Manual AHU-36 custom Ventrol unit with serial 24439-02 and tag AHU-36.pdf
PDF 943 KB Posted
- Solicitation number
- 36C24225R0003
About this file
This document is a Request for Proposals (RFP) for the repair and replacement of the blower motor and steam coil for Air Handling Unit 36 (AHU-36) at the James J. Peters VA Medical Center in Bronx, New York. The RFP is issued by the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 2.
The key details are: the solicitation number is 36C24225R0003, the product and services required are repair and replacement of the blower motor and steam coil for AHU-36, the response date is TBD, the award date is also TBD, and pricing terms are not specified. There are no set-asides mentioned. The incumbent is not identified. The RFP does not contain a Performance Work Statement or Statement of Objectives, but rather provides technical specifications and requirements for the repair and replacement work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24225R0003_2.docx | DOCX document | |
| Amendment 36C24225R0003 0001.pdf | ||
| RFI SOLICITATION 36C24225R0003.pdf | ||
| SITE VISIT SIGN-IN SHEET - RFP 36C24225R0003.pdf | ||
| S02 BRONX WAGE RATE.pdf | ||
| S02 Solicitation 36C24225R0003 AHU-36 Repairs.pdf | ||
| S02 Limitation on subcontracting blank.docx | DOCX document | |
| 36C24225R0003_1.docx | DOCX document | |
| S02 Buy American Certificate blank.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNIT SERIAL # 24439-02
UNIT TAG # AH-36
Date (mm/dd/yy): 02/12/16 9100, rue du Parcours Anjou(Quebec) H1J 2Z1 Design Assistant 6.2.10
Project Name: VAMC Bronx Hospital Unit Tag: AH-36
Serial #: 24439-002
Static Pressure Summary
Condition 1
Air Pressure Drop Tunnel Description Pressure Drop (in.H20)
AirTunnel 8 ESP 6.00 AirTunnel 1 Mixing Box 0.25 AirTunnel 1 Filter - Pre / Final (Initial Pressure Drop) 0.52 AirTunnel 1 Steam Coil 0.14 AirTunnel 1 Fan Isolation Damper 0.25 AirTunnel 3 Final Filter (Initial Pressure Drop) 0.27 AirTunnel 10 Humidifier 0.01 AirTunnel 5 Chilled Water Coil 0.85 AirTunnel 5 SA Opening - Long Radius Bellmouth (Supply Air) 0.38
Total Pressure: 8.67
Certified Performance Data Sheet
James J. Peters VA Medical Center - Bronx Campus 24439-02 Revision: 6
Unit Details
Unit TAG : AH-36
CFM : 49900
Unit Type : Indoor Thermal Break Construction : Gasketed Thermal Break Construction Unit Exterior : Baked polyester sandstone color coated exterior liner (16Ga. PPG) Unit Floor Type : 2" Upturn lip with caulked seams Auxiliary Floor Drains : None Provided Unit Floor Insulation : See Production Note Unit Floor Liner : 16 Ga. Galvanized steel (Standard) Unit Under Floor Liner : 22 Ga. Galvanized steel (Standard) Perimeter Base Rail Material : Steel rectangular structural tubing Unit Wall And Roof Insulation : 2", Polyurethane injected Foam insulation (Not available on units with perforated sections) Unit Exterior Liner : 16 Ga G-90 galvanized steel (Standard) Interior Liner : See unit drawing.
Fasteners : Mechanical screws with a HEX head provided ETL : Units are ETL listed in accordance to UL standard 1995.
Unit TEST : YES (SEE DETAILS) Shrink Wrap : Included on entire unit
Damper
Damper Louver Model : Tamco 1000 Damper Louver Duty : Return air Jackshaft : Not provided
Damper
Damper Louver Model : Ruskin EAMS060 w/ Airflow station Damper Louver Duty : Minimum Outside Air Jackshaft : Provided when damper is in multiple sections
Damper
Damper Louver Model : Ruskin EAMS060 w/ Airflow station Damper Louver Duty : Outside air Jackshaft : Provided when damper is in multiple sections
Combo-Filter
Filter Duty : O/A Filter Loading : Front loading
March, 29 2016
Version 4.1.15
24439-02 Revision: 6
Pre-Filter Type : 2" FARR 30/30 (merv 8) Pre Filter Total Media Sets : 2 sets supplied by Ventrol & shipped loose (Installed in the field by Others) Pre-Filter Gage Type : Dwyer 2002 Final Filter Type : 12" FARR Durafil ES (SH) (merv 11) Filter Total Media Sets : 2 sets supplied by Ventrol & shipped loose (Installed in the field by Others) Final Filter Gage Type : Dwyer 2003 Filter Frame Type Material : Universal Holding Frame Galvanized steel Filter Qty 24 X 24 : 24 Filter Qty 12 X 24 : 4 Blanking Material : Galvanized
Heating Coil(s)
Coil Casing Material : See coil selection.
