Fire Door RV FINAL SOW.docx
DOCX document 68 KB Posted
- Solicitation number
- 36C24425Q0553
About this file
This is a Statement of Work (SOW) for Fire Door Remediation at the Wilkes Barre Veterans Medical Center (VAMC) in Pennsylvania. The project requires correcting deficiencies in approximately 154 fire, smoke, and hazardous door assemblies to comply with National Fire Protection Association (NFPA) standards and Joint Commission Environment of Care regulations. Specific issues include undercuts, hardware problems, non-latching doors, frame penetrations, and improper door ratings across various building floors and locations.
The solicitation (36C24425Q0553) is a Service-Disabled Veteran Owned Small Business (SDVOSB) set-aside with a NAICS code of 561790 and a business size standard of $9.0 million. Contractors must be fully qualified Fire Safety Experts (FSEs) with formal training in fire door inspection and maintenance. Quotes are due by May 8, 2025, and must be submitted via email with past performance references, completed certifications, and detailed pricing information. The project requires comprehensive documentation of all corrective actions, with work to be performed Monday through Friday during normal business hours.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24425Q0553 0002.pdf | ||
| 36C24425Q0553 0002_1.docx | DOCX document | |
| 24-WBVA-Doors-HAZ_Suite-Drawings_5.28.24.pdf | ||
| 24-WBVA-Door-Drawings_4.30.24.pdf | ||
| RFI Questions 36C24425Q0553.pdf | ||
| Amendment 36C24425Q0553 0001.pdf | ||
| 36C24425Q0553 0001_1.docx | DOCX document | |
| WD 2015-4239 Luzerne County PA REV 28 dated 122324.pdf | ||
| 36C24425Q0553_1.docx | DOCX document | |
| Site Visit Information.docx | DOCX document | |
| RM Language for Contracts.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work Fire Door Remediation Department Of Veterans Affairs Wilkes Barre Veterans Medical Center (VAMC) 1111 East End Blvd, Wilkes-Barre Pa 18711
1.0 SCOPE OF WORK:
Provide all parts and labor to correct deficiencies and bring all fire, smoke, hazardous door assemblies into compliance with current regulations found in the latest inspections preformed. Repairs and ratings shall be in accordance with the most recent edition of The National Fire Protection Association’s (NFPA) standard “NFPA 80: Standard for Fire Doors and Other Opening Protectives, Chapter 5 Inspection, Testing, and Maintenance” and The Joint Commission, Environment of Care (EC) standards EC.02.03.05.EP 25. Inspection and testing of door assemblies by qualified person. To comply with National Fire Protection Association (NFPA) 90A; 5.4.7, NFPA 80, and NFPA 105 and Joint Commission Standard EC.02.03.05.
Please note that all the deficient items to be remediated are found in the most recent fire door inspection report. Review the included report photos, descriptions, and spreadsheet to develop pricing, recommendations, and alternate solutions if applicable as part of the proposal.
1.1 The scope of work includes the provision of all labor, materials, equipment, tools, supervision, and quality assurance necessary to correct the attached listing of identified deficiencies at the Wilkes-Barre VAMC. Under this project:
1.1.1 All known deficiencies, as identified in the report and spreadsheet, shall be corrected by the contractor. The contractor shall maintain and provide to the Contracting Officer Representative or designated program representative, a report documenting all corrective actions taken. This documentation shall be maintained by COR or designated program official. The report shall list the deficiency and location and include a general description of work performed and the contractor’s certification of item correction.
1.1.2 Doors requiring removal of Acrovyn must be primed and painted with a color choice provided by the VA.
1.1.3 The report shall be provided to the COR or designated program official within 10 days of physical completion. The report shall be provided electronically in pdf format.
1.1.4 Any work performed which impacts the systems (i.e. Johnson Controls, Metasys, etc.) shall be fully incorporated into the existing system. Fully incorporated is to include the complete installation and operation of fully compatible devices which are tied into the existing system and added to the existing graphical interface programming if appropriate. This work may require the successful bidder to involve the original equipment manufacturer for the performance of the work.
1.1.4 The contractor is responsible for reviewing all items within the contract for assurance that the contractor can meet all required work and inspection criteria.
