Erie VA Medical Center Erie, PA 16504
Design Scope of Work Emergency Replacement of IT HVAC Heat Exchangers 01/11/18 Project No. 562-18-401
TABLE OF CONTENTS
| SECTION | TITLE | ||
| 1.0 | SCOPE OF WORK | ||
| 2.0 | GENERAL | ||
| 3.0 | PROPOSED 50% DESIGN AND DESIGN DEVELOPMENT SCHEDULE | ||
| 4.0 | 50% DESIGN AND DESIGN DEVELOPMENT SUBMISSION | ||
| 5.0 | PROPOSED CONSTRUCTION DOCUMENT SCHEDULE | ||
| 6.0 | CONSTRUCTION DOCUMENT SUBMISSIONS | ||
| 7.0 | CONSTRUCTION PERIOD SERVICES | ||
| 8.0 | SECURITY TRAINING |
1.0 SCOPE OF WORK
A. The Engineering Service (ES) firm shall develop all Phasing Plans, Construction Documents, Construction Administration Services, Technical Specifications, and Cost Estimates, for the “Emergency Replacement of IT HVAC Heat Exchangers” project at VAMC, Erie, PA.
B. This project will improve cooling efficiency of medical center equipment by:
1. Replace the existing dry cooler with a new cooler to serve the loop that services OIT equipment and several office spaces in the basement. New cooler shall be sized to future capacity growth and shall be chosen with a consideration to efficiency and life cycle costs. Cooler shall be Johnson Control compatible or Backnet compatible with control functionality. New cooler shall be raised to a sufficient elevation to aid in circulation of air and ease of maintenance.
2. Replace existing pumps and expansion tank that serves the dry cooler loop with new pumps and expansion tank. New pumps and tank shall be chosen with a consideration to future capacity growth, efficiency and life cycle costs. ES shall price this as alternate option 1, with choosing of option dependent upon dry cooler price and budget.
3. Replace near piping associated with old equipment with new piping sized to the new equipment. New piping to include 3 way valves to accommodate temporary equipment.
4. Replace damaged concrete and adjust slope of concrete pad with new concrete with a slope that improves drainage.
5. Installed equipment manufacturers shall have technicians available to provide local technical training.
C. ES shall investigate and perform analysis necessary to select an appropriate cooler and other options to improve the efficiency and/or capacity of cooling of the loop. This may include, but is not limited to the
1. load calculations
2. investigation of the existing dry cooler loop and the equipment served and its load capacity
3. evaluating current Liebert units
4. evaluating current Mammoth units
5. reviewing valves for current units
6. analysis between dry coolers and adiabatic coolers
7. analysis of applicable statutory or code requirements regarding Legionella
8. life cycle analysis including energy costs/efficiency and maintenance costs
9. assessments of pipes to including sizing
10. investigating the feasibility of a secondary loop for OIT equipment
11. investigating the feasibility of pipe replacement of the loop
12. placing 3 way valves on the loop to allow for temporary equipment
13. VFDs on pumps
14. variable water flow
15. use of 2 way valves
16. possible energy savings from additional CRAC units
17. ensuring JCI-Backnet integration of new equipment with existing system with sufficient status, monitoring and manipulation points ES shall provide and document life cycle cost analysis for the proposed cooler design(s). The life cycle analysis for each proposed design shall calculate and present the following results: the annual energy usage and costs, annual costs of system maintenance, and first costs of construction. Options with different service lives shall be compared. The ES shall provide a report describing the preliminary life cycle cost results for each design option no later than the design development phase of design and a final report prior to the final system selected by the VA.
D. ES shall prepare as-builts of the loop system to include FCUs, AHUs, and other loads on the loop and shall include it in the initial submission.
E. Project shall include equipment planning and site preparation, necessary improvements to the physical structure and also addressing documented deficiencies in the area. Salient design features for the design include the following considerations:
1. Site Work – ES shall include construction plan including documentation of site restrictions as necessary to complete this work.
2. The project to provide all necessary modifications to VAMC existing building structure, mechanical, electrical, and piping work.
3. VAMC Erie will require Alt. Bid Deduct options for the project. Comprehensive price breakdowns of phases and tasks are required to ensure budget constrains are met.
F. All work shall be in accordance with NEC, EPA, and VAMC regulations.
G. ES shall include in the specification that the VA will require a manufacturer trained representative be on site to check initial settings, initial start-up and provide training for VA personnel.
H. ES shall be responsible to review and evaluate existing conditions surrounding the area planned for development. This shall include all existing utilities and structures.
I. Integrated Design – Use a collaborative, integrated planning and design process that initiates and maintains an integrated project team in all stages of a project planning and delivery. Establish performance goals for siting, energy, water, materials, and indoor environmental quality along with other comprehensive design goals and ensures incorporation of these goals throughout the design and lifecycle of the system.
J. ES shall develop a phasing plan and also develop deduct bid alternates for project award which will be based upon available funding of $500,000.
K. All work shall be coordinated with the upcoming and current projects to prevent any duplication of efforts. New design shall be accomplished in accordance with latest VAMC guidelines, codes and specifications.
L. All designs shall comply with applicable sections of VA publications, "Planning Criteria for Medical Facilities", H-08-9; and "Equipment Guide List", H-08-5; also NFPA, OSHA, ANSI, JCAHO, VA Standards and other applicable Federal, State and Local code requirements, including BC. ES will be responsible for complete functional design and provide biddable documents meeting all the requirements.