Blanking Material : Galvanized Coil Rack : Galvanized Steel Coil Rack
Damper
Damper Louver Model : Ruskin CBD6 TYP4.
Damper Louver Duty : Fan Intake Jackshaft : Not provided
Section Note(s) 1- Ventrol to install 7 inch spacer between backdraft damper and fan
Supply Fan
Fan Qty : 4 Fan Model Number : See fan selection.
Class Construction : See fan selection.
Rotation : 2 X CCW , 2 X CW Fan Discharge Arrangement : N/A Fan Arrangement Type : 4 Motor manufacturer : Baldor Enclosure/Hp/RPM/Frame/Eff. : See fan selection.
Vac/Ph/Hz : See fan selection.
Belt Guard : N/A Drive Sheaves : N/A Fan Bearings : N/A Fan Isolation : 2" seismic spring isolation, spring attached directly to fan structure Septum Wall : 4" Single Wall Fan Accessory 1 : Aluminum Wheels, See wheel width and diameter on selection Fan Accessory 2 : Motor Accessory: Motor provided by twin city with shaft grounding brush ( Not Aegis Ring ) Fan Accessory 3 : Baldor Motor provided and installed by twin city Fan Accessory 4 : Piezometer ring by twin city
March, 29 2016
24439-02 Revision: 6
Fan Accessory 5 : Airflow monitoring Station : Typ.4 Dwyer Digihelic II in Fan (DRC) Electrical Panel Fan Accessory 6 : Motor removal I-Beam, with trolley and hoist Fan Accessory 7 : Fan Enclosure Screen by twin city
Final-Filter
Filter Duty : O/A Filter Loading : Front loading Filter Type : 12" FARR Durafil ES (SH) (merv 14) Total Media Sets : 2 sets supplied by Ventrol & shipped loose (Installed in the field by Others) Filter Gage Type : Dwyer 2003 Filter Frame Type Material : Universal Holding Frame Galvanized steel Filter Qty 24 X 24 : 24 Filter Qty 12 X 24 : 4 Blanking Material : Galvanized
Humidifier Dispersion Grid
Description : NORTEC Humidifier as per section detail. See selection for perfomance Blanking Material : 304 Stainless steel
Section Note(s) 1- Humidiifer section includes 18 Ga 304 Stainless Steel sloped drain pan with 2":
connection
2- Review entire Humidifier submittal in Appendix
Cooling Coil(s)
Coil Casing Material : See coil selection.
Blanking Material : Stainless Coil Rack : 304 Stainless Steel Coil Rack Drain Pan : IAQ 304 (18 Ga.) Stainless Steel Drain Pan With (18 Ga.) Intermediate Drain Pan Drain Pan Connection : 2" Dia. Stainless Steel Drain Connection
Heating Coil(s)
Coil Casing Material : See coil selection.
Blanking Material : Galvanized Coil Rack : None
Long Radius Bellmouth
Description : Long Radius Bellmouth Blanking Material : N/A
March, 29 2016
24439-02 Revision: 6
Section Note(s) 1- R=6
2- Bellmouth shall not protrude past unit
Production Notes
1- Panels must withstand L/200 deflection rating at 8" Static Pressure , positive and negative.
2- All access doors include, extruded aluminum door frame, 3 axis adjustable S.S. hinges (SS3), Allegis door handles, and dual thermal pane inspection window
3- Floor insulaton: Where there are no drain pans: 3" Polyurethane spray foam insulation with 4½" cross members (Standard)
4- Floor insulaton: Where there are drain pans: Minumimum two inches of Foam beneath lowest point of pan, 6" cross members needed.
5- Unit sections to be rotated on site to fit through 90" tall opening. Sufficient structure and blanking to be provided by Ventrol internal to unit.
6- After testing, Fans and Elec.Panel will ship loose from unit. All elec. conduit&wires must remain in place so that others in the field can terminate all electrical connections.to panel.
7- Fans to be installed such that wheel rotation is as shown and noted on drawing.
Electrical Notes
1- Marine Light Fixtures with 23 Watts Compact Fluorescent are Provided, see drawing for quantity and location
2- Light Switch 15A is Provided, see drawing for quantity and location
3- GFCI 15A is Provided, see drawing for quantity and location
4- All lights are wired to switches. Switches are wired to all GFI'S for Single point power connection at Fan section. Single 120 V service required in the field.
5- Airflow monitoring station is wired to step down transformer within Fan Electrical panel. 4 separate analog outputs are availiable for field BMS.
6- All fan motors are wired to NEMA 1 Electrical Panel. Each Fan is controlled by one VFD.
Single 460 V/3 service required in the field.
7- All plastic tubing connections between Fan AFMS and Piezomter ring will be completed
March, 29 2016
24439-02 Revision: 6
8- Refer to All electrical Diagrams enclosed.
