This document outlines the requirements for engineering services to replace chilled water lines at the Department of Veterans Affairs Medical Center in Lebanon, Pennsylvania. Interested firms must submit Standard Form 330 by April 14, 2023 for consideration. The contract is set aside for a Service-Disabled Veteran-Owned Small Business and has an estimated value of $7 million. The selected firm will provide design, investigation, and construction period services over 344 days to replace HVAC chilled water lines in multiple buildings on the medical center campus. The firm must have experience with projects of similar size and scope involving mechanical systems. Submissions will be evaluated on factors such as qualifications, experience, past performance, and capacity to complete the work on schedule. The project involves assessing the condition of existing chilled water piping and components, developing design documents, and providing construction administration.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUBJECT*
NRM| 595-23-2-5535-0001 | 595-21-101 Replace Chilled Water Lines Phase 1 AE Contract
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 15215 |
| SOLICITATION NUMBER* |
| 36C24423R0011 |
| RESPONSE DATE/TIME/ZONE |
| 04-14-2023 13:00 EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 60 DAYS AFTER THE RESPONSE DATE |
| SET-ASIDE |
| SDVOSBC |
| PRODUCT SERVICE CODE* |
| C1DA |
| NAICS CODE* |
| 541330 |
| PLACE OF PERFORMANCE |
| 1700 Lincoln Ave |
Lebanon, PA 17042
POSTAL CODE
COUNTRY
CONTACT INFORMATION
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office 4
POINT OF CONTACT*
Contract Specialist Elijah McIntosh elijah.mcintosh@va.gov 412-822-3764
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
| AGENCY CONTACT’S EMAIL ADDRESS |
| elijah.mcintosh@va.gov |
EMAIL DESCRIPTION
DESCRIPTION
This announcement is for the selection of an Engineering Services (ES) Firm for Replacing HVAC Chilled Water Lines Phase 1 services for the Department of Veterans Affairs, Lebanon VA Medical Center located in Lebanon, PA.
VAMC Lebanon 1700 S Lincoln Ave Lebanon, PA, 17042
The Government intends to award a single Firm Fixed Price Contract. All potential offerors must provide a SF 330 containing all required information listed below. The form format must be the General Services Administration SF 330 found on the website http://www.gsa.gov/portal/forms/download/116486 Forms Library.
CONTRACT INFORMATION: The project consists of project that replacing HVAC Chilled Water Lines Phase 1. The contract award will incorporate the attached Statement of Work. Expected design services may require any combination of the following: Title I – Site Investigation Services, Title I - Design Services, and Title II – Construction Period Services.
This contract is being procured in accordance with the Brooks Act as implemented in Federal Acquisition Regulation (FAR) Subpart 36.6, Veterans Administration Acquisition Regulation (VAAR) 836.6 and the Veterans Administration Acquisition Manual (VAAM) Part M836 . The firm will be selected for presentations based on demonstrated competence and qualifications for required work. This contract is set-aside 100% for Service Disabled Veteran Owned Small Business’s (SDVOSB) capable of completing work under the North American Industrial Classification System (NAICS) code 541330. The small business standard is $22.5 million dollars.
The AE Firm cannot also be awarded the construction contract resulting from the AE effort Period of Performance is 344 days
SUBMISSION REQUIREMENTS: Interested firms having the capabilities to perform this work must submit an electronic copy of Standard Form 330 (SF 330). Standard Forms 330’s must be received no later than 1:00 PM on April 14st , 2023. The submittal packages are to be sent to the following:
Email submission of the SF 330 are to be submitted to Elijah McIntosh at Elijah.mcintosh@va.gov
Additionally, the submissions must include an insert detailing the following information placed at the front of the Submission.
1. SAM Unique Identity Number
1. Tax ID Number
1. The E-mail address of the Primary Point of Contact.
1. A printed copy of the firms VetBiz Registry.
1. A copy of Errors and Omissions Insurance Policy for the SDVOSB Prime.
1. A copy of the firm’s Pennsylvania State Licensure for the SDVOSB Prime or a statement indicating how the provided drawings will be sealed by a PA licensed Engineer.
1. A statement indicating what office the Engineering Services firm will utilize as its primary design office.
Special Note: An Engineering Services Firm failing to provide any of the documentation detailed in the Pre-Solicitation Notice may be determined as Non-Responsive and may not be considered.
