About this file

This document contains a presolicitation notice and related federal contract opportunity for firestop maintenance services. The Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 6 will be awarding a contract for inspection and repair of fire and smoke rated barrier walls in buildings 1, 3, 70, 71, 72, and 73 at the Fayetteville VA Medical Center in North Carolina. Services will include developing a firestop maintenance program, performing quarterly life safety surveys, inspecting fire and smoke rated barrier walls, installing UL certified firestop systems, obtaining engineering judgments, and maintaining documentation. Interested service disabled veteran owned small businesses shall provide evidence of qualifications and submit responses by December 5, 2022 at 10:00 AM Eastern Time. The awarded contractor must perform inspection and repair services and provide a one year warranty on all materials and workmanship.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Presolicitation Notice Presolicitation Notice

SUBJECT*
VA-23-00006783/565-23-1-5123-0011 FIRESTOP MAINTENANCE SERVICE VAMC FAYETTEVILLE, NORTH CAROLINA

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
23667
SOLICITATION NUMBER*
36C24623Q0213
RESPONSE DATE/TIME/ZONE
12-05-2022 10:00 EASTERN TIME, NEW YORK, USA
ARCHIVE
99 DAYS AFTER THE RESPONSE DATE
SET-ASIDE
SDVOSBS
PRODUCT SERVICE CODE*
S202
NAICS CODE*
238310
PLACE OF PERFORMANCE
FAYETTEVILLE VAMC

2300 Ramsey Street

FAYETTEVILLE NORTH CAROLINA

POSTAL CODE
28301-3856
COUNTRY
USA

CONTACT INFORMATION

CONTRACTING OFFICE ADDRESS

Department of Veterans Affairs Network Contracting Office 6 100 Emancipation Drive Hampton VA 23667

POINT OF CONTACT*

FIRESTOP PROTECTION

Leonard Overman Leonard.Overman@va.gov 757-728-7054

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

Inspect/Repair Firestop Maintenance Program

GENERAL SCOPE OF WORK:

The Fayetteville VAMC currently has the need for a contractor to establish a firestop maintenance program and provide an inspection and repair of the fire/smoke rated barrier walls in Building 1, 3, 70, 71, 72, and 73 of the Medical Center.

The contractor will, upon successful award of the contract provide an inspection report of the various fire/smoke barriers to include supplying all labor, equipment, parts, material and expertise to develop a firestop maintenance program.

General Information

Company must be recognized as a service disabled veteran- owned small business and provide documented evidence of company’s history, personnel and facility capabilities with their bid.

1. Scope of work

a. Perform quarterly life safety surveys and provide updated Statement of Condition drawings.

b. Inspection of fire/smoke rated barrier walls (smoke resistive hazardous areas). Walls included are: rated barrier walls.

i. 3 hour fire barriers

ii. 2 hour fire barriers

iii. 1 hour fire barriers

iv. 2 hour fire/smoke barriers

v. 1 hour fire/smoke barriers

vi. 30 minute smoke barriers

vii. Smoke resistive hazardous areas

viii. Non-rated smoke partition

ix. Non-rated smoke barrier.

c. Life Safety Drawing may be updated at anytime due to construction completion or reviews by appropriate Fire Protection Engineer.

2. Demo

a. Installation of UL firestop systems may require removal of foreign material (including, but not limited to, drywall mud, mortar, spray foam, fireproofing, and structolite) to create required annular space to accept UL firestop system

3. Installation

a. Install UL firestop systems per the manufactures UL cut sheets for all penetrations and joints which are currently not sealed (or the post installed firestop product surface area) under 12” x 12” (or the aggregate square inch equivalent) found to be deficient.

b. Install UL firestop system identification labels to all repaired penetrations and or joints.

4. Engineering Judgements

a. When field conditions are outside the parameters of an UL tested system and engineering judgment will be obtained from the manufacture and installed.

5. Documentation

a. All information will be recorded electronically during quarterly inspections and will be maintained using an Electronic Drawings-based tracking and verification program that utilizes (facility provided) life safety drawings to denote all inspection and deficiency locations. Opening any of the marks/notes on the drawings will display a page detailing the deficiency type, UL system deployed, product used, wall type and date/time of repair as well as before and after pictures.

b. One copy of the following reports will be supplied in both electronic and hard-copy format:

i. A spreadsheet report documenting the deficiencies repaired, location, corrective action, product used and UL system. UL cut sheet for each system used will also be supplied

ii. Pictures of each deficiency (before and after repair) and UL system employed

iii. A report listing outstating large deficiencies that fall outside the 12”x 12” parameters along with photos, recommended ILSM, UL recommendation for repair, and cost estimate.

1. Repairs greater than 12” x 12” will be funded on a separate CLIN as needed.

iv. An open item report listing areas that were not accessible

6. A one year warranty on all materials and workmanship.

*=Required Field
Presolicitation Notice

Presolicitation Notice

File details come from the government source that posted it. Updated .