite O2 Amico A2A 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
17 3A OR Nurses Desk OR Suite MA Amico A2A 46 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
18 3A OR Nurses Desk OR Suite VAC Amico A2A 20 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
19 3A OR Nurses Desk OR Suite N2O Amico A2A 53 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
20 3D PACU 3D PACU O2 Amico A2A 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
21 3D PACU 3D PACU MA Amico A2A 48 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
22 3D PACU 3D PACU VAC Amico A2A 24 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
23 3D Ambulatory Surg 3D Ambulatory Surg O2 Amico A2A 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
24 3D Ambulatory Surg 3D Ambulatory Surg MA Amico A2A 46 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
25 3D Ambulatory Surg 3D Ambulatory Surg VAC Amico A2A 24 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
26 3B ICU Nurses Desk CCU 1-12 & 14-21 O2 Beacon P0321 50 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
27 3B ICU Nurses Desk CCU 1-12 & 14-21 MA Beacon P0321 46 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
28 3B ICU Nurses Desk CCU 1-12 & 14-21 VAC Beacon P0321 22 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
AREA ALARMS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
A la rm P h y sica l L o ca tio n
A rea
/Z o n e M o n ito red
S y stem G a s
M a n u fa ctu rer
M o d el
P ressu re R ea d sitive in P
S I/N eg a tive in In
/H g
H ig h P ressu re A la rm
S ettin g
(P o sitive in P
S I/N eg a tive in In
/H g
L o w P ressu re A la rm
S ettin g
(P o sitive in P
S I/N eg a tive in In
/H g
A la rm S et P o in ts
T ra n sd u cer L o ca tio n
T ra n sd u cer F u n ctio n
A la rm L o ca tio n
P a n el F u n ctio n
M o d u le F u n ctio n
L a b elin g
O th er
C o m p o n en t C o n d itio n
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
29 3C Cath Recovery
3C 112, 112A, 114, 115, 116, Lab Recovery 125, Cath Lab 125B & 143
O2 Amico A2A 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
30 3C Cath Recovery
3C 112, 112A, 114, 115, 116, Lab Recovery 125, Cath Lab 125B & 143
MA Amico A2A 46 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
31 3C Cath Recovery
3C 112, 112A, 114, 115, 116, Lab Recovery 125, Cath Lab 125B & 143
VAC Amico A2A 24 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
32 1H Spinal 1H106, 108, 112, 117, 119, 122, 1G139 & 141 O2 Amico A2A 52 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
33 1H Spinal 1H106, 108, 112, 117, 119, 122, 1G139 & 141 MA Amico A2A 46 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
34 1H Spinal 1H106, 108, 112, 117, 119, 122, 1G139 & 141 VAC Amico A2A 40 32 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
35 O/S 1G128
SICU 1G114, 115, 116,
118, 119, 121, 123, 126, 129, 133, 135, 1E120 &
O2 Beacon P0321 51 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
36 O/S 1G128
SICU 1G114, 115, 116,
118, 119, 121, 123, 126, 129, 133, 135, 1E120 &
MA Beacon P0321 47 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
AREA ALARMS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
A la rm P h y sica l L o ca tio n
A rea
/Z o n e M o n ito red
S y stem G a s
M a n u fa ctu rer
M o d el
P ressu re R ea d sitive in P
S I/N eg a tive in In
/H g
H ig h P ressu re A la rm
S ettin g
(P o sitive in P
S I/N eg a tive in In
/H g
L o w P ressu re A la rm
S ettin g
(P o sitive in P
S I/N eg a tive in In
/H g
A la rm S et P o in ts
T ra n sd u cer L o ca tio n
T ra n sd u cer F u n ctio n
A la rm L o ca tio n
P a n el F u n ctio n
M o d u le F u n ctio n
L a b elin g
O th er
C o m p o n en t C o n d itio n
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
37 O/S 1G128
SICU 1G114, 115, 116,
118, 119, 121, 123, 126, 129, 133, 135, 1E120 &
VAC Beacon P0321 18 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
38 O/S 1G102
SICU 1G101, 103, 104,
107, 111, 112, 113, 1F123, 125 & 126
O2 Beacon P0321 53 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
39 O/S 1G102
SICU 1G101, 103, 104,
107, 111, 112, 113, 1F123, 125 & 126
MA Beacon P0321 48 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
40 O/S 1G102
SICU 1G101, 103, 104,
107, 111, 112, 113, 1F123, 125 & 126
VAC Beacon P0321 23 30 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
41 1D E.D. Dept LSU Rooms 1D 166-173 O2 Amico A2A 52 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
42 1D 182 1D 182 O2 Amico A2A 52 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
43 1D 182 1D 182 MA Amico A2A 45 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