M. Applicable chapters of VA Master Construction Specifications will be prepared by the ES, including any necessary adaptations. VA Construction Standards JH-08-3,VA HVAC Design Manual, VA Sustainable Design and Energy Reduction Manual, and, ASHRAE Standards 90.1-2007, shall apply to specific design requirements. Particular attention is called to CD4, "Symbol Identification of Contract Drawings", and CD5, "Contract Drawings Requirements". Equipment symbols shall be in accordance with Handbook H-08-6, "Standard Drawing Details". Handbook H-08-4 shall be utilized to the greatest extent practicable.
N. The ES shall carefully review all requirements of the latest edition of the Accreditation Manual for Hospitals, of the Joint Commission Accreditation of Hospitals, with respect to design and operating requirements and report all conflicting conditions in writing.
O. Project Schedule is 45 days to complete Schematic Design, Design Development, Construction Documents, Technical Specifications, and Cost Estimates of Construction. Completion of Construction Administration Services will be dependent upon award of Construction Contract.
| 2.0 | GENERAL |
| A. | The ES shall develop design criteria for the project using an Owner’s Project Requirements (OPR) document. The OPR will be a written matrix of design features, assumptions and key performance requirements based on information collected by the A/E from the VA through project meetings, correspondence and interviews of VA for the proposed design. The OPR shall indicate appropriate orientation by the VAMC offices of Engineering Service and VISN Contracting. The ES shall prepare all necessary drawings including, but not limited to post construction as-built drawings. The degree of completion and the stages of submission shall be as hereinafter specified. The VAMC will provide all standard details, master specifications, design criteria, etc. All provided materials shall be adapted to the specific requirements and conditions of the project. |
| B. | ES discussion with the VA Medical Center personnel concerning requirements will be arranged by and participated in by appropriate Engineering and Contracting Service personnel. The ES shall participate, when required, with the appropriate Project Chief and Project Engineering and other Services in review of project scope, design review comments, etc. An OPR document will be used as a clearing house for all collected design information and criteria. The OPR shall be submitted to the VA for review and approval at each phase of design. |
| C. | The floor plans for the structural, HVAC, plumbing and electrical drawing shall be at the same scale as the architectural drawings to facilitate checking. |
| D. | In each submission, the ES shall re-submit the material specified in the prior submission, revised according to the comments made by the VAMC at the prior review. The ES shall document and provide written response to all design review comments received from the VA. The ES shall attend and chair three (3) design review meetings and record minutes for each meeting and distribute electronically. |
| E. | The ES shall pay particular attention to the fact that during the construction document stage, plans are not subject to change at the request of the VA Medical Center staff without the approval of the Chief, Engineering Service, 138, and Contracting Officer, Acquisition and Materiel Management Service, 90C. |
| F. | Drawings showing architectural and other features of the affected building are available in files of the Engineering Service, VA Medical Center. The drawings are not to be expected to be accurate in all respects, and the Architect-Engineer is to verify all features affecting the project by field investigation. |
| G. | The ES shall design all systems to maximize energy conservation and comply with requirements of VA HVAC Design Manual, VA Sustainable Design and Energy Reduction Manual, and ASHRAE Standards 90.1-2007. |
| H. | The ES shall develop the project utilizing Building Information Modeling "BIM" and Computer Aided Design “CAD” software. Submittal drawings shall be full size plots suitable for half size reproduction. CAD Arch. files are available of the existing building. The ES shall update all existing drawings and background drawings based on field observations. The AE shall provide complete orthographic drawings of all submitted drawings in an AutoCAD format approved by the Erie VAMC. The ES shall provide copies of all electronic drawings in PDF and DWG file format. The ES shall provide a secure method of downloading all submitted electronic drawings via a secure FTP site or other approved method. |
| I. | ES shall utilize BIM software to develop architectural design drawings, renderings, construction documents, and record drawings at completion of construction. At each scheduled submittal date the ES shall submit to the VA, A list of the submitted files that shall include, The Model, 3D Views, Facility Data, and CAD Data Files. |
| J. | BIM Model minimum requirements shall be developed to include the systems described below as they would be built and the processes of installing them, and to reflect final as-built conditions. The deliverable model at the interim design stage and at the final design stage shall be developed to include as many of the systems described below as are necessary and appropriate at that design stage. |
1. At a minimum the Model shall include but not be limited to the following; Architectural/Interior Design, Square Footage/Volume including Room Names and Numbers, Architectural Schedules, Walls and Curtainwall Sizes, Shapes, and Material Data. Doors, Windows, Louvers, Roof, Floors, Ceilings, Vertical Circulation, Architectural Specialties and Woodwork, Signage, Schedules, Furniture, Equipment, Structural, Foundations, Shafts and Pits, Mechanical, HVAC, Plumbing, Electrical/Telecommunications, Power and Lighting, Exterior Building Information, Fire Protection/Alarms, and Civil Engineering Data.
| K. | The VA has ownership of the rights at the date of Closeout Submittal to all CAD files, BIM Model, and Facility Data developed for the Project. The VA may make use of this data following any deliverables. |
| L. | For preparation of project specifications the VAMC will provide master specifications available at the VA website (http:/www.va.ww.va.gov./facmgt)in "Word" format. The ES shall supply copies of the specification files to be electronically transported to the CO for incorporation into the VA specification booklet. |
1. X- Project Title Sheet
2. 1 (numbered only)- Architectural Drawings
3. DE- Architectural Miscellaneous Detail
4. S- Structural Drawings (if required)
5. P- Plumbing Drawings
6. E- Electrical Drawings
7. H- HVAC Drawings P. Prints - Black line on white background, "D" Size (24" x 36") (Full size) – Half size 18”x24” Q. Reproducibles - May be mylar photocopies, "D" Size (24" x 36") R. Electronic Media – CD-ROM. – Revit Architecture 2011, AutoCAD 2012 (dwg files).
