1. What is the weight capacity of the elevator as no freight elevator is available? 4000lbs

2. Is there an identified laydown area for the GC’s dumpster? No assigned area provided.

3. Is there a identified area for the GC’s QC/Supper/SSHO to work from?

TBD – there are several areas around Building 12 that can be utilized and we can work with EMS to assign.

4. Is there an identified area where the GC can store material?

No storage onsite – daily materials can be stored in the elevator lobby on the floor currently under construction (and excess left overnight) – ensuring no hazards or fire code violations.

5. Has the flooring been tested for asbestos?

Yes – the results were previously provided for review. Several layers of flooring are existing. The top layer (broadloom carpet) only will be demolished, and skim coat/install over existing VCT tiles below.

6. Has the substrate been tested to ensure there are no issues?

Yes – the results were previously provided for review. Several layers of flooring are existing. The top layer (broadloom carpet) only will be demolished, and skim coat/install over existing VCT tiles below.