44 1D 182 1D 182 VAC Amico A2A 17 32 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
45 O/S 1D 182 1D 182A O2 Amico A2A 52 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
46 O/S 1D 182 1D 182A MA Amico A2A 45 60 40 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
47 O/S 1D 182 1D 182A VAC Amico A2A 19 32 12 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
AREA ALARMS INVENTORY
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
TOTAL AREA ALARM SIGNALS
BY SYSTEM GAS:
16 15 1 0 0 15 0 0 0
TOTAL
AREA ALARM
PANELS
TOTAL AREA ALARM SIGNALS:
MANUFACTURER
(Or Current Parent
Company )
MODEL AREA ALARM DESCRIPTION
O
M A
N
O
N
C O
V A
C
W A
G D
IA
O th er
Amico A2A Gray Cover with Digital Pressure 11 10 1 0 0 10 0 0 0
Beacon P0321 White with Murphy gauges-"Area Line Press. Alm" 3 3 0 0 0 3 0 0 0
Powerex MedTouch Tritech MedTouch / "Powerex" branding 2 2 0 0 0 2 0 0 0
TOTAL
AREA ALARM
PANELS
AREA ALARMS BREAKDOWN (EACH AREA ALARM SIGNAL COUNTED AS SEPARATE ALARM BY SYSTEM GAS BELOW) www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
AREA ALARM DEFICIENCIES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
AREA ALARM DEFICIENCIES OVERVIEW
ACTION NEEDED
Adjust Set Points to +/-20% Operating Pressure
Move Transducers to Correct Side of Zone Valve
QTY
CORRECTED
DEFICIENCY DESCRIPTION
A) Alarm Set Points: Incorrect High and/or Low Alarm Set Point(s)
QTY
DEFICIENT
Connect Alarm to Life Safety Branch
Repair/Replace Module or Defective Transducer
Label Area Monitored
Label Gas System Monitored
N/A
Install Demand Check
Repair/Recalibrate/Replace Transducer
Move Alarm to Appropriate Location
Install Area Alarm & Transducer
Repair/Replace Annunciator Module / Ribbon Cable / Alarm Panel
Repair/Replace Power Supply
G) Panel Function: Visual and/or Audible Alarm Function Failure
H) Panel Function: Power Failure
I) Panel Function: Incorrect Power Source
J) Module Function: Module Display Blank or Error Message
K) Labeling: Area Monitored Labeling Missing/Incorrect
B) Transducer Location: Incorrect Transducer Location
C) Transducer Location: No Demand Check
D) Transducer Function: Incorrect Gas Pressure Displayed
E) Alarm Location: Improper Alarm Panel Location
F) Alarm Location: No Alarm in Place
L) Labeling: Gas System Monitored Not Labeled
M) Other:
TOTALS: 0
www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
1 Opp 7A 143 7A 133, 134, 143, 156 (Not in Service) O2 Beacon ✓ ✓ ✓ PASS
2 Opp 7A 143 7A 133, 134, 143, 156 (Not in Service) MA Beacon ✓ ✓ ✓ PASS
3 Opp 7A 143 7A 133, 134, 143, 156 (Not in Service) VAC Beacon ✓ ✓ ✓ PASS
4 O/S 6A 101 101, 103,105, 107, 109, 111,113,1115, 117, 121 MA Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
5 O/S 6A 101 101, 103,105, 107, 109, 111,113,1115, 117, 121 O2 Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
6 O/S 6A 101 101, 103,105, 107, 109, 111,113,1115, 117, 121 VAC Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
7 O/S 6A 143 123, 127, 129, 131, 133, 135, 137, 139, 141, 143 MA Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
8 O/S 6A 143 123, 127, 129, 131, 133, 135, 137, 139, 141, 143 O2 Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
9 O/S 6A 143 123, 127, 129, 131, 133, 135, 137, 139, 141, 143 VAC Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
10 Opp 6C 146 6C 117, 118, 124, 128, 133, 137, 140, 145, 146, 149, 151, 152, 154 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
11 Opp 6C 146 6C 117, 118, 124, 128, 133, 137, 140, 145, 146, 149, 151, 152, 154 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
12 Opp 6C 146 6C 117, 118, 124, 128, 133, 137, 140, 145, 146, 149, 151, 152, 154 Vac Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
ZONE VALVES: LOCATION & SPECIFICATION
www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
13 O/S 6D Unit 6D 110-112, 114-119 & 120A O2 Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
14 O/S 6D Unit 6D 110-112, 114-119 & 120A MA Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
15 O/S 6D Unit 6D 110-112, 114-119 & 120A Vac Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
16 O/S 6D101 6D 140A-6D149 O2 Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
17 O/S 6D101 6D 140A-6D149 MA Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
18 O/S 6D101 6D 140A-6D149 VAC Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
19 5A
5A 112, 114, 115, 117, 120, 122, 126, 141, 146, 149, 150, 152, 154, 157, 161, 163, 168 (Add Rm. 144)
VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
20 5A
5A 112, 114, 115, 117, 120, 122, 126, 141, 146, 149, 150, 152, 154, 157, 161, 163, 168
MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
21 5A