9- Damper Airflow monitoring station is wired to Step-down Transformer in Fan electrical panel
10- After testing, Fans and Elec.Panel will ship loose from unit. All elec. conduit&wires must remain in place so that others in the field can terminate all electrical connections.to panel.
Customer Notes
1- Unit lifting lugs cannot be used to rotate, lift and rig units. A platform must be built by others in the field to lift, rotate and continuously support sections.
Testing Notes
1- Airflow test shall be performed.
2- Factory leakage test shall be performed at 8" w.g. Two leakage tests provided, one positive and one negative. The leakage rate shall not exceed 1% of the unit total CFM.
3- After testing, Fans and Elec.Panel will ship loose from unit. All elec. conduit&wires must remain in place so that others in the field can terminate all electrical connections.to panel.
4- Test Reports will be issued to customer. Customer will not witness test.
5- Refer to testing procedures enclosed.
March, 29 2016
Project Name: VAMC Bronx Hospital Unit Tag: AH-36
Serial #: 24439-002
Date (mm/dd/yy): 03/29/16 9100, rue du Parcours Anjou(Quebec) H1J 2Z1 Design Assistant 6.2.11
Note: The FLA and MCA values shown are estimated, see the electrical schematics for the actual values.
Previous Page:
Page:
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02 Order Number:
Legend2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION. VENTRL-003220
P
OPERATING AT THE SUPPLY VOLTAGE
CIRCUIT CONDUCTOR
CIRCUIT CONDUCTOR
UNGROUNDED DC CONTROL CIRCUITS
RED
BLACK
WHITE OR
YELLOW
WHITE WITH
WHITE WITH
BLUE STRIPE
NATURAL GRAY
BLUE
GROUNDED AC CONTROL CIRCUIT CURRENT-CARRYING
CONDUCTOR THAT REMAINS ENERGIZED WHEN THE MAIN
GROUNDED DC CURRENT-CARRYING CONTROL
GROUNDED AC CURRENT-CARRYING CONTROL
VOLTAGE LESS THAN THE SUPPLY VOLTAGE
UNGROUNDED AC CONTROL CIRCUITS OPERATING AT A
ALL UNGROUNDED CONTROL CIRCUIT CONDUCTORS
CONTROL PANEL WIRE COLOR CODING
YELLOW STRIPE DISCONNECT IS IN THE "OFF" POSITION
WIRE CONTINUATION
SOLENOID VALVE
DISTRIBUTION BLOCK
WITH OVERLOAD
1 %%C MOTOR STARTER
WITH OVERLOAD
3 %%C MOTOR STARTER
O/L T1L1
T1 T2
O/L
T2 T3
L1 L2
L2 L3
DISCONNECT
HP
HP
CIRCUIT BREAKER
TERMINAL IN PANEL
1 POLE
FUSE BLOCK
CIRCUIT BREAKER
CIRCUIT BREAKER
2 POLE
3 POLE
R
24 HOUR PIN TIMER
CONTROL TIMER COIL
CONTROL RELAY COIL
M MOTOR STARTER/CONTACTOR
COIL
CONTACTOR
TRANSFORMER
GROUND
DUPLEX RECEPTACLE
CC
HM
ON RISING LEVEL
ON RISING LEVEL
PRESSURE SWITCH CLOSES
MOTOR CYCLE COUNTER
MOTOR HOUR METER
FLOAT SWITCH OPENS
FLOAT SWITCH CLOSES
ON INCREASING FLOW
FLOW SWITCH CLOSES
ON RISING TEMPERATURE
TEMPERATURE SWITCH CLOSES
ON RISING TEMPERATURE
TEMPERATURE SWITCH OPENS
PRESSURE SWITCH OPENS
NORMALLY OPEN RELAY CONTACT
ON RISING PRESSURE
ON RISING PRESSURE
HR L3 T3
PILOT LIGHT
PUSH-TO-TEST
MOMENTARY
FIELD WIRING
NORMALLY OPEN TIMER CONTACT
NORMALLY CLOSED TIMER CONTACT
NORMALLY OPEN PUSHBUTTON
NORMALLY CLOSED RELAY CONTACT
STOP PUSHBUTTON
MOMENTARY
SELECTOR SWITCH
SELECTOR SWITCH
NORMALLY CLOSED EMERGENCY
NORMALLY CLOSED PUSHBUTTON
(ILLUMINATED ON NON-ILLUMINATED)
(ADDITIONAL CONTACTS MAY BE ADDED)
THREE POSITION H.O.A.
