13 05 41 - SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.pdf
PDF 76 KB Posted
- Solicitation number
- 36C24626B0029
About this file
This is a Seismic Restraint Requirements specification for non-structural components applicable to a federal construction project at Durham VAMC (Veterans Affairs Medical Center) for replacing chillers for Air Handling Units 1 and 2.
The specification establishes comprehensive seismic design requirements based on VA Handbook H18-8, ASCE 7-22, ASCE 41-17, and the 2021 International Building Code. The facility is classified as a Critical Facility with Building Risk Category IV and Seismic Design Category C, requiring a Component Importance Factor (Ip) of 1.5 for all non-structural components. Mapped seismic parameters include short-period spectral response acceleration (Sds) of 0.150g and 1.0 second spectral response acceleration (Sd1) of 0.095g at Site Class C. Non-structural components subject to these requirements include mechanical systems (heating, ventilating, air-conditioning, boilers, chillers, and utility plant equipment), electrical elements (power systems, switchgear, generators), architectural elements (facades, partitions, ceilings), and transportation elements (elevators, dumbwaiters).
Shop drawings and delegated design calculations must be prepared by a professional structural engineer with minimum five years' experience in seismic restraint design, registered in the state where the project is located. Submittal requirements include complete bracing and anchorage drawings with calculations, seismic design criteria, computer model documentation, and ICC-ES evaluation reports or OSHPD pre-approvals for post-installed anchors. Products specified include structural steel (ASTM A36), steel pipe (ASTM A53/A53M Grade B), bolts and nuts (ASTM A325 or A490), and concrete with 28-day compressive strength of 20.7 MPa (3,000 psi). Construction requirements mandate equipment supports and anchorages capable of withstanding seismic design forces, thermal expansion accommodation, flexible piping connections for equipment, and testing of 10 percent of anchors in masonry and concrete per ASTM E488 and ACI 355.2 prior to final inspection.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
558-22-172 Replace Chillers for AHU 1 & 2 Durham VAMC
SEISMIC RESTRAINT
REQUIREMENTS FOR NON-
STRUCTURAL COMPONENTS
13 05 41- 1
SECTION 13 05 41
SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS
PART 1 - GENERAL
1.1 DESCRIPTION:
A. Provide seismic restraint in accordance with the requirements of the drawings, VA Handbook H18-8: Seismic Design Requirements and this specification in order to maintain the integrity of non-structural components and equipment of the building so that they remain safe and functional in case of seismic event.
B. The design of seismic restraints of non-structural components to resist seismic load shall be based on Seismic Design parameters indicated below in accordance with VA H-18-8 in conjunction with ASCE 7 and ASCE 41, as specified in H-18-8 Section 4.0, for existing building retrofit projects. Specific requirements for Critical and Essential facilities are covered in Section
4.0 of H-18-8, including applying Ip = 1.5 for all nonstructural components in Critical facilities.
1. International Building Code 2021 Edition
2. American Society of Civil Engineers Seismic Evaluation and Retrofit of Existing Buildings
ASCE 41-17.
3. American Society of Civil Engineers Minimum Design Loads and Associated Criteria for
Buildings and Other Structures ASCE 77-22
4. Facility Occupancy Category per VA H-18-8: Critical Facility
5. Site Class: C
6. Building Risk Category: IV
7. Mapped MCER 0.2 s period Spectral Response Acceleration Parameter (Ss): 0.170g
8. Mapped MCER 1.0 s period Spectral Response Acceleration Parameter (S1): 0.067g
9. Short period Spectral Response Acceleration Parameter (Sds): 0.150g
10. Short period Spectral Response Acceleration Parameter (Sd1): 0.095g
11. Building Seismic Design Category: C
12. Component Importance Factor(s) (Ip): 1.5
13. Components Response Modification Factors(Rp): Per ASCE 7-22
14. Components Overstrength Factors: Per ASCE 7-22
C. Definitions: Non-structural building components are components or systems that are not part of the building’s structural system whether inside or outside, above or below grade. Non-structural components of buildings include but are not limited to (Refer to VA H-18-8, ASCE 7 and ASCE 41 for additional examples):
1. Architectural Elements: Facades that are not part of the structural system and its shear resistant elements; cornices and other architectural projections and parapets that do not function structurally; glazing; nonbearing partitions; suspended ceilings; stairs isolated from the basic structure; cabinets; bookshelves; medical equipment; and storage racks, etc.