5A 112, 114, 115, 117, 120, 122, 126, 141, 146, 149, 150, 152, 154, 157, 161, 163, 168
O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
22 5C 5C 109, 112, 129, 131, 134, 137, 142, O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
23 5C 5C 109, 112, 129, 131, 134, 137, 142, MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
24 5C 5C 109, 112, 129, 131, 134, 137, 142, VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
25 5D
5D 105, 107, 113, 114, 116, 118, 120, 130, 134, 136, 142, 143, 147, 151, 153, 155, 157, 159
O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
26 5D
5D 105, 107, 113, 114, 116, 118, 120, 130, 134, 136, 142, 143, 147, 151, 153, 155, 157, 159
VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
27 5D
5D 105, 107, 113, 114, 116, 118, 120, 130, 134, 136, 142, 143, 147, 151, 153, 155, 157, 159
MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
28 4A 4A 113, 116, 120, 122, 124, 128, 131, 133, 135, 140, 143, 147, 149, 155, 159 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
29 4A 4A 113, 116, 120, 122, 124, 128, 131, 133, 135, 140, 143, 147, 149, 155, 159 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
30 4A 4A 113, 116, 120, 122, 124, 128, 131, 133, 135, 140, 143, 147, 149, 155, 159 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
31 4C 4C 109, 137B, 137C, 138, 142, 145, 147, 152, 154, 160 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
32 4C 4C 109, 137B, 137C, 138, 142, 145, 147, 152, 154, 160 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
33 4C 4C 109, 137B, 137C, 138, 142, 145, 147, 152, 154, 160 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
34 3A PRE-OP OR Holding 1-6 O2 Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
35 3A PRE-OP OR Holding 1-6 MA Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
36 3A PRE-OP OR Holding 1-6 VAC Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
37 3D PACU 3D PACU and Recovery O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
38 3D PACU 3D PACU and Recovery MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
39 3D PACU 3D PACU and Recovery VAC Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
40 3D ASU 3D Ambulatory Surgery Unit O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
41 3D ASU 3D Ambulatory Surgery Unit MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
42 3D ASU 3D Ambulatory Surgery Unit VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
43 3A128 OR 1 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
44 3A128 OR 1 N2O Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
45 3A128 OR 1 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
46 3A128 OR 1 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
47 3A126 OR 2 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
48 3A126 OR 2 N2O Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
49 3A126 OR 2 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
50 3A126 OR 2 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
51 3A123 OR 3 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
52 3A123 OR 3 N2O Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
53 3A123 OR 3 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
54 3A123 OR 3 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
55 3A122 OR 4 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
56 3A122 OR 4 N2O Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
57 3A122 OR 4 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
58 3A122 OR 4 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
59 3A121 OR 5 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
60 3A121 OR 5 N2O Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
61 3A121 OR 5 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
62 3A121 OR 5 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
63 3A119 OR 6 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
64 3A119 OR 6 N2O Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
65 3A119 OR 6 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
66 3A119 OR 6 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
67 3A117 OR 7 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
68 3A117 OR 7 N2O Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
69 3A117 OR 7 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
70 3A117 OR 7 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
71 3A115 OR 8 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
72 3A115 OR 8 N2O Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
73 3A115 OR 8 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
74 3A115 OR 8 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
75 3A115 OR 8 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