1.1.5 The contractor shall attempt to bring doors into compliance by adjusting, replacing minor hardware components, recommended corrective action repairs and/or replacements based on the completed report.
2.0 SPECIFICATIONS:
2.1 All work shall be designed and completed in accordance with all applicable Federal, State and Local guidelines/specifications/design standards and in compliance with NFPA, with special emphasis on NFPA 101, 80 and 105 most current editions.
3.0 HOURS OF WORK:
3.1 The Contractor shall coordinate work schedule with the COR or designated Program Official. Work hours are Monday through Friday 8 am – 4:30 pm.
Work may be required to be performed during normal duty hours.
4.0 CONTRACTOR RESPONSIBILITIES:
4.1 The contractor shall be responsible for furnishing all material, labor and/or equipment required to perform all work in this contract. The Government’s review, approval, acceptance of, or payment for services required under this contract shall not be construed to operate as a waiver of any rights under this contract or of any cause of action arising out of the performance of this contract. The Contractor shall be and remain liable to the Government in accordance with applicable laws for all damages to the Government caused by the Contractor’s negligent performance of any of these services furnished under this contract.
4.2 Accident Reports: The Contractor shall immediately report all accidents resulting in property damage and/or personal injury or death directly to the Government Representative and Contracting Officer.
4.3 The Contractor shall be responsible for complying with all environmental protection regulations promulgated by US Environmental Protection Agency (EPA) and Commonwealth of Pennsylvania Department of Environmental Protection (DEP). Any hazardous materials used by the Contractor in performing this contract shall be properly packaged and stored in a sealed container to avoid spills and shall be promptly removed off post upon completion of the contract. All spills of hazardous materials shall be reported immediately to the Government Representative and Contracting Officer and shall be cleaned up immediately by the contractor at his own expense in accordance with EPA and DEP regulations.
4.4 Hazardous wastes are as defined in EPA regulations 40 CFR 261. The Contractor shall be the official waste generator for any hazardous waste generated through performance of this contract unless specified otherwise in this contract. The Contractor shall not store any hazardous waste in this government property without obtaining prior permission and related instructions from the Contacting Officer. Hazardous wastes shall be moved off post and disposed as they are generated or whenever requested by the Contracting Officer. In no case shall the wastes remain on the government property after completion of this work. It shall be Contractor’s responsibility to comply with EPA 40 CFR 260265 and DER Code 25 CH 75 regulations concerning hazardous waste generation, storage, treatment, and disposal.
4.5 The Contractor shall be responsible for following National Fire Protection Agency (NFPA) 101 Life Safety and maintaining compliance within/around the work area during the performance of any work.
4.6 The Contractor shall be solely responsible for safety during the performance of all work. The Contractor shall coordinate his work with VA Safety through the COR or designated program official. The Contractor shall be responsible for any damage to public or private property resulting from his/her activities and shall repair or otherwise make whole such damage at no cost to Owner.
4.7 The contractor is responsible for transporting and storing all materials required during performance of this contract to and from the Wilkes Barre VAMC, the contractor shall not store any equipment or materials on-site without Program Manager approval. Any storage of contractor owned equipment or materials at the Wilkes Barre VAMC must be approved by the Contract Officer and Program Manager.
4.8 Contractors must be readily identifiable via company badge and/or company branded work shirt.
4.9 As required by the Wilkes Barre VAMC, contractor shall be responsible for all ICRA barriers; acceptable barriers may include but are not limited to Zip walls, Starc walls, rigid wall systems.
5.0 Per VA policy, negative air machines are no longer allowed to exhaust into an occupied space. Contractor must coordinate with the POC prior to deploying negative air machines (HEPA).
5.1 Contractor parking will be provided in the rear of the facility closest. For additional information please coordinate with the POC.