2. Electrical Elements: Power and lighting systems; substations; switchgear and switchboards; auxiliary engine-generator sets; transfer switches; motor control centers;
motor generators; selector and controller panels; fire protection and alarm systems;
special life support systems; and telephone and communication systems, etc.
Durham VAMC
SEISMIC RESTRAINT
13 05 41- 2
3. Mechanical Elements: Heating, ventilating, and air-conditioning systems; medical gas systems; plumbing systems; sprinkler systems; pneumatic systems; boiler/chiller/utility plant/other equipment and components, etc.
4. Transportation Elements: Mechanical, electrical and structural elements for transport systems, i.e., elevators and dumbwaiters, including hoisting equipment and counterweights.
1.2 RELATED WORK:
A. Cast-In-Place Concrete: Section 03 30 00, CAST-IN-PLACE CONCRETE
B. Structural Steel Framing: Section 05 12 00, STRUCTURAL STEEL FRAMING
C. Metal Fabrication: Section 05 50 00, METAL FABRICATIONS
1.3 QUALITY CONTROL:
A. Shop-Drawing Preparation:
1. Non-structural seismic restraint systems shop drawings and delegated design calculations shall be prepared by a professional structural engineer with a minimum of 5 years’ experience in the design and detailing of seismic force restraints. The professional structural engineer shall be registered in the state where the project is located and submit qualifications with list of projects illustrating compliance with the experience requirement of this section.
2. Submit design tables and information used for the design-force levels, stamped and signed by a professional structural engineer registered in the State where project is located.
B. Coordination:
1. Do not install seismic restraints until seismic restraint submittals are approved by the
Contracting Officers Representative (COR).
2. Coordinate trapezes or other multi-pipe hanger systems prior to submission of shop drawings for review.
C. Seismic Certification:
D. In structures assigned to Seismic Design Category C, D, E, or F, permanent equipment and components are to have Special Seismic Certification in accordance with requirements of section 13.2.2 of ASCE 7, including those required in existing buildings within Section 13.7.1.3.3, 13.7.7.3.3 and 13.7.8.3.3 of ASCE 41, except for equipment and components that are considered inherently rugged as listed in Section 4.2.2 of VA H18-8, and shall comply with section 13.2.6 of ASCE 7.
1.4 SUBMITTALS:
A. Submit a complete and coordinated set of bracing and signed and sealed anchorage drawings and calculations for all non-structural elements requiring seismic restraint by the delegated professional structural engineer mentioned in Section 1.3.A.1 for review prior to installation including:
Durham VAMC
SEISMIC RESTRAINT
13 05 41- 3
1. Description, layout, and location of all items to be anchored or braced with anchorage or brace points noted and dimensioned.
2. Details of all anchorage and bracing at large scale with all members, parts brackets shown, together with all connections, bolts, welds etc. clearly identified and specified.
Details shall be coordinated with all project conditions and trades prior to shop drawing submission for review.
3. Complete calculations including but not limited to seismic design criteria, computer model input and output, seismic design forces and capacities, design tables and information used for all proprietary design elements such as post installed anchors, stamped and signed by a professional structural engineer specified in section 1.3 A.1.
4. For all post installed anchorages submit the appropriate International Code Council Engineering Service (ICC-ES) evaluation reports, California’s Office of Statewide Health Planning and Development(OSHPD) pre-approvals, or lab test reports verifying compliance with OSHPD Interpretation of Regulations 28-6.
5. Delegated professional structural engineer qualifications.
B. Submit for review prior to installation, the following for seismic protection of piping in addition to items noted in Section 1.4.A:
1. Single-line piping diagrams on a floor-by-floor basis. Show all suspended piping for a given floor on the same plain.
2. Type of pipe (Copper, steel, cast iron, insulated, non-insulated, etc.).
3. Pipe contents.
4. Structural framing for the seismic and gravity support and the main superstructure for which the bracing and or anchorage is attached.
5. Location of all gravity load pipe supports and spacing requirements.
6. Numerical value of gravity load reactions.
7. Location of all seismic bracing.
8. Numerical value of applied seismic brace loads.
9. Type of connection (Vertical support, vertical support with seismic brace etc.).
10. Seismic brace reaction type (tension or compression): Details illustrating all support and bracing components, methods of connections, and specific anchors to be used.