SCHEMATIC LEGEND SYMBOLS
X1
H1 H3 H2
X2
H4
TDR
PILOT LIGHT
UNGROUNDED AC CONTROL CIRCUITS OPERATING AT A
VOLTAGE LESS THAN THE SUPPLY VOLTAGE (CLASS 2)
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02 Order Number:
Power Electrical Schematic2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION. VENTRL-003220
P
CUSTOMER
SUPPLIED
POWER
480 VAC, 60 Hz, Three Phase
FULL LOAD AMPS =
MINIMUM CIRCUIT AMPACITY =
SHORT-CIRCUIT CURRENT RATING =
178A 189A
65kA
ALL VFD CONTROL WIRING
BY OTHERS EXCEPT WHERE INDICATED
ABB550
1 > SCR
2 > AI/1
3 > AGND
4 > +10V REF
5 > AI/2
6 > AGND
7 > AO/1
8 > AO/2
9 > AGND
10 > +24VDC
11 > GND
12 > DCOM
13 > DI/1
14 > DI/2
15 > DI/3
16 > DI/4
17 > DI/5
18 > DI/6
30 HP
44.0A
FAULT
RUNNING
SUPPLY
PRIMARY
PE
GLG1
PB1
(113) (213) (313) (413)
(4001) (4101)
L3-L
L2-L
L1-L
U1
V1
W1
U2
V2
W2
PE
VFD1
ABB550
+1+3 +2
GLG2
122A
MBX1
REPROGRAM VFD LABEL
MB
L1
L2
L3
PB1
L1 T1
L2 T2
L3 T3
FB1
60A
MBX1
PARTS
MB
DS1
(102)
MB
MBX1
LABELS
MB
MBX1
MOUNTING
MB MBX1
CRATE
MB
HOLE3
MB
HOLE2
MB
HOLE1
MB
CONE_INFO1
Supply
CONE_INFO2
Return
L1 T1
L2 T2
L3 T3
225A
DS1
104A
103A
102A
114A
115A
113A
120A
121A
119A
3005A (3005)
3006A / (3006)
3007A (3007)
L1
L2
L3
GND
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02 Order Number:
2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION. VENTRL-003220
P
ALL VFD CONTROL WIRING
BY OTHERS EXCEPT WHERE INDICATED
ABB550
1 > SCR
2 > AI/1
3 > AGND
4 > +10V REF
5 > AI/2
6 > AGND
7 > AO/1
8 > AO/2
9 > AGND
10 > +24VDC
11 > GND
12 > DCOM
13 > DI/1
14 > DI/2
15 > DI/3
16 > DI/4
17 > DI/5
18 > DI/6
FAULT
RUNNING
SUPPLY
PRIMARY
30 HP
44.0A
U1
V1
W1
U2
V2
W2
PE
+1+3 +2
GLG3
222A
MBX1
REPROGRAM VFD LABEL
MB
L1
L2
L3
PB1
L1 T1
L2 T2
L3 T3
VFD2
ABB550
FB2
60A
214A
215A
213A
220A
221A
219A
3008A (3008)
3009A / (3009)
3010A (3010)
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02 Order Number:
2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION. VENTRL-003220
P
ALL VFD CONTROL WIRING
BY OTHERS EXCEPT WHERE INDICATED
ABB550
1 > SCR
2 > AI/1
3 > AGND
4 > +10V REF
5 > AI/2
6 > AGND
7 > AO/1
8 > AO/2
9 > AGND
10 > +24VDC
11 > GND
12 > DCOM
13 > DI/1
14 > DI/2
15 > DI/3
16 > DI/4
17 > DI/5
18 > DI/6
FAULT
RUNNING
SUPPLY
PRIMARY
30 HP
44.0A
U1
V1
W1
U2
V2
W2
PE
+1+3 +2
GLG4
322A
MBX1
REPROGRAM VFD LABEL
MB
L1
L2
L3
PB1
L1 T1
L2 T2
L3 T3
VFD3
ABB550
FB3
60A
314A
315A
313A
320A
321A
319A
3012A (3012)
3013A / (3013)
3014A (3014)
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02 Order Number:
2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION. VENTRL-003220
P
ALL VFD CONTROL WIRING
BY OTHERS EXCEPT WHERE INDICATED
ABB550
1 > SCR
2 > AI/1
3 > AGND
4 > +10V REF
5 > AI/2
6 > AGND
7 > AO/1
8 > AO/2
9 > AGND
10 > +24VDC
11 > GND
12 > DCOM
13 > DI/1
14 > DI/2
15 > DI/3
16 > DI/4
17 > DI/5
18 > DI/6
FAULT
RUNNING
SUPPLY
PRIMARY
30 HP
44.0A
U1
V1
W1
U2
V2
W2
PE
+1+3 +2
GLG5
422A
MBX1
REPROGRAM VFD LABEL
MB
L1
L2
L3
PB1
L1 T1
L2 T2
L3 T3
VFD4
ABB550
FB4
60A
414A
415A
413A
420A
421A
419A
3015A (3015)
3016A / (3016)
3017A (3017)
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02 Order Number:
2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION. VENTRL-003220
P
SUPPLY
GRD1
U1
V1