Please note this is not a request for proposal. Eligible responses received will be evaluated and the most highly qualified will be compiled on a shortlist of candidates who will be contacted for an interview. For the evaluation, Professional Qualifications to Perform the Services Required, Specialized Experience and Technical Competence, Past Performance, and Experience in Construction Period Services are more important than the other three (3) factors and are of equal weight. The remaining three (3) factors are of equal weight among themselves. The following evaluation criteria shall be used to evaluate firms and determine the most highly qualified firm for possible contract award.
A-E SELECTION BOARD GUIDE CRITERIA
REPLACE CHILLED WATER LINES PHASE I
Project 595-21-101
FOR
LEBANON VA MEDICAL CENTER
1. There are five evaluation factors for each firm: Professional Qualification, Specialized Experience, Past Performance, Capacity to Accomplish Work, and Location. Detailed evaluation guidance is offered for each factor below.
2. The initial evaluation of the packages should determine which firms are the most highly qualified firms. The Selection Board shall produce a list in the order of preference with a narrative explanation supporting the order of preference. Where firms are rated the same adjective, credence will be given to the descending order of importance. The Source Selection Authority will then select no less than two but no more than five firms for interviews, unless a logical break in the rankings occur. For example, if six firms are rated GOOD, the sixth firm will be given an interview. Upon completion of interviews, the Selection Board will then rank the interviewed firms from most highly qualified to least highly qualified. Negotiations will begin with the most highly qualified firm.
3. The Professional Qualification, Specialized Experience and Past Performance factors are significantly more important than the other two factors which are listed in descending order of importance.
4. The determination of a firm's overall rating shall be made in accordance with the following guidance. The lower of a firm's rating in the three key areas (Professional Qualifications, Specialized Experience and Past Performance) establishes the maximum overall rating a firm can receive as shown below.
5. Recency/Relevance: Evaluators will grade the ten projects that the firms submitted in part F of the SF Form 330. If a firm submitted more than ten projects, only the first ten shall be evaluated, the additional projects shall be ignored. Each of the ten projects will be assigned a grade of “relevant” if the project’s professional services completion year (F22) is within the past five years AND the evaluator believes that the project is similar in size and scope to the statement of work for this solicitation. A project that is only partially similar in size and scope AND has been completed in the past eight years may receive a grade of “somewhat relevant”. A project that is not similar in size and score OR has not been completed in the last eight years will be assigned a grade of “not relevant”. Relevancy is a judgement call made by the evaluator. Typical items that influence the relevancy decision include function (exact, similar, not-similar), size/purpose, and new construction vs renovation.
6. Professional Qualifications necessary for satisfactory performance of required services: This is intended to evaluate the personal experience and qualifications of firm members who work in the firm's project office and are scheduled to be assigned to the design team and who are listed in section E.
a. The number of key positions will vary based on the scope of work of the project. Key positions include Project Manager(s), Quality Assurance, and technical staff that are important to the successful outcome of the project. A complex multi-disciplined project may have many key technical staff, including Architects, Civil Engineers, Electrical Engineers, Environmental Engineers, Fire Protection Engineers, Health Care Planners, Interior Designers, Mechanical Engineers, Structural Engineers and Surveyors. A simpler parking lot project may only have Civil Engineers and Surveyors as key technical staff although all assigned personnel are required to be qualified to practice in their field.
b. Of the personnel listed in section E, each board member shall determine which individuals are actually key individuals.
c. For an individual in a key position to count as experienced, they must have experience in relevant projects as documented in Sections E or F/G, and they must have the appropriate professional qualifications for their role.
i. All lead engineers must have a Professional Engineers license (PE) (per Federal Law, they do not need to be licensed in PA, just in one of the 54 states or territories). Best approach is to have at least one PE per discipline
ii. Lead Architect must be a registered architect, this is normally indicated by NCARB, RA or AIA. Associate AIA are not registered and, therefore, do not count.
iii. Interior Designer registration is preferred (NCIDQ)
iv. Surveyors must be licensed (PLS)
v. Other qualifications include (each board member shall determine the requirement for and relevancy of additional credentials)
1. Leadership in Energy and Environmental Design (LED AP or LEED AP BD+C)
2. Project Management Professional (PMP, PgMP)
3. Constructions Specifications Institute (CSI, CCS, CCCA, CDT)
4. Other industry qualifications
d. Determination of what personnel are sub-contractor personnel and what personnel are in branch offices versus the main office shall be made based on Section C and D, and Part II
e. The larger proportion of key personnel who have the required experience/qualifications and work for the Prime Contractor, the higher the grade as shown on the chart below.
