This document is an amendment to a Request for Quotation (RFQ) for Electrical Wire Installation issued by the Department of Veterans Affairs, Veterans Integrated Service Network 6. The amendment provides responses to vendor questions regarding the requirements.
The key details are:
- The contract is for the installation of electrical wiring, including two pulls of 50 feet and 210 feet, each containing 4 #3 conductors and 1 #8 ground.
- The period of performance is to be determined.
- The NAICS code is 238210 - Electrical Contractors and Other Wiring Installation Contractors, and the product/service code is N059 - Installation of Equipment - Electrical and Electronic Equipment Components.
- Delivery will be to the Charles George Asheville VA Medical Center.
- Vendor questions and answers are provided, covering topics such as terminations, breakers, and wire type.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24624Q1245 0003.docx | DOCX document | |
| 36C24624Q1245 0001.docx | DOCX document | |
| WD - 2015-4369 Rev 23 - 13 May 2024.pdf | ||
| 36C24624Q1245.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
08-21-2024
James Risbon Department of Veterans Affairs Network Contracting Office 6 100 Emancipation Drive Hampton VA 23667
Department of Veterans Affairs Network Contracting Office 6 100 Emancipation Drive Hampton VA 23667 To all Offerors/Bidders
36C24624Q1245 08-19-2024
X
See CONTINUATION Page
Vendor Question / Answer Amendment
X Amendment administered to 36C24624Q1245 (Electrical Wire Instillation).
The purpose of this amendment is to post responses to vendor questions (See Section A3).
All question should be emailed to James.Risbon@va.gov NLT 4PM (EST) on 08-21-2024.
CONTINUATION PAGE
A.1 PRICE/COST SCHEDULE
ITEM INFORMATION
| ITEM NUMBER |
| DESCRIPTION OF SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1.00 |
| LT |
| __________________ |
| __________________ |
Provide all materials required for (2) electrical wire pulls:
(1) 50 foot wire pull
(2) 210 foot wire pull Each pull contains (4) #3 conductors and (1) #8 ground.
Contract Period: Base POP Begin: TBD POP End: TBD PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: 6145 - Wire and Cable, Electrical MANUFACTURER PART NUMBER (MPN): None
| 1.00 |
| JB |
| __________________ |
| __________________ |
Provide all labor required for the instillation of electrical wiring.
* Special Note: All raceways have already been installed. This requirement is the the pulling of the wires only".
Contract Period: Base POP Begin: TBD POP End: TBD PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: N059 - Installation of Equipment - Electrical and Electronic Equipment Components MANUFACTURER PART NUMBER (MPN): Service
| GRAND TOTAL |
| __________________ |
A.2 DELIVERY SCHEDULE
| ITEM NUMBER |
| SHIPPING INFORMATION |
| QUANTITY |
| DELIVERY DATE |
| 0001 to 0002 |
| SHIP TO: |
| Charles George Asheville VA Medical Center (637) |
1100 Tunnel Road Asheville, NC 28805
USA
TBD
| MARK FOR: |
| Stephen Pinkerton |
828-298-7911 EXT 41115
stephen.pinterton@va.gov
| FOB: |
| DESTINATION |
A.3 VENDOR QUESTION / ANSWER
RFQ 36C24624Q1245 Electrical Wire Instillation (Amendment #2) The following questions were submitted on 08-20-2024.
Vendor Questions (Black) and Answers (Red)
Question 1: The solicitation states that the pulls are 50' and 210' feet. Do you need an extra 5' on each side for termination purposes?
Answer 1: No. This is the total length including terminations.
Question 2: On the 5th floor of the utility room where the panel is located, is there enough room to set up a pulling station?
Answer 2: The 210' pull, we would suggest pulling from the 5th floor to the Penthouse.
The 50' pull, we would suggest pulling from the Penthouse to the 5th floor.
Question 3: Will we be terminating after its been pulled, if we are terminating the wires, is there an existing breaker in the panel or will there be one provided to us.
Answer 3: Yes, terminations are required. Breakers will be provided.
Question 4: Will the wire need to be copper or aluminum?
Answer 4: Copper
Question 5: What is the amperage that is being pulled?
Answer 5: 100 amp 3 phase/4 wire with neutral.
End to Question / Answers from 08-20-2024