W1 PE
MTR1
M
GRD2
U1
V1
W1 PE
MTR2
M
GRD3
U1
V1
W1 PE
MTR3
M
GRD4
U1
V1
W1 PE
MTR4
M
3007A /(115)
3006A /(114)
3005A /(113)
3010A /(215)
3009A /(214)
3008A /(213)
3014A /(315)
3013A /(314)
3012A /(313)
3017A /(415)
3016A /(414)
3015A /(413)
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02 Order Number:
2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION. VENTRL-003220
P
120V
480 VAC
DIFF PRESSURE XDCR
RANGE: 0-25"
DIFF PRESSURE XDCR
RANGE: 0-25"
DIFF PRESSURE XDCR
RANGE: 0-25"
DIFF PRESSURE XDCR
RANGE: 0-25"
H2 H3
T1
500VA
X1 X2
H4 H1
4004A
4002A
TB1 GND
PB1
L1
L3
XF 1
7A
F1C
4A
F1B
4A
F1A
4010A 4007A
4007A
TS1
4010A 4010B 1 2
MB
FAN1
EXHAUST
MB
4007ABLK
(4009)
CBL1
(4009)
CBL1
BLK
TB2
TB2
4007A4010A
4007A4010A
4007A4010A
4007A4010A
DPT1
1 2
DPT2
1 2
DPT3
1 2
DPT4
1 2
TB1
TB1
4007A4010A
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02 Order Number:
2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION. VENTRL-003220
P
24V
480 VAC
TO DAMPER AFMS
H2 H3
T2
100VA
X1 X2
H4 H1
4104A
4102A
TB2 GND
PB1
L1
L3
XF 1
7A
F2C
1A
F2B
1A
F2A
4107B 4107A
4107A
TB2
TB2
RoboApe
Next Page:
By: Date:Description:Rev:
AH-36
VENTRL-003220
Tag #:
DWG #:
Drawn by:
Engineer:
Approved by:
Checked By: Page Description:
24439-02
Order Number:
Panel layoutP 2016.03.30
Order Name:
Bronx VAMC
THIS DRAWING, SPECIFICATIONS, AND CONCEPTS CONTAINED HEREIN ARE THE
SOLE PROPERTY OF VENTROL AND MAY NOT BE REPRODUCED OR USED IN ANY
FASHION WITHOUT THE PRIOR WRITTEN PERMISSION OF VENTROL CORPORATION.
DS1
&D#10.C
&D#10.C
EXHAUST
&KU,CIRCLE_135,0&BT,CIRCLE_135,0
&BT,ORION_6.7"-FAN-GRILLE,0
FAN1
&KU,CIRCLE_135,0&BT,CIRCLE_135,0
&D#10.B &D#10.B&D#10.B&D#10.B
FB1
&D#10.B &D#10.B&D#10.B&D#10.B
FB2
&D#10.B &D#10.B&D#10.B&D#10.B
FB3
&D#10.B &D#10.B&D#10.B&D#10.B
FB4
GLG1
&BT,BRUMALL_00TP,180&KU,BRUMALL_00TP,180
&D#10.TRILOB
GLG2
&D#10.TRILOB
GLG3
&D#10.TRILOB
GLG5
&D#8.TRILOB
GRD1
&D#8.TRILOB
GRD2
&D#8.TRILOB
GRD3
&D#8.TRILOB
GRD4
&KU,CIRCLE_2.000,0&BT,CIRCLE_2.000,0
&KU,CIRCLE_12.7,0&BT,CIRCLE_12.7,0&KU,CIRCLE_12.7,0&BT,CIRCLE_12.7,0
T1 &D.25.B&D.25.B
&D.25.B &D.25.B
T2
D
.T R
IL
O B
D
.T R
IL
O B
D
.T R
IL
O B
D
.T R
IL
O B
TB1
00 00 00 00 00
TB2
00 00 00 00
&D#6.B
&D#6.B
TS1
&KU,ABB_ACH550_KEYPAD,0&BT,ABB_ACH550_KEYPAD,0
VFD1
VFD1
&BT,AVK_1/4,0&KU,AVK_1/4,0 &BT,AVK_1/4,0&KU,AVK_1/4,0
&BT,AVK_1/4,0&KU,AVK_1/4,0&BT,AVK_1/4,0&KU,AVK_1/4,0
VFD2
&BT,AVK_1/4,0&KU,AVK_1/4,0 &BT,AVK_1/4,0&KU,AVK_1/4,0
&BT,AVK_1/4,0&KU,AVK_1/4,0&BT,AVK_1/4,0&KU,AVK_1/4,0
&KU,ABB_ACH550_KEYPAD,0&BT,ABB_ACH550_KEYPAD,0
VFD3
VFD3
&BT,AVK_1/4,0&KU,AVK_1/4,0 &BT,AVK_1/4,0&KU,AVK_1/4,0
&BT,AVK_1/4,0&KU,AVK_1/4,0&BT,AVK_1/4,0&KU,AVK_1/4,0
&KU,ABB_ACH550_KEYPAD,0&BT,ABB_ACH550_KEYPAD,0
VFD4
VFD4
&BT,AVK_1/4,0&KU,AVK_1/4,0 &BT,AVK_1/4,0&KU,AVK_1/4,0
&BT,AVK_1/4,0&KU,AVK_1/4,0&BT,AVK_1/4,0&KU,AVK_1/4,0
&D#10.TRILOB &D#10.TRILOB&D#10.TRILOB
6"
&D#10.TRILOB
8"
&D#10.TRILOB
&D#10.TRILOB6"&D#10.TRILOB
&D#10.TRILOB6"&D#10.TRILOB
&RP,8005500_DOOR_LEFT &RP,8005500_DOOR_RIGHT
&RP,8005500_PANEL
&D#10.TRILOB
GLG5
&KU,ABB_ACH550_KEYPAD,0&BT,ABB_ACH550_KEYPAD,0
VFD2
&RP,8105235 &RP,8105235
79" H x 32" W x 20" D NEMA 1
&D#10.B &D#10.B
&D#10.B &D#10.B
DS1
&D#10.B&D#10.B
&D#10.B &D#10.B
OSS403
OSS403
0.