76 3B O/S ICU CCU 1-12, 14-21 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
77 3B O/S ICU CCU 1-12, 14-21 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
78 3B O/S ICU CCU 1-12, 14-21 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
79 3C Dialysis 3C 112, 112A, 114, 115, Cath Lab
Recovery 125, Cath Lab 125B & 143 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
80 3C Dialysis 3C 112, 112A, 114, 115, Cath Lab
Recovery 125, Cath Lab 125B & 143 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
81 3C Dialysis 3C 112, 112A, 114, 115, Cath Lab
Recovery 125, Cath Lab 125B & 143 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
82 2A Opp 2A 147 2A 118, 120, 127, 134, 136, 139, 143 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
83 2A Opp 2A 147 2A 118, 120, 127, 134, 136, 139, 143 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
84 2A Opp 2A 147 2A 118, 120, 127, 134, 136, 139, 143 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
85 O/S 2D 249 2D 185, 218, 222, 225, 227, 249, 2D
189, 2D 143 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
86 O/S 2D 249 2D 185, 218, 222, 225, 227, 249, 2D
189, 2D 143 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
87 O/S 2D 249 2D 185, 218, 222, 225, 227, 249, 2D
189, 2D 143 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
88 O/S 2D 149 2D 149 PET CT Scan O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
89 O/S 2D 149 2D 149 PET CT Scan MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
90 O/S 2D 149 2D 149 PET CT Scan VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
91 O/S 2D 165 2D 165 Nuc Med O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
92 O/S 2D 165 2D 165 Nuc Med MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
93 O/S 2D 165 2D 165 Nuc Med VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
94 O/S 2D 154 2D 154 & 156 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
95 O/S 2D 154 2D 154 & 156 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
96 O/S 2D 154 2D 154 & 156 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
97 O/S 1G139 1H106, 108, 112, 117, 119, 122, 1G139 & 141 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
98 O/S 1G139 1H106, 108, 112, 117, 119, 122, 1G139 & 141 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
99 O/S 1G139 1H106, 108, 112, 117, 119, 122, 1G139 & 141 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
100 O/S 1G128
SICU 1G114, 115, 116, 118, 119, 121,
123, 126, 129, 133, 135, 1E120 & 123 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
101 O/S 1G128
SICU 1G114, 115, 116, 118, 119, 121,
123, 126, 129, 133, 135, 1E120 & 123 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
102 O/S 1G128
SICU 1G114, 115, 116, 118, 119, 121,
123, 126, 129, 133, 135, 1E120 & 123 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
103 O/S 1G102
SICU 1G101, 103, 104, 107, 111, 112,
113, 1F123, 125 & 126 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
104 O/S 1G102
SICU 1G101, 103, 104, 107, 111, 112,
113, 1F123, 125 & 126 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
105 O/S 1G102
SICU 1G101, 103, 104, 107, 111, 112,
113, 1F123, 125 & 126 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
106 Opp 1F102 1F103, 105, 107, 109, 115 & 1E129 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
107 Opp 1F102 1F103, 105, 107, 109, 115 & 1E129 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
108 Opp 1F102 1F103, 105, 107, 109, 115 & 1E129 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
109 O/S 1E 137 1E 137 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
110 O/S 1E 137 1E 137 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
111 O/S 1E 137 1E 137 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
112 O/S 1E 139 1E 139 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
113 O/S 1E 139 1E 139 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
114 O/S 1E 139 1E 139 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
115 O/S 1D100 1D 155 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
116 O/S 1D100 1D 155 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
117 O/S 1D100 1D 155 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
118 O/S 1D149 1D EENT Rms 149, 148, 145, 143 O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
119 O/S 1D149 1D EENT Rms 149, 148, 145, 143 MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
120 O/S 1D149 1D EENT Rms 149, 148, 145, 143 VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
122 O/S 1D135 1D135 Chair 1-12, 1D135A O2 Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
123 O/S 1D135 1D135 Chair 1-12, 1D135A MA Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