5.0 SPECIFICS:
5.1 PDF spreadsheet Deficiency Report
5.2 Approximately 154 doors identified with various noted inspection report deficiencies such as:
· Clearance issues
· Hardware issues
· Rating label issues
5.2 PDF Fire/Smoke Door Compliance Report for reference. Date range: 2/12/2024 – 2/20/2024.
5.4 PDF Hazardous/Suite Door Inspection Report for reference. Date Range:2/21/24-2/22/24
5.5 PDF Life Safety Plan Dated 3/23/23
6.0 COMPETENCY OF PERSONNEL SERVICING EQUIPMENT:
6.1 Each respondent must have an established business, with an office and full-time staff. The staff includes a "fully qualified" FSE and a "fully qualified" FSE who will serve as the backup.
6.2 "Fully Qualified" is based upon training and on experience in the field. For training, the FSE(s) has successfully completed a formalized training program for the inspection, testing and maintenance of fire door assemblies, IAW the most recent edition of NFPA 80.
6.3 The FSEs shall be authorized by the Contractor to perform the maintenance services. All work shall be performed by "Fully Qualified" competent FSEs. The Contractor shall provide written assurance of the competency of their personnel and a list of credentials of approved FSEs for each make and model the Contractor services at the VAMC. The CO may authenticate the training requirements, request training certificates or credentials from the Contractor at any time for any personnel who are servicing or installing any VAMC equipment. The CO and/or COR specifically reserve the right to reject any of the Contractor's personnel and refuse them permission to work on the VAMC equipment.
6.4 If subcontractor(s) are used, they must be approved by the CO; the Contractor shall submit any proposed change in subcontractor(s) to the CO for approval/disapproval.
B.2 PRICE/COST SCHEDULE
ITEM INFORMATION
| ITEM NUMBER |
| DESCRIPTION OF SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 0001 |
| Fire Door Remediation |
| 1.00 |
| JB |
| __________________ |
| __________________ |
Major repairs IAW of the SOW. Services provided are estimated, actual usage under this CLIN will vary based on agreed upon remediation schedule, pricing, and effort.
Approximately 154 doors This CLIN will be funded as needed, any unused funding will be de-obligated at the end of the performance period. Hourly rates for services under this CLIN are as follows:
Regular: $ Contract Period: Base POP Begin:
POP End:
PRINCIPAL NAICS CODE: 561790 - Other Services to Buildings and Dwellings PRODUCT/SERVICE CODE: H312 - Inspection - Fire Control Equipment
| SUB TOTAL |
| __________________ |
Inv # Inspect Date
Building
FLR
Location
Type of Door Door Rating
Assessment Comments
Repair comments
12-02a
2/12/24 Wilkes Barre
| Stair 3 double door |
| Fire/Smoke Door FD |
Undercut
12-02b
Wilkes Barre
| Stair 3 double door |
| Fire/Smoke Door FD |
12-06
Wilkes Barre
| Stair 1 MER |
| Fire/Smoke Door FD |
Non latching
11-11
Wilkes Barre
| Staff only C11-21 |
| Linen Chute FD |