in ch
&D#10.TRILOB &D#10.TRILOB
&D#10.TRILOB &D#10.TRILOB
PB1
DPT1 DPT2
DPT3 DPT4
DS1
&KU,CIRCLE_31.0,0&BT,CIRCLE_31.0,0&BT,ABB DISCONNECT,135
Date (mm/dd/yy): 02/12/16 9100, rue du Parcours Anjou(Quebec) H1J 2Z1 Design Assistant 6.2.10
Project Name: VAMC Bronx Hospital Unit Tag: AH-36
Serial #: 24439-002
Coil Layout Coil Hand Configuration Connection Orientation Connection Material Connection Type
Rack Style
Rack Finish Blankoff Material Blankoff Finish
Right and Left Dual Inline Exterior (Straight) Red Brass
MPT
Slide Rack (individually removable) Steel
None 16Ga G90 Galv None
Construction Quantity Serpentine Fin Height Fin Length Rows Fins per Inch Face Area
Stand Height Tube Detail - Primary Surface
Material O.D. x Wall Spacing Internal Return Bends
Casing Coating
Fin Detail - Secondary Surface Material Thickness
Configuration
0.5
24.000 in
69.000 in
69.00 ft²
15 in
Copper
1.125 x 0.035 in
3.000 in x 1 row Int. Dist. (ISDT) N/A
16Ga G90 Galv None
Aluminum
0.010 in Corrugated, Waffle with Straight Edge
Connections Quantity Type Material Pipe Size Supply Return
1 MPT Red Brass 1.5 1 MPT Red Brass 1.5
9NS - 24 x 69 x 1 - 4 AL
Steam Coil 9 : SC : Box 2
Dual Inline Bank 1, Right Hand, 3 per unit 9NS - 24 x 69 x 1 - 4 AL
Steam Coil 9 : SC : Box 2
Dual Inline Bank 2, Left Hand, 3 per unit Condition 1
Entering Conditions Leaving Conditions Actual Airflow Standard Airflow 49,900 SCFM Sensible Capacity 1,660.3 MBH Elevation 39 ft Face Velocity 723.19 ft/min Entering Air DB 39.0 °F Leaving Air DB 69.7 °F Steam Pressure 15.0 psig Air Pressure Drop 0.14 in.H20 SteamTemperature 249.2 °F Condensation Rate 1,755.4 lb/hr Notes:
Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Notes / Features
1. Manufacturer: Temtrol, LLC, 106 N. Industrial Blvd, Okarche, OK 73762
2. 0.75" top and bottom coil flanges provided on coil casing.