S. Drawing Data Information - Shall list all basic information including but limited to the following: File names, fonts, layer names/types color, blocks used, hatches, etc.
T. All submitted construction drawings shall minimally conform to the content requirements defined in the VA standards for construction. Specifically the content features of PG-18-15 Minimum requirements for ES submissions. See http://www.cfm.va.gov/contract/aeDesSubReq.asp.
U. The ES shall provide and designate a single point of contact (POC) to represent the ES’s design team throughout the design and construction administration. The POC shall coordinate all communications between the VA and the ES and act as a central path of communication. The designated POC shall communicate directly to the VA through written requests and responses and provide weekly documentation to the VA in the form a design progress/issues log. Upon request, an example of the approved issue log format will be provided. The design progress/issues log shall:
1. Summarize current design progress made during that week
2. Log all sent and received requests for design information as well as other pertinent matters of communication
3. Document all pending matters that will potentially affect the delivery schedule defined in this document
4. Identify upcoming actions that may require advanced preparations (i.e. on-site project meetings, walk though visits, site visits, construction administration visits).
V. The ES shall develop and furnish an owners project requirements (OPR) document that details and logs the development of salient features of the project design. Upon request, an example template of the approved OPR matrix format will be provided. The ES shall collaborate with the VA. The ES shall update the OPR documents with each progressive stage of the design.
| 3.0 | PROPOSED 50% DESIGN AND DESIGN DEVELOPMENT SCHEDULE |
| A. | The 50% design development submission shall be submitted within twenty one (21) days after award of contract. The submission shall include: |
1. Preliminary drawings (prints) (1 copy) ½ size sets and (1 copy) full size set
2. Field Report – follow up from surveys and investigations done including keynoted photos
3. Design Narrative identifying ES findings and recommendations as well as descriptions for all structural, mechanical, electrical, plumbing and telecommunications systems considered. Designs shall use requirements as stated in section 1.0 as basis of design.
4. Design plan describing design solution approach, cost/scope/budget alignment, preliminary scope of work for each design option, preliminary cost estimates for conceptual designs and design options to be considered and any potential disruptions to the site.
5. Preliminary cost estimate utilizing BIM software.
6. Preliminary scope of work
7. Life cycle cost analysis
8. Updated Owner’s Project Requirements
9. Final VA user group approved plans and locations, - Phase in and proposed sequences of construction in each phase. Plans at this stage should include site, exterior elevations for review and comment along with mechanical – electrical.
10. All submitted information shall be made available for secure download to the VA.
| B. | There will be a seven (7) day review of the first submission by VAMC. |
| C. | ES shall note that the above schedule is for guidance only. This schedule may be adjusted to meet the needs of the VA Medical Center for obligation of funds and other consideration. The above proposed design schedule includes government review time. |
4.0 50% DESIGN DEVELOPMENT SUBMISSION
There will be one (1) submission of 50 % design development documents. The requirement for each design submission is described below.
| 4.1 | 50% DESIGN DEVELOPMENT DOCUMENTS |
| A. | Site Planning |
| If project requires the modification of the existing VA campus site the preliminary plans should show how existing area will be modified paving, proposed site enclosure (fencing – screen walls, gates/security requirements, landscaping, exterior lighting, etc.). | |
| B. | Architectural |
| 1. | Submit 1/8" scale design development plans with a single line layout for all floors, penthouses, and roof areas with double line exterior walls. These drawings will show all rooms, doors (shown with a slash), corridors, electrical closets and equipment rooms, signal and telephone closets, mechanical shafts and space, and all vertical circulation, e.g., stairs, conveyors, elevators (personal and service), and automatic conveyances. This includes the fire plans and exit calculations. The 1/16" scale preliminary floor plans should show net program area of each room with the designed net area. Outline and label activities or services as required. |
| 2. | Submit 1/8" scale floor plans for each floor showing all plumbing fixtures, program room codes (from Space Plan), room names, room numbers, door locations and swing, and the net program area over the designed net area (which will not be shown on the working drawings). Outline and label activities and services, as required for the first submission. |
3. Label each room or space with its name and the required net area of the designed net area. Names on drawings shall be the same as those used in the Space Plan. The area figures will appear in fractional form,e.g.,400/390.Spacesprovided but not called for in the Space Plan (such as mechanical rooms) shall be indicated as: -/390. The designed net area shall exclude such circulation space within the room as is permitted by the space planning criteria. Plan shall also note all dimensions to finished wall. Show the overall exterior dimensions for determining the total gross area of the buildings.
