Fire Panel Questions

1. At the very least may we get a copy of the full building report from last year’s test and inspection? It’s in about 5 binders (Not all electronic) but, yes

1. Elevator smokes will require coordination with the Elevator maintenance people; access to equipment room, etc. Is there an existing Elevator contractor for VAMC? Yes, Landmark and Quality elevator

1. How many elevators are on the campus that will need to be serviced? What buildings are they in? 7 in main hospital, 1 in our Dom, 1 in our CLC, 1, in our dementia ward

1. How is the current system being monitored now? Our central dispatch center here on campus/Fire dept.

1. Does the current system go out to a Central Station and then to Emergency services on VAMC site? Dialer in panel? No

1. Are there any drawings of fire riser or as built? Yes, request through our engineering dept.

7.Any buildings/ areas require lift for accessing devices? No

8.How many annunciators are there? 36

9.We will need access to panel software and passcode. Is this possible? If you are certified to work on EST systems in this region

10. The most current sprinkler system reports? (Perhaps Chief Gray can provide the full reports for both FA and Sprinklers for last year?) yes

11. On our campus we have the following:

Control Devices – 125 Initiating Devices – 1500 Indicating – 700 Sprinkler Systems – 80 wet and Dry systems Panels - 38