This document is an amendment to a previous combined solicitation for water system testing and maintenance services for the Pittsburgh VA Medical Center. The solicitation, numbered 36C24424Q0946, is a Request for Quote (RFQ) for a five-year, firm-fixed-price Indefinite Delivery - Indefinite Quantity (IDIQ) contract. The required services include quarterly testing of dental clinic water lines, with specific protocols for sample collection and analysis. The solicitation is a Service-Disabled Veteran Owned Small Business (SDVOSB) set-aside, with a response due date of September 4, 2024, at 10:00 AM Eastern Time. The North American Industrial Classification System (NAICS) code is 541380, and the Product/Service Code is F103. The contracting office is the Department of Veterans Affairs Network Contracting Office 4 in Wilkes-Barre, PA.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
Water System Testing and Maintenance | Dental Clinic Water Testing | Pittsburgh (VA-25-00003650)

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
18711
SOLICITATION NUMBER*
36C24424Q0946
RESPONSE DATE/TIME/ZONE
09-04-2024 10:00 AM EASTERN TIME, NEW YORK, USA
ARCHIVE
30 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N

SET-ASIDE

PRODUCT SERVICE CODE*
F103
NAICS CODE*
541380
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office 4 Wilkes-Barre VA Medical Center 1111 East End BLVD Wilkes-Barre PA 18711

POINT OF CONTACT*

Contracting Officer Edward Ferkel edward.ferkel@va.gov

PLACE OF PERFORMANCE

ADDRESS
Pittsburgh VA Medical Center

University Drive C

Pittsburgh PA

POSTAL CODE
15240
COUNTRY
USA

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

See attached document: Question and Answer - 36C24424Q0946 - Version 2.

Question and Answer

1. In the Statement of Work, General Requirements, C states sample to be collected at first “draw” to catch the water that comes out immediately from the outlet, without the use of “flush”. Bacterial sample procedure includes flushing.

Answer: Testing protocol a. Test each line separately. b. Remove all handpieces and any other equipment reprocessed by SPS before drawing samples from the lines. Air-water syringe tips should be removed. The air-water syringe itself, if not changed between patients (e.g., if barrier + disinfection is accomplished by dental personnel), should remain on the line while drawing the sample. c. Quarterly d. Use of a water testing lab certified in environmental specimens is preferred. e. Report results to the Infection Control Committee or the Safety Committee as appropriate for the facility.

Action Levels f. If >200 cfu but 500 cfu line before returning it to service. h. If shocking and retesting again yields >500 cfu i. Line remains out of service. ii. Contact dental equipment manufacturer and waterline treatment manufacturer for recommendations on options, such as repeat shocking or line replacement.

SOW has been updated

2.

Does the HPC analysis need PA state cert? Can we send the quote and certification directly to your email once prepared? Can we have a separate line for sampling fees or should the sampling price be incorporated in the cost of analysis?

Laboratory used for analysis must be EPA or state certified to conduct HPC analysis. Contractor must provide a copy of EPA or state certificate for the laboratory.

I believe the answer is NO either EPA certified or state EPA certified.

All submissions are completed via email at Edward.ferkel@va.gov. They also must be complete according to the instructions listed in the combined synopsis.

Please only include pricing listed in the price schedule. Any other fees are assumed by the vendor.

End of Document