4. When the project includes more than one service or activity, as identified in the Space Summary Sheets of the Master Plan or Space Program, each activity shall be labeled and its boundaries indicated with a heavy or distinctive line. In addition to the name, this labeling shall include the Activity Code Number. When a service is fragmented or scattered in various locations, then each piece of it shall be similarly outlined and identified.
5. Submit a separate 1/8" scale plan for each floor to show the building's fire protection features. The plan shall show, as a minimum, smoke barrier partitions, fire partitions, sprinklered areas, location of fire extinguisher cabinets, exit paths to the outside and the occupancy of each fire section. Submit exit calculations for each floor which justify the number of exits provided.
6. Show the structural grid pattern with expansion joints, if used. (indicate existing and new column lines and column numbers ).
7. Show schematic sections, as needed, to define that building concept.
8. Submit elevations at all significant sides of the building in sufficient detail for the VA to judge its appearance. All significant materials, including their colors, must be indicated. This includes rooftop mechanical equipment and any architectural screens.
9. Submit a sample sheet of filled out finished Interior Finish schedule forms. The Medical Center will provide Interior Design input, review, and approval.
10. Submit a title sheet with drawing index and department index (Revise as necessary for each review).
| C. | Functional |
| Submit a written explanation to justify any substantial variations from the Space Plans or Criteria. | |
| D. | Space Control |
Submit a report of the total gross areas for the buildings, per instruction in paragraph CP4, Supplement A to SF 252, Special Provisions. Compare and contrast existing space, proposed Medical Center Space Program, and Space Program required by VACO as designated in 7610.
E. Transport Systems Provide a written description of all existing transport systems. Describe impact of existing systems on new transport systems. Provide recommendations for new transport systems necessary to complete this project.
F. Structural
1. Submit cost estimates for each system. Include foundation and fireproofing costs in estimate. The ES shall assess the economics of each structural system with due consideration of the systems cost effective on the entire building assembly.
2. Show column and shear wall locations.
| G. | Heating, Ventilating and Air Conditioning |
| 1. | Provide block load calculations for HVAC of each building. Describe the building elements (walls, windows, roof, etc.), occupancies and internal loads. Size central equipment (chillers, converters, pumps, etc.). |
| 2. | Describe major functional areas such as administrative, patient bedrooms and ambulatory with distinct and different HVAC requirements that may necessitate individual HVAC treatment. Describe for each of the above functional areas proposed HVAC systems that will be included in the economic analysis. |
| 3. | Provide a written description of the three (3) HVAC and central refrigeration systems to be compared through an economic analysis. Demonstrate the rationale for choosing the candidate systems. Provide documentation of any computerized methodology that will be used for the economic analysis. |
| 4. | Provide a brief description of the parameters that will be used in the economic analysis for each of the HVAC and Central refrigeration systems. Reference the source of all data. |
| 5. | Provide complete feasibility analysis of the existing HVAC and central refrigeration systems including written descriptions of energy conserving concepts. Demonstrate rationale for the proposed concepts. Provide a brief description of the parameters that will be used in the feasibility analysis for each of the candidate energy conserving concepts. Reference the source of all data and provide full documentation of the computerized methodology and full explanation of all coded and abbreviated terms. |
| 6. | Provide a brief description of existing HVAC and Central refrigeration systems that will interact with the proposed new systems. Describe the impact of the existing systems on the new systems and the impact the new systems will have on the existing systems with respect to overall system capacity and ability to handle the new loads, system re-balancing needs, controls interface, etc. |
| 7. | Provide a brief description of the methods to be used in sizing ducts and piping. |
| 8. | Provide plans showing the location of any proposed new chillers, cooling towers and any outside piping distribution for water and steam. |
9. Show on plans the location and size of all mechanical rooms. Provide a block outline of the mail elements (equipment) in each mechanical room.
10. Provide a brief description of the fire and safety aspects of the HVAC systems. Describe the fire and smoke zones and address in principle the fire and safety control systems. Show smoke partitions clearly delineated on the mechanical drawings.
11. For any alterations of existing buildings, determine whether asbestos abatement is required and provide the preliminary finding on the presence of asbestos.