7. Specialized Experience and Technical Competence in the type of work required. This factor evaluates the experience of the firm in completing projects relevant to this contract.
a. Firms provided sample projects as part of section F. Each board member determines which projects are relevant, somewhat relevant and not relevant.
b. Extra consideration may be given for experience designing projects for Department of Veterans Affairs Facilities.
c. For a project to count as relevant for this section, the offeror must have completed the project as the prime contractor. Projects completed by the firm as a sub-contractor or projects completed by key personnel while employed by another firm are not relevant for this section.
d. Board members may use their judgement in providing some credit for projects that are only somewhat relevant but must be consistent.
e. The more projects that the firm has completed, the higher the grade as shown below.
8. Past performance on contracts with Government agencies (Particularly Department of Veterans Affairs) and private industry in terms of cost control, quality of work and compliance with performance schedules.
a. Sources of past performance information include CPARS and personal knowledge.
b. The VA is solely responsible for accessing CPARS data.
c. Board members may give as much weight to contractor provided performance data as they feel appropriate. This data, when provided, is in section H.
d. The more favorable the information, the higher the grade as shown below.
9. Capacity to accomplish the work in the required time: this factor evaluates the ability of the A-E firm, given their current projected workload and the availability of their key personnel, to accomplish the project in the required time.
a. Each A/E firm should address their capacity in part H. This is typically expressed as a firm having a percentage of their resources available for additional work.
b. A firm whose part II section 11 shows a large revenue number likely needs a lower percent capacity in order to perform our project then a firm with a small revenue number. Typically, a design firm will bill 70% of the design fee over the first year and then 30% over the next two years.
c. Rating a firm to have unacceptable capacity requires positive knowledge that they are unable to perform or have had substantial difficulty performing in the past.
10. Location in the general geographic area of the project and knowledge of the locality of the project: This factor evaluates the distance from the A-E firms design office from the location of work (Lebanon VA Medical Center). The personnel identified as the design team staff are expected to work in the design office identified for evaluation of this factor.
a. Distance shall be measured from the Lebanon VA Medical Center, Lebanon, PA
b. Sections C, D, E and Part II shall be used to determine what project office the majority of key personnel are operating from.
Presolicitation Notice Presolicitation Notice
| *=Required Field |
| Presolicitation Notice |
Presolicitation Notice
Lebanon VA Medical Center Lebanon, Pennsylvania
ARCHITECT/ENGINEER SCOPE OF WORK
FOR
Replace Chilled Water Lines Phase 1 595-21-101
| Estimated cost of construction $7,000,000 |
| Bid Documents ready by: 344 DAYS AFTER Notice to Proceed |
| Contracting Officer: Elijah McIntosh |
Contracting Officer’s Representative (COR): Brian Pedersen
-- Services --
Provide professional Architect/Engineer (A/E) services to include:
· Conduct site investigations - architectural, structural, mechanical, electrical, plumbing, site surveys, etc.
· Provide a complete set of construction documents, including construction drawings and specifications
· Provide a third-party cost estimate at each design milestone
· Provide a cost estimate of expected construction cost as per the schedule of values at the end of each phase
· Provide construction period services - review of submissions, provide recommendations regarding contractor change proposals, visit site per VA's request and add to drawings as-built conditions from contractor's record drawings and VA correspondence during construction. A/E shall review all construction change orders and provide an independent cost estimate on each change order request. A/E shall respond on site within a two-hour period when requested and shall provide site visits as requested during construction.
· Develop an Infection Control Risk Assessment (ICRA) including a drawing and specification
-- Project Scope --
GENERAL OVERVIEW:
The schematic design phase shall consist of the A/E completing a survey of the campus chilled water system to identify deficiencies in terms of component (piping, valve, gauges, meters, insulation, etc) size, configuration, or condition. For purposes of this contract, the A/E shall survey components from the central chilled water plant all the way to the fan coils/AHUs/other terminal devices in Buildings 1, 17, 18, 19, 22, 23, 24. In Buildings 2, 101, 102 and 104, 106, 136 the survey will run from the central chilled water plant to the building circulation pumps. The piping condition assessment will be conducted via non-invasive methods such as visual inspection in buildings and crawl spaces and ground penetrating radar or other electronic means for underground piping. The A/E shall categorize the findings, in order of importance, explaining the finding and how the importance ranking was determined. The AE shall also provide a rough order of magnitude cost to correct each finding. Additionally, the A/E shall determine a rough order of magnitude cost and system configuration for creating a campus wide chilled water loop allowing for individual buildings or sections of pipe to be isolated from the campus system without disruption to the entire campus. Finally, the A/E shall determine a rough order of magnitude cost for providing chilled water tie in points for each of the 13 buildings listed above. The A/E shall present these results to the government, which will direct the A/E on what findings the A/E shall prepare construction documents for, not exceeding the construction budget.
