About this file

This is a Sources Sought Notice for emergency generator comprehensive maintenance at the Washington DC VA Medical Center. The Department of Veterans Affairs (VA) NCO 5 is seeking potential contractors to provide a 5-year service contract for preventative maintenance of emergency generator systems, with performance period from 12/01/25 to 11/30/30 and four potential renewal options. The solicitation (36C24526Q0063) requires interested entities to submit detailed information including business type, socio-economic status, contact information, capability statements, previous experience, available contract vehicles, service capabilities, and certifications.

The comprehensive maintenance services involve monthly, quarterly, and annual inspections of emergency generators, automatic transfer switches, fuel systems, and associated equipment, adhering to NFPA 110, Joint Commission standards, and VA policies. Key requirements include 24/7 emergency response with a 4-hour maximum onsite response time, maintenance by factory-trained technicians, compliance with federal/state/local codes, and detailed reporting. The solicitation targets entities capable of self-performing or subcontracting while meeting limitations, with responses due by 10/24/2026 at 11:00 AM EST, to be submitted via email to William.Galletta@va.gov.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sources Sought Notice Sources Sought Notice

SUBJECT*
Emergency Generator Comprehensive Maintenance

Washington DC Medical Center 5 Year Service Contract

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
21201
SOLICITATION NUMBER*
36C24526Q0063
RESPONSE DATE/TIME/ZONE
10-24-2025 11am EASTERN TIME, NEW YORK, USA
ARCHIVE
60 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N

SET-ASIDE

PRODUCT SERVICE CODE*
J061
NAICS CODE*
238210
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Baltimore VAMC

NCO5

10 N Greene St Baltimore MD 21201

POINT OF CONTACT*

Contracting Officer William Chris Galletta William.Galletta@va.gov Services Team One

PLACE OF PERFORMANCE

ADDRESS
Department of Veterans Affairs

Washington DC VAMC

50 Irving St

Washington DC

POSTAL CODE
20422
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL
https://www.va.gov/washington-dc-health-care/
URL DESCRIPTION
VA
AGENCY CONTACT’S EMAIL ADDRESS
william.galletta@va.gov
EMAIL DESCRIPTION
NCO 5

DESCRIPTION

Department of Veterans Affairs NCO 5 is seeking responses from entities that are interested in this procurement and consider themselves to have the resources, capabilities, and qualifications necessary to provide the services required for Washington DC VA Medical Center.

Please respond to this RFI/Sources Sought 36C24526Q0063 with your:

1. Business name (including Unique Entity ID (SAM.gov)

2. Business type, socio-economic status (e.g., Veteran-Owned, Woman-Owned, Disadvantaged Small Business, 8(a), etc.), and

3. Person of contact (including telephone number & email address).

4. Capability statement and summary of previous experience providing these types of services for the Veterans Health Administration or other similar facilities.

5. Available contract vehicles (GSA FSS, etc.) for use by Department of VA (include applicable NAICS)

6. Brief Summary of categories of services that your company can/cannot provide.

7. Certification(s) / Licenses for meeting the local requirements to provide these services at the Washington DC VAMC (if applicable)

8. Confirmation that your organization has the capability & expertise to meet the performance requirements while complying with applicable limitations in subcontracting by responding to the questions below with your response:

a. Do you intend to self-perform this effort?

b. If you are located outside the immediate area, how will you self-perform?

c. Or do you intend to subcontract work under this contract?

d. If you intend to subcontract work under this contract, how will you ensure compliance with the limitations on subcontracting?

Response Instructions:

Responses must be received by Friday 10/24/ 2026 @ 11:00 AM EST. Responses to the information requested above must be submitted via email to William.Galletta@va.gov

Generator Preventative Maintenance Washington DC VA Medical Center 50 Irving St. NW, Washington DC 20422

1. Introduction This Statement of Work (SOW) outlines the requirements for providing preventative maintenance services for emergency generators and associated equipment at the Washington DC VA Medical Center, located at 50 Irving St. NW, Washington DC 20422.

2. Scope of Work The Contractor shall furnish all labor, materials, equipment, supervision, and transportation necessary to provide comprehensive preventative maintenance services for the facility’s emergency generator systems in accordance with the manufacturer’s recommendations, NFPA 110, Joint Commission standards, and VA policies.

2.1 Equipment Covered

- Main emergency generators (list types, sizes, serial numbers if known)

- Automatic Transfer Switches (ATS)

- Generator day tanks and fuel systems

- Associated control panels and switchgear

2.2 Preventative Maintenance Tasks

At a minimum, services shall include but are not limited to:

A. Monthly Inspections:

- Visual inspection of generator and components

- Check fluid levels (oil, coolant, fuel)

- Inspect and record battery voltage and condition

- Inspect belts, hoses, and connections for wear/leaks

- Inspect exhaust system

- Check for abnormal noise or vibration

- Run generator under load per NFPA 110 and record readings

- Inspect ATS for proper operation and cleanliness

- Record all readings and observations

B. Quarterly Inspections:

- All monthly inspection tasks

- Inspect and test battery charging system

- Inspect air intake and exhaust system

- Inspect the engine and alternator for leaks

- Check and clean air filters

- Inspect and test generator control panel

C. Annual Maintenance:

- All monthly and quarterly tasks

- Change engine oil and filters

- Change fuel filters and water separators

- Change air filter elements

- Inspect and test the coolant system; flush and replace coolant as needed

- Inspect and test block heaters

- Clean generator and ATS enclosures

- Test and calibrate all safety devices and alarms

- Load bank testing (if required by VA or code)

- Provide comprehensive written report of all findings, actions, and recommendations

2.3 Emergency Service

- Contractor shall provide 24/7 emergency response with a maximum 4-hour onsite response time for generator failures.

3. Performance Requirements

- All maintenance shall be performed by qualified, factory-trained technicians.

- Work shall comply with all applicable federal, state, and local codes, including NFPA 110, OSHA, and VA regulations.

- All work shall be scheduled in advance with the VA Medical Center’s designated representative.

4. Deliverables

- Maintenance checklists and service reports after each visit

- Annual comprehensive report with recommendations

- Immediate notification of any deficiencies or potential failures

- Documentation of all parts replaced and services performed

5. Schedule

- Preventative maintenance services shall be performed per the following schedule:

- Monthly: Inspections and testing

- Quarterly: Enhanced inspections

- Annually: Comprehensive maintenance

- Emergency response: 24/7/365 availability

6. Hours of Work

- Routine maintenance shall be performed during normal business hours (Monday-Friday, 7:00 am – 5:00 pm), unless otherwise approved by the VA Medical Center.

- Emergency services must always be available.

7. Safety and Security

- Contractor personnel shall comply with VA Medical Center safety, infection control, and security requirements.

- All personnel must check in and out with Engineering Service upon arrival and departure.

8. Points of Contact

- VA Medical Center Representative: TBD

- Contractor Project Manager: [Name, Title, Phone, Email]

9. Period of Performance

- The period of performance for this contract is 12/01/25-11/30/30 with 4 options for renewal.

10. Quality Assurance

- The VA Medical Center reserves the right to inspect work at any time and request corrective action for any deficiencies identified.

*= Required Field
Sources Sought Notice

Sources Sought Notice

File details come from the government source that posted it. Updated .