| H. | Electrical | ||
| 1. | Furnish a report describing the systems proposed, including appropriate facts to support the designer's decisions including the basic assumptions and points of interconnections with the existing electrical systems. Submit preliminary square foot load calculations for both normal and emergency. Calculations should be broken down into lighting, receptacles, power (X-ray, elevator, etc.), and mechanical. Provide assessment of the impact of the renovated construction to the existing distribution system. Include current demand loading (H.V. switchgear and primary feeder) and projected load of new construction. | ||
| 2. | Provide a sheet for all symbols. | ||
| 3. | On a plan show any proposed and existing underground electrical circuitry, telephone service, or inter-building signal system (fire alarm, CCTV, radio and security systems), as required. | ||
| 4. | Submit an elementary one-line diagram of the proposed electrical system. Include high voltage and low voltage switchgear, transformers and low voltage main and/or distribution panels, branch panels and representative methods of feeding 277/480 volt, 120/208 volt, and emergency panels. Show size of any electrical device which will be reused. Locate all electrical and signal closets on floor plans. Show preliminary sizes of major components of the electrical one-line and riser diagrams, including high voltage and normal and emergency distribution equipment. Show tentative locations of primary distribution, switchgear/switchboard, engine-generator sets, unit substations/ pad mount transformer, manholes, and other major items. Indicate the electrical equipment (panel boards, transformers, etc.) to be installed in the proposed electrical closets based on the preliminary riser. Show fire alarm risers and locate fire alarm devices. | ||
| 6. | Submit a list of the specialty areas that the designer shall layout for the design development submission, such as: Lab Equipment. | ||
| 7. | Submit a report of the fire alarm items. | ||
| 8. | On typical floor plan indicate location and type of lighting fixtures to be used in each space. Show special features such as under floor raceways, power outlets, exit lights, fire alarms and signal system devices, and panel boards. Show typical circuitry of branch circuits including receptacles, lighting and power for one major representative area. | ||
| 9. | Submit a sample lighting calculation. Describe the proposed method of short-circuit calculation. Describe the method by which voltage drop and demand will be calculated. | ||
| 10. | Electrical drawings shall show fire alarm zones and smoke partitions. | ||
| 11. All drawings shall show room designations. | |||
| 12. | Existing or demolition work shall be shown by dashed lines. | ||
| I. | Plumbing and Sanitary | ||
| 1. | Describe basis for design and submit description of proposed system. | ||
| 2. | Show and identify all plumbing fixtures. Show location of pumps, compressors, tanks, therapeutic pool equipment, and other major central plumbing equipment. | ||
| 3. | Complete plumbing layout for work required in existing buildings including pipe sizes and plumbing fixture identification. | ||
| 4. | Identify smoke partitions, fire alarm zones and fire sprinkler zones on plumbing drawings. | ||
| J. | Cost Estimating | ||
| The ES shall present a cost estimate, utilizing the BIM software, predicated on the assessment made during the conceptual design phase. | |||
| K. | Sustainable Design & Energy Efficiency |
Submit narrative addressing how the design will meet Federal Mandates for sustainability and energy efficiency. Submit ASHRAE 90.1 Compliance Forms for Chapter 5-Envelope, Chapter 6-HVAC, Chapter 7-Water Heating, Chapter 9-Lighting, and Appendix G-Performance Rating and refined ASHRAE 90.1-2007 base-case energy model and as-designed energy model, including all assumptions used, targeting compliance with the 30% energy reduction goal, or exceeding the goal. Submit refined indoor and outdoor water use analysis. Submit lighting calculations including computer-generated point-to-point photometric analysis and narrative for all proposed lighting controls including use of occupancy sensors, daylight harvesting and other energy-conserving strategies as appropriate. Submit preliminary commissioning specifications.
L. Preliminary Construction Phasing
1. Complete phasing and bid alternates information in written form and/or chart form.
2. Complete pictorial representations of construction period laydown areas for each construction phase accompanied by a Gant chart estimates of major construction milestones
| M. | Design Narrative Report |
| 1. A written narrative describing the major design features, expected operations and performance. The report shall be divided according to major systems. Key components shall be described individually. Design options shall be described in terms of impacts to project: cost, operational, maintenance and environmental concerns. ES recommendations shall be included along with rationale. The narrative shall include an executive summary, support standards, and analysis calculations. |
5.0 PROPOSED CONSTRUCTION DOCUMENT SCHEDULE
A. The second submission is to be a 100% Bid Document Submission, and shall be submitted within fourteen (14) days after VA approval and comments of the 50% submission. This submission shall include:
1. Construction drawings prints (2) 1/2size sets (1) Full size set
2. Edited specifications (1 copy)
3. Detailed final cost estimates
4. Detailed scope of work
5. Detailed phasing plan
6. Specifications and drawing files on CD-ROM (If requested)
7. All submitted information shall be made available for secure download to the VA.
D. There will be a seven (7) review of the 100% submission by VAMC. Any additional comments shall be incorporated into final documents. Provide six (6) sets of copies/prints submitted within fourteen (14) days as follows:
1. Final Bid Construction drawings prints (4) 1/2size sets (2) Full size set
2. Final Edited specifications (2 copy)
3. Final detailed cost estimates
4. Final detailed scope of work
5. Final detailed phasing plan
6. Final Specifications and drawing files on CD-ROM
7. All submitted information shall be made available for secure download to the VA.
E. ES shall note that the above schedule is for guidance only. This schedule may be adjusted to meet the needs of the VA Medical Center for obligation of funds and other considerations. The above proposed design schedule is exclusive of government review time.
