This document contains questions and answers regarding solicitation 36C24623Q1183 for breaker testing services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6 is seeking to have breakers tested in vaults 3, 4, and 5, which are rated above 80 Calorie arc flash hazards. Contractors should plan to provide a 480 generator for testing purposes, as shutting down the main busses would cause the hospital to revert to emergency power which does not have enough excess capacity. The VA electrical shop will isolate and lock out switchgear as required. Cleaning of switchboards is desired but may not be possible without a full shutdown. IR scans will only be conducted in areas below a 60 Calorie protection limit. Replacement parts are not required to be on-site for the breakers being tested, only for molded case breakers mentioned in the original statement of work. Work will be done on weekends unless night hours are available. Testing of energized busses is not acceptable due to arc flash hazards, so breakers will need to be racked out one at a time. Test results may be submitted in PDF format.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| HH 3 Report 002.pdf | ||
| Vault 1 Initial Report 002.pdf | ||
| Vault 2 Initial Report 002.pdf | ||
| 36C24623Q1183 0001.docx | DOCX document | |
| HH 5 Arc Flash Report 002.pdf | ||
| HH 4 Report 002.pdf | ||
| Site Visit Instructions.docx | DOCX document | |
| 36C24623Q1183_2.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7.
ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF
PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE
OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO:
Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERE
D CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR
OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendmen t, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED
STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF
CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF
SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 9/6/2023 Department of Veterans Affairs Network Contracting Office 6 100 Emancipation Drive Hampton VA 23667 Department of Veterans Affairs Network Contracting Office 6 100 Emancipation Drive Hampton VA 23667 To all Offerors/Bidders
36C24623Q1183 09-05-2023
X X
X
Solicitation 36C24623Q1183 is hereby amended as follow.
1. To post all Questions and Answers
Warren A Pennil Contracting Officer 9/6/2023
QUESTIONS AND ANSWERS
36C24623Q1183 Breaker Tester
Q3. Will the VA be providing test power?
A3. Shutting down the main busses will cause the hospital to revert to emergency power, which there is not enough excess power in each vault for testing, therefore contractor should plan on providing a 480 generator for testing.
Q4. Is the VA going to be responsible for isolation of the switchboard? Vaults 3, 4 ,5 are rated above 80 Cal Arc flash hazard, no PPE exist for this Cal range.
A4. Yes, VA Electrical Shop will switch and lock out Switch Gear.
Q5. Does the VA want the backs of the switchboard cleaned?
A5. Yes, the VA wants the switchboard cleaned, but in the event we are unable to have a complete shutdown (emergency surgery etc.) the cleaning of the bus is not feasible.
Q6. IR scan is not possible with covers in place and covers cannot be removed while energized due to 80cal plus Arc Flash Hazard. How should this be accomplished?
A6. IR scans will only be required in areas that do not exceed 60 Cal PPE protection limit.
Q7. Requirement H states that we should have replacement parts on hand. Normally this requirement is for the molded case units that are not being tested. Do we need to have replacement parts for the breakers that are being tested?
A7. The original SOW included molded case breakers; the spare parts were only intended for those breakers. It is not feasible to have spare parts on hand for failed breakers because of the size and type of breakers in this testing scenario.
Q8. Will all work be done on weekends or are night hours available?
A8. Please see Solicitation B.4, 1. Work Hours or Hours Of Operation for answer
Q9. Busses are 80 Cal or more and will need to be shutdown to be tested. Is that acceptable?
A9. The hospital’s goal will be to keep as much power on as possible, therefore the best plan would be to rack out one breaker at a time for testing. If there are unforeseen circumstances or if racking out the breakers are determined to expose contractor or employees to hazards above the 60 Cal threshold, then there will have to be a shutdown to perform testing.
Q10. Are test result acceptable in PDF format?
A10. Yes, PDF is acceptable.