The A/E shall then prepare a full set of construction documents for a project that accomplishes the correction of the agreed upon findings within the construction budget. As part of their design, the AE shall provide a phasing and mitigation plan that meets the operational needs to the hospital.
SCHEDULE:
Submit review package so they are received on or before the noted day. All days below are calendar days. The issuance of the Notice to Proceed (NTP) shall be the first PDT Meeting. A/E shall be required to attend and take minutes of each Project Design Team (PDT) Meeting. Minutes shall be submitted electronically to the COR and Contracting Officer within three (3) business days of each meeting.
| Initial Project Design Team (PDT) Meeting |
| Day 0 |
| Schematic Submission |
| 63 Days after Initial PDT meeting |
| Government Review |
| 21 Days after receipt |
| Design Development 1 (DD1) – 35% Design |
| 63 Days after Schematic Approval |
| Government Review |
| 21 Days after receipt |
| Design Development 2 (DD2) – 65% Design |
| 42 Days after DD1 Approval |
| Government Review |
| 21 Days after receipt |
| Construction Documents 1 (CD1) – 95% Design |
| 42 Days after DD2 Approval |
| Government Review |
| 14 Days after receipt |
| Construction Documents 2 (CD2) – 100% Design |
| 28 Days after CD1 Approval |
| Government Review |
| 14 Days after receipt |
| Bid Documents |
| 14 Days after CD2 Approval |
| Total |
| 343 Days |
GENERAL REQUIREMENTS:
· Use the latest VA Master Construction Specifications (PG-18-1), supplemented by the Lebanon VAMC specific sections 01 00 00 General Requirements and 01 35 26 Safety Requirements. Where an appropriate specification does not exist, create a specification in the same format and ensure that it is not proprietary to a single manufacturer.
· Perform all services in accordance with the current VA Design and Construction Procedures (PG-18-3)
· Perform all services in accordance with the current VA Building Information Modeling (BIM) Manual and current VA Drawing Deliverable Requirements (PG-18-4): https://www.cfm.va.gov/til/projREq.asp
· Perform all services in accordance with the current VA Equipment Guides and Planning Information (PG-18-5):
· All designs shall be compliant with space criteria referenced in VA space planning criteria (PG-18-9): http://www.cfm.va.gov/til/space.asp
· Perform all work in accordance with current VA Design Manuals in PG-18-10, including Physical Security and Resiliency. If a section of one of the manuals cannot be met, the A/E shall notify the VA immediately, and assist the VA in the waiver process. These design manuals are supplemented by Lebanon VAMC specific design criteria.
· Perform all work in accordance with current VA Barrier Free Design Standard (PG-18-13)
· Perform all work in accordance with current VA Roof Finishes, Door, and Hardware Schedule (PG-18-14)
· Ensure patient privacy criteria are met (e.g. computerized information, patient privacy, Health Insurance Portability and Accountability Act).
· Design and construction work shall be coordinated with other construction projects on-going at the hospital. A list of current projects will be provided upon approval of the 35% submission.
· A/E shall use most current healthcare delivery processes and the VA design criteria as a guide. The direction that fits the situation the best will be used in the design.
· If shutdowns are required during construction, a full shutdown plan shall be included in the design. Shutdown plans shall include the particular energy source to shut off (e.g. breaker, valve, etc.) and what area, outlets, utilities and/or equipment the shutdown affects. The specific name of the energy source to be shut off shall be identified, for example: “panel H1L1, breaker 2” for electric, or “Valve 3-f” for a water source, etc. Drawings and a written narrative shall be provided.
· A Leadership in Energy and Environmental Design (LEED) Silver Rating is desired with the construction. A rating will not be sought, but practices will reflect LEED Silver requirements. Proof of possible LEED credits shall be provided. The VA shall conduct an Energy Review upon receipt of the 65% submittal (DD2).
· Bid Alternates/Deducts shall be designed into the project to decrease the price of the project 20%.
· A/E shall be responsible for providing certified industrial hygiene services to perform asbestos survey investigations, sampling, development of specifications and drawings, and construction period services. Any place where a sample is taken shall be restored to original condition.
· A/E shall pay particular attention to Occupational Safety and Health Administration (OSHA), National Fire Protection Association (NFPA), International Building Code (IBC), and Environmental Protection Agency (EPA) requirements. Upon receipt of the 65% (DD2) and 95% (CD1) submittals, the VA shall conduct a third-party life safety review. The A/E shall be responsible for making any necessary changes for code compliance and assisting the VA in the waiver process if required.