| 6.0 | CONSTRUCTION DOCUMENTS SUBMISSION |
| A. | There will be a first (100%) of construction documents. The requirements of each submission are described below. |
| 6.1 | MINIMUM REQUIREMENTS FOR FIRST (100%) SUBMISSION OF CONSTRUCTION DOCUMENTS | ||
| A. | General | ||
| 1. | Contract drawings and all related documents shall be completed, fully coordinated, and ready for reproduction for bidding and construction purposes at this review. | ||
| 2. | The ES shall deliver the original working drawings to the Contracting Officer for signature after review and approval of the review material. The working drawings shall bear the seal of the Registered Engineer and the principal CIH on project. This shall be in the form of an electronic drawing files (DWGs and PDFs), hard copy and CD-ROM of the BIM Model. | ||
| 3. | The ES shall make any changes to the working drawings, calculate any specifications identified as necessary during the 95% Submission review conference. | ||
| 4. | When requested, the ES shall deliver three (3) reproduced drawings and specifications to the Contracting Officer. The sets shall be collated, bound and ready to issue for bids. The Contracting Officer will provide the legal portion (front section) of the specification prior to reproduction. The three (3) sets of construction documents are in addition to necessary review submissions. The ES shall also provide one complete electronic set of drawings and specifications. | ||
| 5. | Submit a final cost estimate utilizing the BIM software of construction costs for the project, estimating to further clarify changes or modify previous estimates based on projected construction award date. | ||
| B. | Calculations | ||
| Assemble complete computations and engineering data including basis of design, systems narratives, equipment selections, pipe and duct sizing. Recapitulations, from which the basic heat load calculations served, sound attenuation for high pressure systems and computations and like data for this submission. Provide a separate volume for each discipline with an index and numbered pages, bound with removable metal fastenings. | |||
| C. | Specifications | ||
| 1. | When the drawings and specifications are nearing completion, the ES shall furnish the VA with a brief description of work for inclusion in the Invitation for Bids. | ||
| 2. | Submit original, photocopies of VA Master Specification sections to marked-up suit the project requirements and, also, four (4) copies of any sections originated by the ES. Editing and marked-up of Master Specifications shall easily identify modifications, deletions, and insertions. Specifications shall be typed after the review. | ||
| D. | Architectural | ||
| Submit completed plan, elevations, details and schedules. | |||
| E. | Heating, Ventilation and Air Conditioning (HVAC) | ||
| 1. | The drawings and calculations shall be complete. | ||
| 2. | Duct sizing and pipe sizing computations shall be complete with system layout and tabulated data. | ||
| 3. | Show complete equipment schedules. | ||
| 4. | Show complete control diagrams. | ||
| 5. | Details, elevations, sections and legends on the drawings are to be completed. Show a section of each critical point in corridors indicating the location and space allocation intended for all ducts, piping, and larger conduits regardless of trade. | ||
| F. | Structural | ||
| Include all structural plans, elevations, sections, details, schedules, and general notes necessary to complete the drawings. | |||
| G. | Plumbing and Sanitary | ||
| 1. | Submit complete drawings. | ||
| 2. | All piping shall be drawn and all pipes sized. | ||
| 3. | Submit legend, notes, details, plan views and sized riser diagrams, equipment, etc. | ||
| H. | Electrical | ||
| 1. | Submit complete electrical plans. | ||
| 2. | On drawings, show outlets circuited all motor outlets, complete riser diagrams, switchboards, panels, and feeders. Show panel and switchboard schedules for all equipment with sizes of mains and branches determined. | ||
| 3. | Detail drawings, show symbols, lighting fixture details and construction details. | ||
| 4. | Electrical floor plans shall be complete with panel location and major components located. | ||
| I. | Phasing | ||
| 1. | Complete phasing and bid alternates information in written form and/or chart form. | ||
| 2. | Complete pictorial representations of construction period laydown areas at for each construction phase accompanied by a Gant chart estimates of major construction milestones. | ||
| J. | Estimating | ||
| 1. | Follow the same general instructions as first working drawings submitted. | ||
| 2. | Furnish additional details to the estimator, as design progresses, to show sub-headings under each major numerical heading. | ||
| 3. | Show unit quantity, unit measure, unit cost, and total cost of labor and material for sub-heading. | ||
| 4. | Show a subtotal of labor and material for each sub-heading. | ||
| 5. | Show taxes and insurance on labor. | ||
| 6. | Show sub-total of the total cost. | ||
| 7. | Show applicable sub-contractor's mark-up as a percentage of cost. | ||
| 8. | Show total cost of each sub-heading. | ||
| 9. | Show total estimated cost of each major heading. | ||
| 10. | Show summary of major headings. | ||
| 11. | Provide Data Sheets. | ||
| 12. | See Section F-8 of requirements for first submission of working drawings for site estimate requirements. | ||
| K. | Comments | ||
| 1. | Incorporate all comments shown on the 50% design review. | ||
| L. | Asbestos Abatement | ||
| 1. | Drawings shall be complete and show containment areas, suggest location(s) of decontamination facilities, negative pressure (HEPA) units, building/site access routes, all piping/equipment requiring stripping of asbestos contaminate insulation, rounded-off quantities, etc. | ||
| 2. | Specifications shall be completed. | ||
| 3. | Show phasing as it relates to rest of the project. |
| 7.0 | CONSTRUCTION PERIOD SERVICES | |
| A. | Contract Procurement | |
| 1. | Attend contractor's Pre-Bid site visit and respond with recommendations to any questionable items. If necessary, develop amendments or assist with project procurement. A written response is required. | |
| 2. | Attend one (1) pre-construction meeting, meeting after award of construction contract. | |
| 3. | Attend one (1) commissioning/project schedule coordination meeting after award of construction contract (telephone attendance mandatory, site attendance optional). | |
| B. | Construction Administration and Submittal Review | |