124 O/S 1D135 1D135 Chair 1-12, 1D135A VAC Powerex ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
125 1D MRI MRI 1D118B, 118G, 118J, 118R O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
126 1D MRI MRI 1D118B, 118G, 118J, 118R MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
126 1D MRI MRI 1D118B, 118G, 118J, 118R VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
127 1D E.D. Dept ID 181, 181A, 181B, 193, 193A O2 Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
128 1D E.D. Dept ID 181, 181A, 181B, 193, 193A MA Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
129 1D E.D. Dept
ID 181, 181A, 181B, 193, 193A, 1D
VAC Beacon ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
130 1D E.D. Dept LSU Rooms 1D 166-173 O2 Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
131 1D 182 1D 182 O2 Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
132 1D 182 1D 182 MA Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
133 1D 182 1D 182 VAC Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
FUNCTION AND CONDITION
Z V
B P h y sica l L o ca tio n
R o o m s o r A rea S erv ed
S y stem G a s
M a n u fa ctu rer
B a ll
G a te/G lo b e
G a u g e P ressu re A ccu ra cy
G a u g e
G en era l C o n d itio n
L a b elin g
L ea k s
L o ca tio n
O th er
C o m p o n en t C o n d itio n
ZONE VALVES: LOCATION & SPECIFICATION
134 O/S 1D 182 1D 182A O2 Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
135 O/S 1D 182 1D 182A MA Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
136 O/S 1D 182 1D 182A VAC Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
137 O/S 1D182A 1D 183, 1D183A O2 Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
138 O/S 1D182A 1D 183, 1D183A MA Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
139 O/S 1D182A 1D 183, 1D183A VAC Amico ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVES INVENTORY
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
TOTAL ZONE VALVES BY SYSTEM GAS: 45 43 8 0 0 43 0 0 0
TOTAL
ZONE VALVE
BOXES
TOTAL ZONE VALVES
MANUFACTURER
(Or Current Owner )
VALVE
TYPE
ZONE VALVE DESCRIPTION
O
M A
N
O
N
C O
V A
C
W A
G D
IA
O th er
Amico Ball 1/4 Turn Ball Valve 7 6 0 0 0 7 0 0 0
Beacon Ball 1/4 Turn Ball Valve 35 34 8 0 0 33 0 0 0
Powerex Ball 1/4 Turn Ball Valve 3 3 0 0 0 3 0 0 0
ZONE VALVES BREAKDOWN (EACH SYSTEM GAS COUNTED AS SEPARATE ZONE VALVE)
TOTAL
ZONE VALVE
BOXES
www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
ZONE VALVE DEFICIENCIES
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
ZONE VALVE DEFICIENCIES OVERVIEW
QTY
CORRECTED
QTY DEFICIENT
Rebuild if Possible or Replace Leaking Valve
Re-install Gauge Using Oxygen-Safe Sealant (Replacement of Valve May be Necessary)
Move Valve to Visible and Accessible Location
Move Valve to Compliant Location
Install Zone Valve
Label All Required Components with Non-Standard Pressure
Update Label to Include System Gas
Update Label to Include Warning Verbiage
Verify if Rooms/Area is Served by an Existing Zone Valve (Installation
Necessary if Rooms/Area is not Currently Served by a Zone Valve)
Rebuild if Possible or Replace Leaking Valve
R: Location: No Valve in Place
N/A
0 0TOTALS:
S: Other: 0
Q: Location: Improper Location
DEFICIENCY DESCRIPTION
A: Gauge: Inaccurate Pressure Reading
B: Gauge: Incorrect Scale Range
C: Gauge: No Gauge in Port
D: Gauge: On Source Side of Valve
N: Leak: Gas Passes Through Valve When Closed
P: Location: Hidden or Not Accessible
M: Leak: External Leak
J: Labeling: Missing System Gas
K: Labeling: Missing Warning Verbiage
L: Labeling: Rooms/Area not Attributed a Zone Valve
O: Leak: Gauge Connection Leaks
I: Labeling: Missing Non-Standard Pressure Verbiage
ACTION NEEDED
Replace Gauge
Install Gauge With Correct Scale Range
Install Gauge
Repipe Valve So Gauge is Downstream of Valve
Replace Handle
Replace Window
Verify Rooms/Area Served and Relabel
Verify Rooms/Area Served and Relabel (Repiping or Decommissioning
Valve May Be Necessary)
E: General Condition: Missing/Broken Handle
F: General Condition: Missing/Broken Window
G: Labeling: Inaccurate Rooms/Area Served
H: Labeling: Labeled as if in Series www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
OUTLETS & INLETS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
7th Fl A Wing (Not in