· A/E shall be responsible for providing all services necessary for design of this project, e.g. structural, industrial hygiene, mechanical, electrical, etc.
SITE INVESTIGATION REQUIREMENTS:
Make site visits as required to determine existing as-built conditions affecting this project. Note: Information including drawings and other documentation provided to the A/E shall be used as reference only. A/E shall field verify every aspect that relates to the project, including all dimensions, wall layouts, capacities, etc. A/E shall coordinate visits with the Contracting Officer’s Representative (COR) as assigned after award. The A/E shall arrange for and oversee the performance of such investigations as required for the proper design of the project.
SUBMISSION REQUIREMENTS:
· Deliver all design packages in person directly or by traceable carrier to the COR on the established dates to allow the VA Project Design Teams to meet as scheduled. A transmittal letter is required to go to the Contracting Officer on the same day as delivery.
· Electronic Narratives shall be provided in portable document format (.pdf)
· Electronic Specifications shall be provided in both portable document format (.pdf) and Microsoft word (.docx) format compatible with the VA’s system.
· Electronic Drawings shall be provided in document format (.pdf), AutoCAD format (.dwg) and REVIT format compatible with the VA’s system.
· Schematic Submission
· All items required in Attachment B Design Submission Requirements
· At least three (3) proposed layouts (facility project) or solutions (utility project) as outlined at the initial PDT meeting. More layouts shall be required if the provided layouts do not meet the needs of the medical center. The A/E shall be required to present the advantages, disadvantages and costs of each layout to the Medical Center director for approval
· One (1) physical copy and an electronic copy of the narrative report describing the layouts/solutions with their advantages, disadvantages and costs
· One (1) physical copy and an electronic copy of the narratives required in Attachment B
· Two (2) physical copies, 30” x 42” size, and an electronic copy of the drawings of each proposed layout/solution including all information required in Attachment B
· Design Development 1 Submission (35%)
· All items required in Attachment B Design Submission Requirements
· The A/E shall be required to present the layout, renderings and sample boards to the Medical Center director for approval
· One (1) physical copy and an electronic copy of all non-drawing items required in Attachment B
· Two (2) physical copies, 30” x 42” size, and an electronic copy of the drawings including all information required in Attachment B. One hard copy shall be broken up into Civil/Site, Structural, Architectural, Hazardous Material, Equipment, Life Safety and Fire Protection, Plumbing and Heating, Air Conditioning, and Electrical sections.
· Identification of potential bid deducts
· Annotated responses to all comments provided by the VA during the review of the schematic submission
· Provide the period of performance for the construction of the design
· Design Development 2 Submission (65%)
· All items required in Attachment B Design Submission Requirements
· The A/E shall be required to present the layout, renderings and sample boards to the Medical Center director for approval
· One (1) physical copy and an electronic copy of all non-drawing items required in Attachment B
· Two (2) physical copies, 30” x 42” size, and an electronic copy of the drawings of including all information required in Attachment B. One hard copy shall be broken up into Civil/Site, Structural, Architectural, Hazardous Material, Equipment, Life Safety and Fire Protection, Plumbing and Heating, Air Conditioning, and Electrical sections
· Identification of potential bid deducts
· Annotated responses to all comments provided by the VA during the review of the Design Development 1 submission
· Construction Documents 1 Submission (95%)
· All items required in Attachment B Design Submission Requirements
· One (1) physical copy and an electronic copy of all non-drawing items required in Attachment B
· Two (2) physical copies, 30” x 42” size, and an electronic copy of the drawings including all information required in Attachment B. One hard copy shall be broken up into Civil/Site, Structural, Architectural, Hazardous Material, Equipment, Life Safety and Fire Protection, Plumbing and Heating, Air Conditioning, and Electrical sections
· Identification of potential bid deducts
· Annotated responses to all comments provided by the VA during the review of the Design Development 2 submission, including the life safety review and energy review
· Construction Documents 2 Submission (100%)
· All items required in Attachment B Design Submission Requirements
· One (1) physical copy and an electronic copy of all non-drawing items required in Attachment B
· Two (2) physical copies, 30” x 42” size, and an electronic copy of the drawings including all information required in Attachment B
· Identification of potential bid deducts
· Annotated responses to all comments provided by the VA during the review of the Construction Documents 1 submission, including the life safety review
· Bid Documents
· One (1) physical copy and an electronic copy of all non-specifications/drawing items that changed during the CD2 review
· One (1) physical copy and an electronic copy of the specifications with stamps/seals
· Two (2) physical copies, 30” x 42” size, and an electronic copy of the drawings with stamps/seals
· Annotated responses to all comments provided by the VA during the review of the Construction Documents 2 submission
· Provide the period of performance for the construction of the design
CONSTRUCTION PERIOD SERVICES REQUIREMENTS:
· Assist the VA with a price reasonableness determination of bid prices
· Review all submissions and provide recommendations to the VA within fifteen calendar days
· Review and provide replies to contractor generated Requests for Information (RFI) within 5 workdays
· Review contractor’s change order request and provide an independent cost estimate for each change order request.