3. Vents and drains provided on supply and return connections, unless otherwise noted.
4. Red Brass coil connections provided.
5. This coil should be mounted with the tubes pitched toward the return end to insure proper condensate removal.
6. Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Date (mm/dd/yy): 05/06/16 9100, rue du Parcours Anjou(Quebec) H1J 2Z1 Design Assistant 6.3.1
Project Name: VAMC Bronx Hospital Unit Tag: AH-36
Serial #: 24439-002
Coil Layout Coil Hand Configuration Connection Orientation Connection Material Connection Type
Rack Style Rack Finish Blankoff Material Blankoff Finish
Right and Left Dual Inline Exterior (Straight) Red Brass
MPT
None N/A 16Ga G90 Galv None
Construction Quantity Serpentine Fin Height Fin Length Rows Fins per Inch Face Area
Stand Height Tube Detail - Primary Surface
Material O.D. x Wall Spacing Internal Return Bends
Casing Coating
Fin Detail - Secondary Surface Material Thickness
Configuration
0.5
30.000 in
69.000 in
28.75 ft²
0 in
Copper
1.125 x 0.035 in
3.000 in x 1 row Int. Dist. (ISDT) N/A
16Ga G90 Galv None
Aluminum
0.010 in Corrugated, Waffle with Straight Edge
Connections Quantity Type Material Pipe Size Supply Return
1 MPT Red Brass 1.5 1 MPT Red Brass 1.5
9NS - 30 x 69 x 1 - 10 AL
Steam Coil 5 : SC5 : Box 5
Dual Inline Bank 1, Right Hand, 1 per unit 9NS - 30 x 69 x 1 - 10 AL
Steam Coil 5 : SC5 : Box 5
Dual Inline Bank 2, Left Hand, 1 per unit Condition 1
Entering Conditions Leaving Conditions Actual Airflow Standard Airflow 28,400 SCFM Sensible Capacity 1,528.6 MBH Elevation Face Velocity 987.83 ft/min Entering Air DB 56.0 °F Leaving Air DB 105.6 °F Steam Pressure 15.0 psig Air Pressure Drop 0.49 in.H20 SteamTemperature 249.2 °F Condensation Rate 1,616.1 lb/hr Notes:
Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Notes / Features
1. Manufacturer: Temtrol, LLC, 106 N. Industrial Blvd, Okarche, OK 73762
2. 0.75" top and bottom coil flanges provided on coil casing.
3. Vents and drains provided on supply and return connections, unless otherwise noted.
4. Red Brass coil connections provided.
5. This coil should be mounted with the tubes pitched toward the return end to insure proper condensate removal.
6. Coil Operating Weight is: 361 lb
7. Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Date (mm/dd/yy): 05/06/16 9100, rue du Parcours Anjou(Quebec) H1J 2Z1 Design Assistant 6.3.1
Project Name: VAMC Bronx Hospital Unit Tag: AH-36
Serial #: 24439-002
Coil Layout Coil Hand Configuration Connection Orientation Connection Material Connection Type
Rack Style
Rack Finish Blankoff Material Blankoff Finish
Right and Left Dual Inline Exterior (Straight) Red Brass
MPT
Slide Rack (individually removable) 304 Stainless Steel
None 16Ga 304 SS None
Construction Quantity Serpentine Fin Height Fin Length Rows Fins per Inch Face Area
Stand Height Tube Detail - Primary Surface
Material O.D. x Wall Spacing Internal Return Bends
Casing Coating
Fin Detail - Secondary Surface Material Thickness
Configuration
0.6666667
36.000 in
69.750 in
69.75 ft²
1 in
Copper
0.625 x 0.020 in
1.500 x 1.299 in Smooth
0.028 in
16Ga 304 SS None
Aluminum
0.008 in Corrugated, Waffle with Straight Edge
Connections Quantity Type Material Pipe Size Supply Return
1 MPT Red Brass 2.0 in 1 MPT Red Brass 2.0 in
5WC - 12 - 36 x 69.75 x 8 - 8 AL
Chilled Water Coil 1 : CC1 : Box 5
Dual Inline Bank 1, Right Hand, 2 per unit 5WC - 12 - 36 x 69.75 x 8 - 8 AL
Chilled Water Coil 1 : CC1 : Box 5
Dual Inline Bank 2, Left Hand, 2 per unit Condition 1
Entering Leaving Actual Airflow Standard Airflow 32,400 SCFM Elevation Entering Air DB 85.5 °F Entering Air WB 69.4 °F Fluid Type Water Fluid Entering Temp 45.0 °F Fluid Flow Rate 182.3 GPM FoulingFactor 0.0000
Total Capacity 1,555.1 MBH Sensible Capacity 1,105.7 MBH Face Velocity 464.52 ft/min Leaving Air DB 54.5 °F Leaving Air WB 54.2 °F APD 0.74 in.H20 Leaving Fluid Temp 62.0 °F Fluid Velocity 3.16 ft/s Fluid Pressure Drop 10.55 ft.H20
Notes / Features
1. Manufacturer: Ventrol, 9100, rue du Parcours, Montreal QC H1J 2Z1 Canada
2. 0.75" top and bottom coil flanges provided on coil casing.
3. Vents and drains provided on supply and return connections, unless otherwise noted.
4. Red Brass coil connections provided.
5. Coil Operating Weight is: 2,726 lb -- Fluid volume of the coil is: 72.1 Gal
6. Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Customer: W/A February 12, 2016 Job Name: BronxVA Page 1 of 3 Job ID: BronxVA
Fan Description Fan Performance Motor Data
Tag . . . . . . . . . . . . . . . . . . . AH-36 Total CFM . . . . . . . . . . . . . 49,900 HP Quantity . . . . . . . . . . . . . . . . . . . . 4 CFM/fan . . . . . . . . . . . . . . . 12,475 RPM # fans per system . . . . . . . . . . . . 4 Operating SP (in.wg) . . . . . . . 8.67 Voltage . . . . . . . . . . . . . 230/460V Type . . . . . . . . . . . . . . . . . . EPQN Standard SP (in.wg) . . . . . . . 8.67 Phase Size . . . . . . . . . . . . . . . . . . . . . 270 RPM . . . . . . . . . . . . . . . . . . . 1977 Hz Width . . . . . . . . . . . . . . . . . . SWSI Tip Speed (fpm) . . . . . . . . 13,975 Enclosure . . . . . . . . . . . . . . TEFC Arrangement . . . . . . . . . . . . . . . . 4 Oper. BHP/fan . . . . . . . . . . . 23.87 Efficiency . . . . . . . . . . . . . Prm.Eff.