Service) 133 O2 Beacon DIA II Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 133 MA Beacon DIA II Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 133 VAC Beacon Dia III Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 134 O2 Beacon DIA II Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 134 MA Beacon DIA II Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 134 VAC Beacon Dia III Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 143 O2 Beacon DIA II Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 143 MA Beacon DIA II Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 143 VAC Beacon Dia III Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 156 O2 Beacon Dia III Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 156 MA Beacon Dia III Recessed NOT IN USE
7th Fl A Wing (Not in
Service) 156 VAC Beacon Dia III Recessed NOT IN USE
13 6th Fl A Wing 101 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
14 6th Fl A Wing 101 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
15 6th Fl A Wing 101 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
L o ca tio n
O th er
G a s C o n cen tra tio n
C o m p o n en t C o n d itio n
O p era tio n a l F lo w
S ta tic P ressu re
FUNCTION AND CONDITIONOUTLETS & INLETS: LOCATION & SPECIFICATION
G en era l C o n d itio n
L ea k s
L a b elin g
M o d el
P o sitio n
/S ty le
A rea o r Z o n e
R o o m
, B ed o r O u tlet #
(In ven to ry ta ken clo ckw ise a ro u n d ro o m
, fro m to p to b tto m a n d /o r left to rig h t)
S y stem G a s
M a n u fa ctu rer www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
OUTLETS & INLETS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
L o ca tio n
O th er
G a s C o n cen tra tio n
C o m p o n en t C o n d itio n
O p era tio n a l F lo w
S ta tic P ressu re
FUNCTION AND CONDITIONOUTLETS & INLETS: LOCATION & SPECIFICATION
G en era l C o n d itio n
L ea k s
L a b elin g
M o d el
P o sitio n
/S ty le
A rea o r Z o n e
R o o m
, B ed o r O to ry ta ken clo ckw ise a ro u n d ro o m
, fro m to tto m a n d /o r left to rig h t)
S y stem G a s
M a n u fa ctu rer
16 6th Fl A Wing 103 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
17 6th Fl A Wing 103 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
18 6th Fl A Wing 103 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
19 6th Fl A Wing 105 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
20 6th Fl A Wing 105 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
21 6th Fl A Wing 105 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
22 6th Fl A Wing 107 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
23 6th Fl A Wing 107 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
24 6th Fl A Wing 107 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
25 6th Fl A Wing 109 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
26 6th Fl A Wing 109 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
27 6th Fl A Wing 109 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
28 6th Fl A Wing 111 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
29 6th Fl A Wing 111 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
30 6th Fl A Wing 111 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
31 6th Fl A Wing 113 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
32 6th Fl A Wing 113 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
33 6th Fl A Wing 113 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
34 6th Fl A Wing 115 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
35 6th Fl A Wing 115 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
36 6th Fl A Wing 115 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
37 6th Fl A Wing 117 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
38 6th Fl A Wing 117 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
39 6th Fl A Wing 117 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
OUTLETS & INLETS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
L o ca tio n
O th er
G a s C o n cen tra tio n
C o m p o n en t C o n d itio n
O p era tio n a l F lo w
S ta tic P ressu re
FUNCTION AND CONDITIONOUTLETS & INLETS: LOCATION & SPECIFICATION
G en era l C o n d itio n
L ea k s
L a b elin g
M o d el
P o sitio n
/S ty le
A rea o r Z o n e
R o o m
, B ed o r O to ry ta ken clo ckw ise a ro u n d ro o m
, fro m to tto m a n d /o r left to rig h t)
S y stem G a s
M a n u fa ctu rer
40 6th Fl A Wing 121 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
41 6th Fl A Wing 121 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
42 6th Fl A Wing 121 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
43 6th Fl A Wing 123 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
44 6th Fl A Wing 123 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
45 6th Fl A Wing 123 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
46 6th Fl A Wing 127 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
47 6th Fl A Wing 127 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
