Amendment 0001 The purpose of this amendment is to answer a question from a quoter. The closing date and time of the solicitation remain unchanged.
This question came up:
The solicitation is asking for a per unit price, but there is no total number of units to be quoted. Do you know if this is available, or what the quote should be based on?
This is the response:
There are approximately 739 outlets these are the individual oxygen vacuum and air outlets. This for full medical gas system including master alarms area alarms Zone valves and patient terminals. Medical air sample testing and Oxygen sample testing. All testing to NFPA 99 2018 code.
Thank you, Cheryl