Class . . . . . . . . . . . . . . . . . . . . . III Standard BHP/fan . . . . . . . . 23.87 Frame . . . . . . . . . . . . . . . . . . 286T Rotation . . . . . . . . . . . . . . . . . W/A Tot. Oper. BHP . . . . . . . . . . 95.49 Design VFD Op. Freq.(hz) Discharge . . . . . . . . . . . . . . . HOR Tot. Standard BHP . . . . . . . 95.49 Wheel diameter (in.) . . . . . . . . . 27 Outlet area (sq. ft) . . . . . . . . . . N/A Drive method . . . 60 Hz direct drive Outlet Velocity (fpm) . . . . . . . . N/A Percentage width . . . . . . . . . 95% Temperature (°F) Percentage diameter . . . . . . 100% Altitude (ft)
Density (lb/ft³) . . . . . . . . . . . 0.075 Max RPM for Class Static Efficiency . . . . . . . . . . 71.22 Mechanical Efficiency . . . . . 71.22
Modifiers
4 fans operating in system, % width: 95%
Sound
Individual Sound Power Levels in dB re. 10-12 Watts:
Octave Bands 1 2 3 4 5 6 7 8 LwA Level at Inlet 86 88 100 90 83 79 75 72 94 Level at Outlet 93 94 98 96 92 85 80 76 97
Total Package Sound Power Levels in dB re. 10 -12 Watts:
Octave Bands 1 2 3 4 5 6 7 8 LwA Level at Inlet 92 94 106 96 89 85 81 78 100 Level at Outlet 99 100 104 102 98 91 86 82 103
Individual fan estimated sound pressure level in dBA (re: 0.0002 microbar) based on a single* ducted installation:
Distance in ft 1 3 5 dBA at Inlet 94 84 80 dBA at Outlet 97 87 83
*To estimate dBA level for ducted inlet and ducted outlet (into and out of the room) type installation, deduct 20 from the LwA value shown.
Using a directivity factor of 1.
Estimated Sound Pressure based on free field, spherical (Q = 1) radiation at the stated distance.
Ver 9.82X - Report B Job created 12-03-2015
All quotations per Twin City Fan Terms and Conditions found at http://www.twincityfan.com/TC_TCF.pdf
C F M ( i n 1 , 0 0 0 s ) 10 20 30 40 50 60 70 80 90
SP
SYSTEM CURVE
S T
A T
I C
P
R E
S S
U
E i n w g
1.5
3.0
4.5
6.0
7.5
9.0
10.5
12.0
BHP
B R
A K
H O
R S
E P
O W
49,900Total CFM:
8.67 in.wgSP:
1977RPM:
23.87 / fanBHP:
N/AOutlet Velocity:
0.075Density:
Corrected for:
4 fans operating in system % width: 95%
Total Package Sound Power Level
In/OutOctave 92 / 991 94 / 1002 106 / 1043 96 / 1024 89 / 985 85 / 916 81 / 867 78 / 828 in db re 10-¹² watts 02/12/16 Page: 1 of 2
Customer: W/A Job ID: BronxVA Represented By: Ventrol 514-354-7776
Fan Tag: AH-36 Model: 270 EPQN
T W I N C I T Y F A N A N D B L O W E R P E R F O R M A N C E C U R V E
C F M ( i n 1 , 0 0 0 s ) 10 20 30 40 50 60 70
SP
SYSTEM CURVE
S T
A T
I C
P
E
S S
U i n w g
1.5
3.0
4.5
6.0
7.5
9.0
10.5
12.0
BHP
B R
A K
H O
R S
E P
O W
46,000Total CFM:
7.37 in.wgSP:
2036RPM:
25.52 / fanBHP:
N/AOutlet Velocity:
0.075Density:
Corrected for:
3 fans operating in system Aluminum wheel % width: 95%
Total Package Sound Power Level
In/OutOctave 94 / 991 96 / 1002 104 / 1053 98 / 1044 92 / 1015 88 / 946 84 / 887 81 / 858 in db re 10-¹² watts 02/12/16 Page: 1 of 2
Customer: W/A Job ID: BronxVA Represented By: Ventrol 514-354-7776
Fan Tag: ah 36 FOR REF ONLY Model: 270 EPQN
T W I N C I T Y F A N A N D B L O W E R P E R F O R M A N C E C U R V E
File details come from the government source that posted it. Updated .