· Make 36 site visits, including those necessary for acceptance inspections, at the request of the VA and prepare written reports to include agreed upon changes in design as determined necessary during the construction. Visits made based on errors and omissions in design will be at no cost to the VA.
· Within 30 days after receipt of red-line drawings that the contractor kept during construction, prepare as-built drawings with A/E’s stamp. Transpose contractor’s as-builts to the current version of AutoCAD and provide a set of updated as-builts, specifications and BIM model.
Attachment A:
Project Areas
Attachment B: Design Submission Requirements
1. GENERAL, SURVEY, GEOTECHNICAL, CIVIL AND LANDSCAPE: Submit the following:
| General, Survey, Geotech, Civil, Landscape |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative
· Site Feasibility Analysis
· Circulation Study
· Phasing Analysis
· Parking Analysis
· Subsurface Investigation Report
· Boring Logs
Drawings
· General Information
· List of sheets and symbols
· Code summary
· Orientation Maps
· Layout Plan showing location of
· Buildings and Structures
· Roads
· Fire Access
· Parking
· Accessible Spaces
· Van Spaces
· Mechanical and Electrical Equipment on Grade
· Future Expansion
· Off-site Roads
· Off-site Utilities
· Service Areas
· Entrances and Exits
· Walks
· Inlets
· Contractor’s Staging Area
· Temporary fencing
· Soil borings
· Vertical and Horizontal Road Alignment
· Paving Joint Patterns
· Grading Plan Showing:
· Existing Contours
· Proposed Contours
· Spot Elevations at Structure Corners, Entrances, Equipment Pads, etc
· First Floor Elevations
· Rim and Invert Elevations on Storm Drainage Fixtures
· Erosion and Sedimentation Control
· Rock Excavation (Quantity)
· Demolition Plan
· Planting Plan Showing
· Landscape Drawings with Plant Groupings
· List of Plant Material
· Site Details
· Landscape Details
· Signage Plan and Schedule
· Phasing Plan
· Infection Control Plan
2. HAZARDOUS MATERIALS: Submit the following:
| Hazardous Materials |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative
· Summary results of building records
· Summary results of station personnel interview
· Determination of materials known to contain asbestos, lead, PCBs, Ozone Depleting Substances or other toxins
· Visual inspection of work area to determine location and condition of hazardous materials
· Sample strategy
· Table of quantities and types of materials to be abated
Drawings
· Major Decontamination Areas
· Limits of sealing off the location
· Locations, types, and quantities of hazardous materials to be removed
· Locations and quantities of hazardous materials to remain
· Arrangements for auxiliary rooms
· Engineering of negative air systems
· Path of hazardous materials to loading areas
· Location and connection to required utilities
· Personal decontamination area
· Minor Decontamination Areas
· Local, types and length of items to be abated by glove and bag approach
· Other abatement features
· Restoration of impacted areas
· Abatement phasing
3. STRUCTURAL: Submit the following:
| Structural: |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative
· Three alternative structural systems for typical bays
· Supporting calculations
· Cost estimates for each system
· Recommend preferred system
Drawings
· Inspection Requirements
· Structural plans
· Sections
· Details
· Existing Columns
· New Columns
· Beams
· Lateral load resisting elements
· Shear load resisting elements
· Load bearing walls
· Slabs
· Foundations
· Elevations
· Schedules
· General notes
· Estimated quantity of rock
· Spray on fireproofing
· Phasing
4. ARCHITECTURAL, INTERIOR DESIGN, EQUIPMENT: Submit or show the following:
| Architectural, Interior Design, Equipment: |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative
· Schematic Options
· Circulation Study
· Phasing Analysis
· Written interior design concept