10-17
Wilkes Barre
| In laundry chute C10-12 room ceiling |
| Access Door FD |
Non self closing door
8-11
2/13/24 Wilkes Barre
| MER C8-56 |
| Fire/Smoke Door FD |
Undercut Vertical gap
7-05
Wilkes Barre
| Data C7-46A |
| Fire/Smoke Door FD |
7-07
Wilkes Barre
| Data C7-55 |
| Fire/Smoke Door FD |
7-10
Wilkes Barre
| MER C7-50 |
| Fire/Smoke Door FD |
Undercut Clearance
7-14
Wilkes Barre
| Electrical shaft C7 02 |
| Fire/Smoke Door FD |
6-01
Wilkes Barre
| Stair 2 |
| Fire/Smoke Door FD |
Insufficient rating on glass - replace
6-06
Wilkes Barre
| Ecloset C6-74 |
| Fire/Smoke Door FD |
5-08
Wilkes Barre
| Data C5-57b |
| Fire/Smoke Door FD |
Unused strike needs filler plate
5-11
Wilkes Barre
| Linen chute room C5-16 |
| Fire/Smoke Door FD |
5-12
Wilkes Barre
| Stair 5 |
| Fire/Smoke Door FD |
Latch sticking
5-15
Wilkes Barre
| Stair 1 |
| Fire/Smoke Door FD |
Top gap
4-03
Wilkes Barre
| Electrical C4-43 |
| Fire/Smoke Door FD |
Vertical gap
4-04
Wilkes Barre
| Soiled utility C4-30 |
| Fire/Smoke Door FD |
Undercut- improper repair
4-05
Wilkes Barre
| Storage C4-29 |
| Fire/Smoke Door FD |
Undercut- improper repair
4-14
2/14/24 Wilkes Barre
| Stair 4 |
| Fire/Smoke Door FD |
Frame wrapped in plastic
4-27
Wilkes Barre
| CLC stair 2 |
| Fire/Smoke Door FD |
Frame has plastic wrap on it
4-28
Wilkes Barre
| Sterile supply $-104 |
| Fire/Smoke Door FD |
4-29
Wilkes Barre
| Break room 4-108 |
| Fire/Smoke Door FD |
Non latching Frame wrapped in plastic
4-30
Wilkes Barre
| Dialysis storage 4-116 |
| Fire/Smoke Door FD |
4-34
Wilkes Barre
| Soiled 4-109 |
| Fire/Smoke Door FD |
4-37
Wilkes Barre
| Clean equipment 4-113 |
| Fire/Smoke Door FD |
Frame has plastic wrap on
4-38
Wilkes Barre
| Dialysis bulk storage 4-115 |
| Fire/Smoke Door FD |
4-39
Wilkes Barre
| Water Equipment 4117 |
| Fire/Smoke Door FD |
4-40
Wilkes Barre
| Office 4-119 |
| Fire/Smoke Door FD |
4-43
Wilkes Barre
| Soiled utility 4-138 |
| Fire/Smoke Door FD |
4-44
Wilkes Barre
| Sterile supply 04-148 |
| Fire/Smoke Door FD |
4-45
Wilkes Barre
| 04-150 storage room |
| Fire/Smoke Door FD |
4-46a
Wilkes Barre
| Xcor SB C4-54 |
| Fire/Smoke Door SD |
4-46b
Wilkes Barre
| Xcor SB C4-54 |
| Fire/Smoke Door SD |
4-48
Wilkes Barre
| CLC 4-135 clean supply |
| Fire/Smoke Door FD |
Clearance
4-49
Wilkes Barre
| Soiled utility 4-156 CLC |
| Fire/Smoke Door FD |
Improper undercut
4-50
Wilkes Barre
| CLC stair 3 |
| Fire/Smoke Door FD |
Frame penetration Frame has plastic on
4-51a
Wilkes Barre
| Xcor FB CLC outside oncology |
| Fire/Smoke Door FD |
4-51b
Wilkes Barre
| Xcor FB CLC outside oncology |
| Fire/Smoke Door FD |
4-64
Wilkes Barre
| Men's locker room to clean core |
| Fire/Smoke Door SD |
No positive latching hardware
4-65
Wilkes Barre
| Female locker room to clean core N4-122 |
| Fire/Smoke Door SD |
4-67a
Wilkes Barre
| Xcor SB by A4-81 |
| Fire/Smoke Door SD |
Missing parts of hardware/strike
4-67b
Wilkes Barre
| Xcor SB by A4-81 |
| Fire/Smoke Door SD |
Missing parts of hardware/strike