| 1. | The ES firm shall review and respond to all: requests for information (RFI), submittals, change orders (construction materials, and equipment and proposed by the contractor for use in construction of this project), commissioning reports, equipment startup reports, functional test reports, and commissioning issue reports. All RFIs shall be reviewed within five (5) days with critical RFIs reviewed within twenty four (24) hours of submission. All submittals shall be reviewed within ten (10) days with critical submittals within three (3) days; ES shall develop a list of required submissions. All change orders and independent cost estimates shall be reviewed within five (5) days. | |
| 2. | The ES shall support commissioning inquiries related to the designed mechanical, electrical, plumbing, fire protection, lighting, and other building systems included in this project’s scope. Where required by the commissioning authority, the ES shall actively respond to design intent clarification requests that occur while inspecting and testing the systems per applicable ANSI/ASHRAE Standards and the Commissioning Plan developed during design. | |
| 3. | As directed by the VA, the ES shall provide review commentary for functional testing and startup issue troubleshooting. | |
| C. | Site Visits (In addition to site visits listed in Item ‘A’ above) | |
| 1. | The ES shall visit the site at the request of the Contracting Officer to answer technical questions and/or provide clarification to documents due to errors or omissions at no additional cost to the government. Such meetings will not count against required meetings set forth below. | |
| 2. | One Pre-Construction site visit. Attend and assist with site inspections at the 50% and final inspection of percent complete for all project phases. 3 visits total. | |
| 3. | Spot checking of contractors progress (Intermediate Inspections) based on Three- (4) hour site visits when requested by the VAMC contracting officer. These meetings may also be used to answer technical questions and/or develop minor changes due to site conditions, etc. This is in addition to item C.1 and C.2 above. | |
| 4. 50% Completion – One team visit. | ||
| 5. Final inspection of construction – One team visit. | ||
| 6. Post-construction, final commissioning report meeting (telephone attendance mandatory, site attendance optional). | ||
| D. | Commissioning Support |
1. Provide procurement selection criteria and a written scope of work for procurement of a construction phase commissioning authority upon VA request.
2. Participate in commissioning project meetings (i.e. Pre Bid, Pre Construction, Cx kick-off meeting, Acceptance Testing Meetings, Lessons- learned project t close-out meeting). Remote attendance is permissible with CO approval.
3. Coordinate commissioning plan efforts and answer design questions of project commissioning authority.
4. Review and respond to commissioning agent inquiries, comments and recommendations (i.e. project progress meetings, Site Visit Reports, Pre-functional checklists, Functional Test Procedures, TAB reports, Issues Log, Start-up test reports, Operations and Maintenance Manuals, Systems Manual, Final Commissioning Report, Cx Training materials, and seasonal testing reports )
5. Provide systems diagrams and other appropriate data to the Commissioning Agent in electronic format for development of a Systems Manual
6. Provide and report resolution of any issue identified as a Design Issues.
| E. | As Built Drawings | |
| 1. | The ES shall modify design drawings based on marked drawings supplied by the contractor and are to be verified by the ES in field. As-Builts to include all addendums and Bulletins issued by the VA and the ES during construction. The changes shall be incorporated into the final BIM Model with the revision documented on the title block as appropriate. These changes shall be bubbled and dated. The ES is to reformat the drawings based on the VA layering system before final submission. The ES will receive these required layer standards under a separate cover. A reproducible hardcopy and the electronic model of the “As-Builts” are to be submitted to the COR on CD-ROM. Any approved shop drawings with major differences from contract drawings, supplemental agreements processed change orders, etc., shall be incorporated. The ES shall obtain master INDUS drawings and revise/update per VA PG-18-4 VA CAD standards and the VA National CAD Standard Application Guide. |
2. The ES shall deliver completed as-built drawings no later than construction close out.
8.0 PRIVACY TRAINING
A. VA Privacy and Information Security Awareness and Rules of Behavior Course (text version) must be completed by all contractors and subcontractor employees assigned to VA accounts prior to delivery of service and annually thereafter as long as the contract is in place.
B. The contractor shall provide to the VA COR a copy of the completed training certificate(s).
C. Certification and accreditation requirements do not apply, and a Security Accreditation Package is not required. At no time will the vendor be in contact or have access to VA sensitive information. VA sensitive information procedures will be followed per VA Handbook 6500.6.
D. The contractor shall provide to the VA COR a copy of the completed training certificate(s).
- - - END OF SCOPE - - -
EXPECTATION: The generalized privacy training “VA Privacy Training for Personnel Without Access to VA Computer Systems or Direct Access or Use to VA Sensitive Information” must be completed by all contractors and subcontractor employees assigned to VA accounts prior to delivery of service and annually thereafter as long as the contract is in place.
1. The contractor shall provide to the VA COR a copy of the completed training certificate(s).
SOW Emergency Replacement of IT HVAC Heat Exchangers Page 13 of 14 image1.emf
VA Privacy Training No PHI or Access final 4 7 14.doc
VA Privacy Training for Personnel without Access to VA Computer Systems or Direct Access or Use to VA Sensitive Information
The Department of Veterans Affairs, VA must comply with all applicable privacy and confidentiality statutes and regulations. One of the requirements in VA is to have all personnel trained annually on privacy requirements. “Privacy” represents what must be protected by VA in the collection, use, and disclosure of personal information whether the medium is electronic, paper or verbal.
This document satisfies the “basic” privacy training requirement for a contractor, volunteer, or other personnel only if the individual does not use or have access to any VA computer system such as Time and Attendance, PAID, CPRS, VistA Web, VA sensitive information or protected health information (PHI), whether paper or electronic. You will find this training outlines your roles and responsibility for protecting VA sensitive information (medical, financial, or educational) that you may incidentally or accidentally see or overhear.