Floor Plans/Drawings
· Rooms (w/Names & Numbers)
· Doors
· Corridor(s)
· Basic column grid/sizes
· Electrical closets
· Equipment rooms
· IT closets
· Mechanical shafts and space
· Stair(s)
· Ramp(s)
· Elevator(s)
· Penthouse
· Program net/designed net SF
· Size and shape of all departmental functions and services
· Exterior dimensions/total building gross area
· Exterior building elevations
· Expansion and seismic joints
· Roof plan
· Pipe basement
· Pipe tunnel
· Reflected ceiling
· Demolition plans
· Exterior finishes
· Finish floor elevations
· Wall thickness and ratings
· Plumbing fixtures
· Wall sections
· Building sections
· Finish grades at corners, entrances, exits, platforms and ramps
· Lead-lined and radio-frequency-shielded partitions
· Psychiatric areas
· Fire extinguisher cabinets
· Construction details
· Drafting symbols, abbreviations, and general notes
· Door, window, and louver schedules
· Perspectives of key spaces
· Interior details, elevations, sections and perspectives
· Wayfinding and Signage
· Interior finishes Plan
· Wall protection and handrails
· Flooring
· Finish Schedule
· Major Equipment
· All Equipment from PG-18-5
· Equipment elevations and details
· Equipment schedule
· Phasing
Color renderings (interior and exterior)
Sample Boards for interior and exterior materials, products, and finishes
Activation Equipment List (Excel format)
5. FIRE PROTECTION: Submit the following:
| Fire Protection: |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative:
· Fire and smoke separation
· Fire sprinkler/standpipe system
· Size of fire pumps
· Water supply available/max. demand
· Water flow testing results
· Fire alarm systems
· Calculations
· Estimated capacities for proposed air handling units in cubic meters (cubic feet) per minute
Drawings:
· Kitchen extinguishing systems
· Size of air handling unit
· Exit paths from each zone
· Distances to stairs
· Occupancy of each area
· Exit calculations for each floor
· Smoke control features
· Life Safety Summary
· Sprinkler zones
· Fire alarm zones
· Smoke zones
· Building water supply
· Interior sprinkler supply lines
· Standpipes
· Fire extinguisher cabinets
· Fireproofing of structural members
· Sprinkler/standpipe riser supply piping
· Termination of sprinkler main and inspector test drains
· Sprinkler alarm valves
· Waterflow and tamper switches
· Sprinkler system fire department connections
· Sprinkler design hazards per
NFPA 13
· Occupied areas not protected by automatic sprinklers
· Fire alarm system
· Annunciator panels
· Pull stations
· Flow switches
· Audio-visual devices
· Smoke detectors
· Duct smoke detectors
· Smoke dampers
· Fire dampers
· Fire alarm risers
· Exit signs
· Emergency lighting
· Fire sprinklers
· Standpipes
· Fire hydrants
· Fire pumps
· Post indicator valves
· Sectional valves
· Electromagnetic door hold- open devices
· Wall sections indicating fire resistive ratings
· Staff sleeping rooms
· Excavation plan signage
· Door and window schedule with fire rating or fire rated glazing
· Zoning of each fire alarm initiating device
· Details:
· Fire pump system (capacity and pressure)
· Elevation and isometric view of fire pump
· Stairwell sign
· Annunciator panel
· Interconnection of fire alarm system with:
· Smoke dampers
· Air handlers
· Elevator controls
· Kitchen fire extinguishing and fire pump system
· HVAC system with smoke duct detectors
· Single line riser diagram for fire alarm system
· Height/configuration of storage racks and shelving
6. PLUMBING: Submit the following:
| Plumbing |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative
· Demolition plans
· Existing plumbing systems to be used and necessary modifications
· New plumbing systems
· New or modified water treatment
· Calculations (equipment & piping)
· Existing systems: water, sewer, storm, & gas with sources, disposal methods, pressures, condition, etc.