4-68a
Wilkes Barre
| Xcor SB by A4-23 |
| Fire/Smoke Door SD |
Frame penetrations
4-68b
Wilkes Barre
| Xcor SB by A4-23 |
| Fire/Smoke Door SD |
Frame penetrations
3-07
2/15/24 Wilkes Barre
| Data C3-57b |
| Fire/Smoke Door FD |
Unused strike needs filler plate
3-14a
Wilkes Barre
| Double storage doors adjacent 3-112 |
| Fire/Smoke Door FD |
Door penetrations Frame penetration Non latching
3-14b
Wilkes Barre
| Double storage doors adjacent 3-112 |
| Fire/Smoke Door FD |
Door penetrations Frame penetration Non latching
3-19a
Wilkes Barre
| Xcor FB A3-03 |
| Fire/Smoke Door FD |
Non latching- air differential in room
3-19b
Wilkes Barre
| Xcor FB A3-03 |
| Fire/Smoke Door FD |
Non latching- air differential in room
3-20b
Wilkes Barre
| MER a3-03 in back |
| Fire/Smoke Door FD |
Frame/door penetration Add 3-20a
3-25
Wilkes Barre
| CLC West Stair |
| Fire/Smoke Door FD |
Plastic wrap on frame
3-26
Wilkes Barre
| CLC stair 1 |
| Fire/Smoke Door FD |
Missing hardware screws
3-29a
Wilkes Barre
| Xcor FB by C3-28b |
| Fire/Smoke Door FD |
| Non rated opening No hardware |
| DOOR HAS BEEN REMOVED |
3-29b
Wilkes Barre
| Xcor FB by C3-28b |
| Fire/Smoke Door FD |
| Non rated opening No hardware |
| DOOR HAS BEEN REMOVED |
2-02
Wilkes Barre
| Stair 2 |
| Fire/Smoke Door FD |
Frame penetration
2-07
Wilkes Barre
| Data C2-106b |
| Fire/Smoke Door FD |
Vertical gap- excessive
2-08a
Wilkes Barre
| Xcor SB by C2-34 |
| Fire/Smoke Door SD |
Vertical gap Undercut
2-08b
Wilkes Barre
| Xcor SB by C2-34 |
| Fire/Smoke Door SD |
Vertical gap Undercut
2-22
Wilkes Barre
| CLC stair 2 |
| Fire/Smoke Door FD |
Plastic wrap on doors
2-24a
Wilkes Barre
| Xcor FB by 2-134 |
| Fire/Smoke Door FD |
Door penetrations
2-24b
Wilkes Barre
| Xcor FB by 2-134 |
| Fire/Smoke Door FD |
2-26a
Wilkes Barre
| Storage CLC by 2-114 |
| Fire/Smoke Door FD |
Down rods with no latch Door penetration
2-26b
Wilkes Barre
| Storage CLC by 2-114 |
| Fire/Smoke Door FD |
Down rods with no latch Door penetration
2-34a
Wilkes Barre
| Xcor SB by stair 3 |
| Fire/Smoke Door SD |
Vertical gap Multiple door penetrations
2-34b
2/19/24 Wilkes Barre
| Xcor SB by stair 3 |
| Fire/Smoke Door SD |
Vertical gap Multiple door penetrations
2-35a
Wilkes Barre
| Xcor SB by N2-95 |
| Fire/Smoke Door SD |
Multiple door penetrations
2-35b
Wilkes Barre
| Xcor SB by N2-95 |
| Fire/Smoke Door SD |
Multiple door penetrations
2-38a
Wilkes Barre
| Xcor SB by C2-115 |
| Fire/Smoke Door SD |
| Non latching Vertical gap |
| DOOR HAS BEEN REMOVED |
2-38b
Wilkes Barre
| Xcor SB by C2-115 |
| Fire/Smoke Door SD |
| Non latching Vertical gap |
| DOOR HAS BEEN REMOVED |
01-01
Wilkes Barre
| Stair 2 |
| Fire/Smoke Door FD |
01-05
Wilkes Barre
| MER shaft inside C1-76 |
| Fire/Smoke Door FD |
No door closer
01-09
Wilkes Barre
| Stair 3 |
| Fire/Smoke Door FD |
Improper undercut repair
01-12
Wilkes Barre
| Entrance adjacent blue elevator |
| Fire/Smoke Door FD |
No frame label- storefront aluminum Side lite deficient