If you have direct access to protected health information or access to a VA computer system where there is protected health information such as CPRS, VistA Web, you must take “Privacy and HIPAA Focused Training” (TMS 10203). “VA Privacy and Information Security Awareness and Rules of Behavior” (TMS 10176) is always required in order to use or gain access to a VA computer systems or VA sensitive information, whether or not protected health information is included. Both trainings are located within the VA Talent Management System (TMS): https://www.tms.va.gov
What is VA Sensitive Information/Data?
All Department information and/or data on any storage media or in any form or format, which requires protection due to the risk of harm that could result from inadvertent or deliberate disclosure, alteration, or destruction of the information. The term includes not only information that identifies an individual but also other information whose improper use or disclosure could adversely affect the ability of an agency to accomplish its mission, proprietary information, and records about individuals requiring protection under applicable confidentiality provisions.
What is Protected Health Information?
The HIPAA Privacy Rule defines protected health information as Individually Identifiable Health Information transmitted or maintained in any form or medium by a covered entity, such as VHA.
What is an “Incidental” Disclosure?
An incidental disclosure is one where an individual’s information may be disclosed incidentally even though appropriate safeguards are in place. Due to the nature of VA communications and practices, as well as the various environments in which Veterans receive healthcare or other services from VA, the potential exists for a Veteran’s protected health information or VA sensitive information to be disclosed incidentally.
For example:
· You overhear a healthcare provider’s conversation with another provider or patient even when the conversation is taken place appropriately.
· You may see limited Veteran information on sign-in sheets or white boards within a treating area of the facility.
· Hearing a Veteran’s name being called out for an appointment or when the Veteran is being transported/escorted to and from an appointment.
Safeguards You Must Follow To Secure VA Sensitive Information:
· Secure any VA sensitive information found in unsecured public areas (parking lot, trash can, or vacated area) until information can be given to your supervisor or Privacy Officer. You must report such incidents to your Privacy Officer timely.
· Don’t take VA sensitive information off facilities grounds without VA permission unless the VA information is general public information, i.e., brochures/pamphlets.
· Don’t take pictures using a personal camera without the permission from the Medical Center Director.
· Any protected health information overheard or seen in VA should not be discussed or shared with anyone who does not have a need to know the information in the performance of their official job duties, this includes spouses, employers or colleagues.
· Do not share VA access cards, keys, or codes to enter the facility.
· Immediately report lost or stolen Personal Identity Verification (PIV) or Veteran Health Identification Cards (VHIC), any VA keys or keypad lock codes to your supervisor or VA police.
· Do not use a VA computer using another VA employee’s access and password.
· Do not ask another VA employee to access your own protected health information. You must request this information in writing from the Release of Information section at your facility.
What are the Six Privacy Laws and Statutes Governing VA?
1. Freedom of Information Act (FOIA) compels disclosure of reasonably described VA records or a reasonably segregated portion of the records to any person upon written request unless one or more of the nine exemptions apply.
2. Privacy Act of 1974 provides for the confidentiality of personal information about a living individual who is a United States citizen or an alien lawfully admitted to U.S. and whose information is retrieved by the individual’s name or other unique identifier, e.g. Social Security Number.
3. Health Insurance Portability and Accountability Act (HIPAA) provides for the improvement of the efficiency and effectiveness of health care systems by encouraging the development of health information systems through the establishment of standards and requirements for the electronic transmission, privacy, and security of certain health information.
4. 38 U.S.C. 5701 provides for the confidentiality of all VA patient and claimant information, with special protection for their names and home addresses.
5. 38 U.S.C. 7332 provides for the confidentiality of drug abuse, alcoholism and alcohol abuse, infection with the human immunodeficiency virus (HIV) and sickle cell anemia medical records and health information.
6. 38 U.S.C. 5705 provides for the confidentiality of designated medical-quality assurance documents.
What are the Privacy Rules Concerning Use and Disclosure?
You are not authorized to use or disclose protected health information. In general, VHA personnel may only use information for purposes of treatment, payment or healthcare operations when they have a need-to-know in the course of their official job duties. VHA may only disclose protected health information upon written request by the individual who is the subject of the information or as authorized by law.
How is Privacy Enforced?
There are both civil and criminal penalties, including monetary penalties that may be imposed if a privacy violation has taken place. Any willful negligent or intentional violation of an individual’s privacy by VA personnel, contract staff, volunteers, or others may result in such corrective action as deemed appropriate by VA including the potential loss of employment, contract, or volunteer status.
Know your VA/VHA Privacy Officer and Information Security Officer. These are the individuals to whom you can report any potential violation of protected health information or VA sensitive information, or any other concerns regarding privacy of VA sensitive information.
YOU ARE RESPONSIBLE FOR PROTECTING THE CONFIDENTIAL INFORMATION OF OUR VETERANS
Employee (Print Name)
Date
Employee Signature
Print Name of Contract Agency, if contractor
Print Name of VHA Department/Supervisor/Contracting Officer
PROVIDE A COPY OF THIS FORM TO YOUR SUPERVISOR/CONTRACTING OFFICER
FOR DATA ENTRY INTO TALENT MANAGEMENT SYSTEM
File details come from the government source that posted it.