Questions and Answers Solicitation 36C24424Q0601 Critical Water Testing Pittsburgh VAMC.docx

DOCX document 16 KB Posted

Attached to
F103--Water System Testing and Maintenance | Critical Water & Utility Testing Pittsburgh VAMC
Solicitation number
36C24424Q0601
Issued by

About this file

This document is a set of Questions and Answers related to Solicitation 36C24424Q0601 for Critical Water Testing at the Pittsburgh VAMC. The solicitation is for a 5-year IDIQ contract to provide critical water and utility testing services at the VAMC. Key details include:

The solicitation requires testing for silicates, not silicon, and does not specify the type of silicates. Retesting is at the discretion of the government and will be based on repeat positive bacteria tests. Samples are to be collected from hot and cold water taps as well as from Medivator units, with the Medivator collections representing a single location. The pricing schedule accounts for three monthly critical water sampling locations, fifteen quarterly utility water sampling locations, and eighteen quarterly ionic water sampling locations. The solicitation has a guaranteed minimum of $5,000 and is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). Quotes are due by May 13, 2023 at 1:00 PM Eastern Time.

View the file

Other files

File Type Posted
36C24424Q0601 0001_1.docx DOCX document
36C24424Q0601 0001.pdf PDF
36C24424Q0601_1.docx DOCX document
RM Language for Contracts.docx DOCX document
Section IV Pricing Sheet Attachment 2.xlsx XLSX spreadsheet
WD 2015-4235 PITTSBURGH PA REV 25 12-26-2023.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers Solicitation 36C24424Q0601 Critical Water Testing Pittsburgh VAMC

1. Could you tell me what the number of tests (108) for Line item 0004 (Retesting) is for?

Answer: Retesting is at the discretion of the designated program official and will be based on repeat positives for bacteria.

2. It is my understanding that the silica compound (SiO2) is the normal state in which Silicon exists at standard temperatures and pressures. Due to this, we assume that all Silicon present in a sample exists as silica, (SiO2), and thus we are able to calculate its volume within a sample. The compound this solicitation is requesting, Silicate or SiO4, is not the natural form of Silicon, so we cannot make the same assumptions and we are thus not able to calculate its volume within a sample. That is however, unless the sample matrix (aka the type of water) is known to hold Silicon only as Silicate (SiO4) compounds.

Since some samples will be pulled from Medivator's, I thought it may be possible that the above is true about this water. In other words, I thought it may be correct to assume that all Silicon held by this water is in fact in the form of Silicate (SiO4). If that is a true statement, we can calculate a volume for this parameter. If it is not, would it be acceptable to report results as either pure Silicon, or as Silica (SiO2)?

Answer: The required testing is for “silicates” not silicon. We have not done nor are we requiring the type of silicates be specified, just the amount of silicates present in the samples.

3. There are several lines in the charts provided describing sampling locations that have two collection points, one for Hot and one for Cold water. Also, for every sampling location involving a Medivator, it is followed by two numbers, Medivator #22 and #23 for example. Are we to interpret this as Medivator #22 and Medivator #23, both of which we are to collect samples from? These samples are not accounted for in the quantities stated in the price sheet. All the price sheet accounts for are three monthly sampling locations for critical water, fifteen quarterly sampling locations for utility water, and eighteen quarterly sampling locations for ionic water testing.

Answer: The collection at the point of use, in this case that would be the sinks require hot and cold collection. Each Medicator has 2 bays, each back has a number such as #22 or #23. We only required to have one collection from the medivator. We list the numbers on the results so we are clear which location the testing was collected from.