01-15
Wilkes Barre
| Ecloset N1-91 |
| Fire/Smoke Door FD |
Non latching- door rubs on frame
01-19
Wilkes Barre
| Stair 1 |
| Fire/Smoke Door FD |
01-20
Wilkes Barre
| MER C1-04 |
| Fire/Smoke Door FD |
1-23
Wilkes Barre
| MER CLC 1-103 |
| Access Door FD |
Non rated/self closing
01-27a
Wilkes Barre
| Double door 1-108 |
| Fire/Smoke Door FD |
Non latching - binds on other leaf
01-27b
Wilkes Barre
| Double door 1-108 |
| Fire/Smoke Door FD |
Non latching - binds on other leaf
01-30
Wilkes Barre
| Office by canteen N1-96 |
| Fire/Smoke Door FD |
Top gap
01-34a
Wilkes Barre
| Xcor SB by stair 5 |
| Fire/Smoke Door FD |
Multiple door penetrations Non latching
01-34b
Wilkes Barre
| Xcor SB by stair 5 |
| Fire/Smoke Door FD |
Multiple door penetrations Non latching
B-02a
Wilkes Barre
B
| Pump room |
| Fire/Smoke Door FD |
B-02b
Wilkes Barre
B
| Pump room |
| Fire/Smoke Door FD |
B-03a
Wilkes Barre
B
| Xcor into BG-4 fire pump |
| Fire/Smoke Door FD |
B-03b
Wilkes Barre
B
| Xcor into BG-4 fire pump |
| Fire/Smoke Door FD |
B-04a
Wilkes Barre
B
| Xcor FB in hall by EG-31 |
| Fire/Smoke Door FD |
Missing strike
B-04b
Wilkes Barre
B
| Xcor FB in hall by EG-31 |
| Fire/Smoke Door FD |
Missing strike
B-05a
Wilkes Barre
B
| Xcor FB by CG-24 storage |
| Fire/Smoke Door FD |
Non latching Door penetrations
B-05b
Wilkes Barre
B
Xcor FB by CG-24 storage Fire/Smoke Door FD
Non latching Door penetrations
B-07
Wilkes Barre
B
| Oxygen room on loading dock |
| Fire/Smoke Door FD |
B-13a
2/20/24 Wilkes Barre
B
| Double door Dry storage CG- 44 |
| Fire/Smoke Door FD |
B-13b
Wilkes Barre
B
| Double door Dry storage CG- 44 |
| Fire/Smoke Door FD |
B-18a
Wilkes Barre
B
| Double door electrical room CG-9 |
| Fire/Smoke Door FD |
B-18b
Wilkes Barre
B
| Double door electrical room CG-9 |
| Fire/Smoke Door FD |
B-21a
Wilkes Barre
B
| Xcor FB by reception AG-62 |
| Fire/Smoke Door FD |
B-21b
Wilkes Barre
B
| Xcor FB by reception AG-62 |
| Fire/Smoke Door FD |
| 45 |
B-23a
Wilkes Barre
B
| Storage CG-90 |
| Fire/Smoke Door FD |
Undercut Door penetrations Aluminum plates covering holes
| B-23b |
| 2/20/24 |
| Wilkes Barre |
| B |
| Storage CG-90 |
| Fire/Smoke Door FD |
| 90 |
| No latch on leaf |
B-24
Wilkes Barre
B
| In kitchen paper good storage CG-42 |
| Fire/Smoke Door FD |
No closer Clearance issue
B-29b
Wilkes Barre
B
| Bulk storage NG-125 |
| Fire/Smoke Door FD |
Missing screw in hinge
B-30
Wilkes Barre
B
| Inpatient Pharmacy |
| Fire/Smoke Door FD |
Large vertical gap
B-32
Wilkes Barre
B
| Inside stair 4 |
| Fire/Smoke Door FD |
B-35a
Wilkes Barre
B
| Xcor SB by CG-19a |
| Fire/Smoke Door FD |
B-35b
Wilkes Barre
B
| Xcor SB by CG-19a |
| Fire/Smoke Door FD |
B-43a
Wilkes Barre
B
| Xcor FB left of AG-27 |
| Fire/Smoke Door FD |
B-43b
Wilkes Barre
B
| Xcor FB left of AG-27 |
| Fire/Smoke Door FD |
B-44
Wilkes Barre
B
| Behind emergency room check in |
| Fire/Smoke Door FD |
Glass non rated
B-53a
Wilkes Barre
B
| Double door in ED by AG-06a |
| Fire/Smoke Door FD |