· New sanitary systems
Floor Plans/Drawings
· Demolition Plan
· Room Names
· Identify
· Existing and new plumbing fixtures w/VA numbering system
· Existing and new equipment
· Existing and new medical gas outlets
· Existing and new laboratory/ process gas outlets
· Existing and new sanitary connections and drains
· Plumbing piping
· Size of Pipe
· Equipment schedule
· Fire & smoke partitions
· Riser diagrams
· Legend, notes, and details
· Invert Elevations
· Location/Size
· Pumps
· Storage Facilities
· Treatment Equipment
· Fire Hydrants
· Sectional and post indicator valves
· Backflow preventer
· sprinkler riser, standpipes, system connection and fire pumps
· Profiles of sanitary & storm sewers
· Location of emergency eyewash and shower equipment
· Phasing
7. HVAC: Submit the following:
| HVAC |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative
· Description of HVAC systems
· Equipment for each functional space
· Life cycle cost analysis
· Block layout of equipment
· Selection of HVAC Equipment
· Engineering calculations
· Selection of HVAC equipment
· Catalog cuts of equipment
· Room by room heating and cooling loads
· Zone by zone heating & cooling loads
· Building block heating & cooling loads
· Tabulation of steam consumption
· Psychometric chart for air handling unit
· Fan motor heat gains
· Consumption of humidification loads
· Sound/acoustic analysis
· Total heating and cooling loads
· Domestic hot water load
· Humidification load
· Equipment steam demand
· Zoning of systems
· Capacity
· Quantity and type of equipment
HVAC Drawings
· Main supply, return and exhaust ductwork
· Volume dampers
· Fire and smoke partitions
· Smoke detectors
· Automatic control dampers
· Air Quantities for each room
· Air inlets/outlets
· Rises and drops in ductwork
· Expansion loops
· Anchors
· Vanes
· Drip Assemblies
· Balance Fittings
· Equipment Rooms
· Vertical shafts
· Louvers:
· Outside air
· Exhaust air
· Relief air
· Air changes per hour in each room
· Room-by-room air balance charts
· Coil entering and leaving conditions
· Interconnection of HVAC equipment with fire protection equipment (see fire protection)
· Plan/Section of mechanical rooms
· Schematic flow and riser diagrams
· HVAC demolition
· Phasing plan
· Equipment Schedule
· Seismic bracing
· VA symbols and abbreviations
· Section of
· Pumps
· Fans
· Expansion tanks
· Steam to hot water convertor
· Heat exchangers
· Complete data section
· Outside chilled water and condenser water distribution
· Automatic temperature control drawings
8. ELECTRICAL: Submit the following:
| Electrical |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative
· Design
· Life cycle cost analysis
· Method of short-circuit calculations
· Method of voltage drop and demand calculations
· Utility company correspondence
· Utility company requirements
· Load calculations for normal & emergency use
· Calculations for emergency generator(s)
Drawings Showing:
· Electric closets
· IT closets
· Signal closets
· Major Electrical equipment
· Electrical plot plan of existing and proposed underground power (including manholes)
· Signal inter-building systems
· Proposed electrical system
· Lighting fixture schedule
· Emergency Life Safety Equipment (see fire protection)
· Electrical distribution equipment
· Symbols, note, abbreviations
· Lighting layouts
· Power layouts
· Signal layouts
· Specialty area layouts
· IT Layout
· Demolition plans
· Riser diagrams/On-Line diagrams
· Panel Schedules
· Engine-generator sets
· Substation/pad mounted transformer
· Location of smoke dampers and duct smoke detectors
· Phasing scheme
· Electrical details
9. AUTOMATIC TRANSPORT: Submit the following:
| Automatic Transport: |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative:
· Narrative w/ recommended improvements for exiting system
· Traffic study including existing and proposed ATS w/ alternate methods of distribution
· Rail loadings
· Hydraulic elevator piston pit loads
Drawings:
· Automatic Transport Systems
· Elevators
· Dumbwaiters
· Other ATS systems
· Changes to existing systems (arch. dwgs.)
· Hoistway (arch. dwg.)
· Machine room vents (arch. dwg.)
· Type of ventilation (mech. dwg.)
· Electrical requirements (elect. dwg.)
· Hoistway enclosures
· Pits
· Pit ladders
· Machine area ladder and railings
· Entrances
· Machine rooms
· Elevator cars
· Entrances
· Counterweights
· Trap doors
· Location of hoistway vents
· Location of steel hoisting beams
· Size of machine beams
· Size of end reactions
· Location/detail of machine beam pockets
· Hoistway entrances for elevators
· Carlifts
· Dumbwaiters
· Elevator machine room equipment layout
· Interface with automatic recall and shutdown (see fire protection)
10. SPACE PLANNING
| SPACE PLANNING: |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Narrative:
Space-Accounting Summary Table
11. ESTIMATING: Submit the following:
| Estimating: |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Cost estimate in compliance with Manual for Preparation of Estimates (separate estimates for new construction and alteration work)
12. SPECIFICATIONS
| Specification: |
| Schematic |
| 35% DD1 |
| 65% DD2 |
| 95% CD1 |
| 100% CD2 |
Specifications:
· Table of Contents
· Marked up Specifications
· Complete Specifications
· Submittal Register
End of Document