48 6th Fl A Wing 127 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
49 6th Fl A Wing 129 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
50 6th Fl A Wing 129 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
51 6th Fl A Wing 129 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
52 6th Fl A Wing 131 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
53 6th Fl A Wing 131 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
54 6th Fl A Wing 131 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
55 6th Fl A Wing 133 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
56 6th Fl A Wing 133 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
57 6th Fl A Wing 133 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
58 6th Fl A Wing 135 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
59 6th Fl A Wing 135 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
60 6th Fl A Wing 135 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
61 6th Fl A Wing 137 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
62 6th Fl A Wing 137 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
63 6th Fl A Wing 137 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
OUTLETS & INLETS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
L o ca tio n
O th er
G a s C o n cen tra tio n
C o m p o n en t C o n d itio n
O p era tio n a l F lo w
S ta tic P ressu re
FUNCTION AND CONDITIONOUTLETS & INLETS: LOCATION & SPECIFICATION
G en era l C o n d itio n
L ea k s
L a b elin g
M o d el
P o sitio n
/S ty le
A rea o r Z o n e
R o o m
, B ed o r O to ry ta ken clo ckw ise a ro u n d ro o m
, fro m to tto m a n d /o r left to rig h t)
S y stem G a s
M a n u fa ctu rer
64 6th Fl A Wing 139 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
65 6th Fl A Wing 139 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
66 6th Fl A Wing 139 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
67 6th Fl A Wing 141 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
68 6th Fl A Wing 141 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
69 6th Fl A Wing 141 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
70 6th Fl A Wing 143 VAC Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
71 6th Fl A Wing 143 MA Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
72 6th Fl A Wing 143 O2 Amico S-DIA Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
73 6th Fl C Wing 117 O2 Beacon DIA II Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
74 6th Fl C Wing 117 MA Beacon DIA II Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
75 6th Fl C Wing 117 VAC Beacon Dia III Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
76 6th Fl C Wing 117 O2 Beacon DIA II Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
77 6th Fl C Wing 117 MA Beacon Dia III Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
78 6th Fl C Wing 117 VAC Beacon Dia III Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
79 6th Fl C Wing 117 O2 Beacon DIA II Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
80 6th Fl C Wing 117 MA Beacon Dia III Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
81 6th Fl C Wing 117 VAC Beacon Dia III Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
82 6th Fl C Wing 118 O2 Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
83 6th Fl C Wing 118 MA Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
84 6th Fl C Wing 118 VAC Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
85 6th Fl C Wing 124 O2 Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
86 6th Fl C Wing 124 MA Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
87 6th Fl C Wing 124 VAC Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS www.evergreenmedical.com © 2021 Evergreen Medical Services, Inc. - VER 1.3 Corporate Office: 1-800-872-8992
OUTLETS & INLETS
Medical Gas and Vacuum Systems Inspection/Testing
VAMC Augusta Downtown
Augusta, GA
L o ca tio n
O th er
G a s C o n cen tra tio n
C o m p o n en t C o n d itio n
O p era tio n a l F lo w
S ta tic P ressu re
FUNCTION AND CONDITIONOUTLETS & INLETS: LOCATION & SPECIFICATION
G en era l C o n d itio n
L ea k s
L a b elin g
M o d el
P o sitio n
/S ty le
A rea o r Z o n e
R o o m
, B ed o r O to ry ta ken clo ckw ise a ro u n d ro o m
, fro m to tto m a n d /o r left to rig h t)
S y stem G a s
M a n u fa ctu rer
88 6th Fl C Wing 128 O2 Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
89 6th Fl C Wing 128 MA Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
90 6th Fl C Wing 128 VAC Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
91 6th Fl C Wing 133 O2 Beacon DIA I Recessed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ PASS
92 6th Fl C Wing 133 MA…