B-53b
Wilkes Barre
B
| Double door in ED by AG-06a |
| Fire/Smoke Door FD |
B-65
Wilkes Barre
B
| Soiled linen CG-14 under chute |
| Access Door FD |
No closer
B-33b
Wilkes Barre
B
| Double door MER in ED CG- 29 |
| Fire/Smoke Door FD |
Hazardous/Suite
6h-1a
| 6 |
| Storage C6-15 |
| Haz |
No closure
6h-1b
| 6 |
| Storage C6-15 |
| Haz |
No Closure
6h-2a
| 6 |
| Storage C6-39 |
| Haz |
Vertical gap
6h-2b
| 5 |
| Storage C5-22 |
| Haz |
Undercut
5h-1
| 5 |
| Storage c5-15 |
| Haz |
No door closers
5h-3a
| 5 |
| Storage c5-15 |
| Haz |
No door closers
5h-3b
| 4 |
| Storage c4-40 |
| Haz |
No latching hardware
4h-1
| 4 |
| Suite entrance c4-50 |
| Suite |
Undercut 3/4
4h-3
4h-4
2/21/24 Wilkes Barre
Sterile supply c4-51e
HAZ
Undercut 3/4
4h-6
Wilkes Barre
Suite entrance c4-50a
Suite
4h-11a
Wilkes Barre
Hemodialysis suite entrance 4- 107
Vertical gap Door penetrations
4h-11b
Wilkes Barre
Hemodialysis suite entrance 4- 107
Vertical gap Door penetrations
4h-13a
Wilkes Barre
Suite doors by 4-121
4h-13b
Wilkes Barre
4h-15a
Wilkes Barre
Suite doors by a4-08
Vertical gap Mechanical hold open
4h-15b
Wilkes Barre
Vertical gap Mechanical hold open
4h-21
Wilkes Barre
Storage n4-90
4h-22
Wilkes Barre
Recovery n4-86
No closer Non latching
4h-29
2/22/24 Wilkes Barre
OR storage n4-120
4h-30
Wilkes Barre
Center clean core back hall a4-63
No latching hardware
3h-1
Wilkes Barre
Dry storage a3-47 to main hall
Door no longer present- print wrong
Inv # Inspect Date
Building
FLR
Location
Type of Door
UL Labels Door Rating
Assessment Comments
4h-4
Wilkes Barre
Sterile supply c4-51e
Undercut 3/4
4h-6
Wilkes Barre
Suite entrance c4-50a
4h-11a
Wilkes Barre
Hemodialysis suite entrance 4- 107
Vertical gap Door penetrations
4h-11b
Wilkes Barre
Hemodialysis suite entrance 4- 107
Vertical gap Door penetrations
4h-13a
Wilkes Barre
4h-13b
Wilkes Barre
4h-15a
Wilkes Barre
Vertical gap Mechanical hold open
4h-15b
Wilkes Barre
Vertical gap Mechanical hold open
4h-21
Wilkes Barre
Storage n4-90
4h-22
Wilkes Barre
Recovery n4-86
No closer Non latching
4h-29
Wilkes Barre
OR storage n4-120
4h-30
Wilkes Barre
Center clean core back hall a4-63
No latching hardware
3h-1
Wilkes Barre
Door no longer present- print wrong
3h-2
Wilkes Barre
Missing closer
3h-10
Wilkes Barre
Soiled utility 3c-69
3h-11
Wilkes Barre
Physical therapy CLC 3-114
No latching hardware Hold open closer
3h-13
Wilkes Barre
Storage 3-112
2h-5
Wilkes Barre
Radiology check in n2-85
Double dutch door-no closer
2h-6
Wilkes Barre
File room to office n2-94
2h-7
Wilkes Barre
Storage room 205 by hot lab
No closer
2h-12
Wilkes Barre
Recreational CLC therapy 2- 114 by storage
Hold open closer
1h-1a
Wilkes Barre
Storage n1-95 outside canteen
No closer on either leaf
1h-1b
Wilkes Barre
Storage n1-95 outside canteen
No closer on either leaf
1h-2
Wilkes Barre
Electrical storage n1-92
GH-3a
Wilkes Barre
G
Double door EMS storage
GH-3b
Wilkes Barre
G
Double door EMS storage
GH-4
Wilkes Barre
G Consult 2 by pharmacy NG- 129b
No closer