C. Submit for review prior to installation, the following items for seismic protection of suspended ductwork and suspended electrical and communication cables, in addition to items noted in Section 1.4.A:
1. Details illustrating all support and bracing components, methods of connection, and specific anchors to be used.
2. Numerical value of applied gravity and seismic loads and seismic loads acting on support and bracing components.
3. Maximum spacing of hangers and bracing.
1.5 APPLICABLE PUBLICATIONS:
A. The Publications listed below (including amendments, addenda revisions, supplements and errata) form a part of this specification to the extent referenced. The publications are referenced in text by basic designation only.
SPEC WRITER NOTE: Edit applicable publications to indicate the most recent edition.
B. American Concrete Institute (ACI):
355.2-19 .................................. Qualification for Post-Installed Mechanical Anchors in Concrete and Commentary
Durham VAMC
SEISMIC RESTRAINT
13 05 41- 4
C. American Institute of Steel Construction (AISC):
D. Load and Resistance Factor Design, Volume 1, Second Edition
E. ASTM International (ASTM):
A36/A36M-19 ........................... Standard Specification for Carbon Structural Steel A325-14 ................................... Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength A490-14a ................................. Standard Specification for Heat-Treated Steel Structural Bolts, 150 ksi Minimum Tensile Strength
A992/A992M-11(2015) ............ Standard Specification for Steel for Structural Shapes for Use in
Building Framing E488/E488M-18 ....................... Standard Test Methods for Strength of Anchors in Concrete
Elements
F. American Society of Civil Engineers
1. Minimum Design Loads and Associated Criteria for Buildings and Other Structures
(ASCE 7) Edition as indicated in section 1.1 B of this specification. Associated Criteria for Buildings and Other Structures ASCE 7-22
G. International Building Code (IBC) Edition as indicated in Section 1.1 B of this specification.
H. VA Handbook H18-8 Seismic Design Requirements, VA H-18-8, July 1, 2023
I. National Uniform Seismic Installation Guidelines (NUSIG)
J. Sheet Metal and Air Conditioning Contractors National Association
K. (SMACNA): Seismic Restraint Manual - Guidelines for Mechanical Systems, 3RD EDITION 2008 and Addendum
1.6 Regulatory Requirement:
A. IBC as shown in Section 1.1 B of this specification.
B. Exceptions: The omission of seismic restraints shall be allowed only in accordance with VA H18-8, ASCE 7 and ASCE 41.
PART 2 - PRODUCTS
2.1 STEEL:
A. Structural Steel: ASTM A36.
B. Steel Pipe: ASTM A53/A53M, Grade B.
C. Bolts & Nuts: ASTMA325, orA490.
Durham VAMC
SEISMIC RESTRAINT
13 05 41- 5
2.2 CAST-IN-PLACE CONCRETE:
A. Concrete: 28 day strength, f’c = 20.7 MPa (3,000 psi)
PART 3 - EXECUTION
3.1 CONSTRUCTION, GENERAL:
A. Provide equipment supports and anchoring devices to withstand the seismic design forces, so that when seismic design forces are applied, the equipment cannot displace, overturn, or become inoperable.
B. Provide anchorages in conformance with recommendations of the equipment manufacturer and as shown on approved shop drawings and calculations.
C. Construct seismic restraints and anchorage to allow for thermal expansion.
D. Testing Before Final Inspection:
1. Test 10-percent of anchors in masonry and concrete per ASTM E488, and ACI 355.2 to determine that they meet the required load capacity. If any anchor fails to meet the required load, test the next 20 consecutive anchors, which are required to have zero failure, before resuming the 10-percent testing frequency.
2. Before scheduling Final Inspection, submit a report on this testing indicating the number and location of testing, and what anchor-loads were obtained.
3. Construct seismic restraints and anchorages to not interfere with other trades or damage existing or in-situ elements of the constructed building.
3.2 EQUIPMENT RESTRAINT AND BRACING:
A. See drawings for equipment to be restrained or braced.
3.3 MECHANICAL DUCTWORK and piping; boiler plant stacks and breaching; electrical busways, conduits, and cable trays; and telecommunication wires and cable trays
A. Support and brace mechanical ductwork and piping; electrical busways, conduits and cable trays; and telecommunication wires and cable trays including boiler plant stacks and breeching to resist directional forces (lateral, longitudinal and vertical).
B. Brace duct and breeching branches with a minimum of 1 brace per branch.
C. Provide supports and anchoring so that, upon application of seismic forces, piping remains fully connected as operable systems which will not displace sufficiently to damage adjacent or connecting equipment, or building members.
D. Piping Connections: Provide flexible connections where pipes connect to equipment. Make the connections capable of accommodating relative differential movements between the pipe and equipment under conditions of earthquake shaking.
- - - E N D - - -