S02- 561-19-160_Prosthetics Lab_ Final Bid Drawings NEW_Part6.pdf

PDF 3 MB Posted

Attached to
Y1DA--Upgrade prosthetics (VA-22-00010940)
Solicitation number
36C24222B0005
Issued by

About this file

This pre-solicitation notice is for an upcoming solicitation to upgrade the prosthetics lab at the VA New Jersey Healthcare Systems East Orange Campus. The project scope includes demolition of existing interior walls, finishes, mechanical and electrical components as well as installation of new architectural, mechanical, plumbing and electrical systems. Specific tasks involve demolition work in stairwell A-S7 and rooms A-103G, A-E-102 and A-103J. The estimated cost range for the project is $1-2 million. The NAICS code is 236220 and size standard is $39.5 million. The solicitation number is 36C24222B0005 and will be released on or around November 5, 2020 on SAM.gov. Responses are due based on details in the solicitation. The project requires bonding and responses must be hard copies submitted by verified SDVOSBs registered in VIP and SAM.gov. The completion period is 180 calendar days.

View the file

Other files

File Type Posted
36C24222B0005 0001.docx DOCX document
36C24222B0005.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F S

FS

PT

PP

S

S

S

S

S

S

S

S

M P

T Z

M P

T Z

P Q R S

40"

CB

80"

36"

80"

80"

80"

TV

80"

80"40"

PANEL 'LPA2'

PANEL 'LCP2'

PANEL 'EMP AD'

PANEL 'P2A'

PANEL 'DP-A'

PANEL 'DP-B'

E

E

E

E E

E

FACP

E

ON WIREMOLD

CONTROL PANEL

GAS ALARMS

E

100A-3P

CIRCUIT BREAKER

E

E

ORTHOTIC

LAB

A-103D

ORTHOTIC

LAB

A-103E

FITTING AREA

A-103C

RECEPTION

A-103K

STORAGE

A-103F

TOILET

A-103B

WHEEL

CHAIR

REPAIR

A-103A

WASTE

A-103G

MECH.

ROOM

A-103J

CORRIDOR

A-103H

ELEC.

A-E-102

ELEC.

A-E-102D

PED

ORTHOTICS

A-103

STAIR

A-S7

TELEPHONE

OPERATOR

SUITE

A-102D

TOILET

A-102B

CHIEF

PROSTH.

PROS.

A-102E

ASSIST.

CHIEF

A-102B

PROSTH.

SVC.

A-102

PROSTH.

SVC.

A-102E

PROSTH.

SVC.

A-102F

PROSTH.

SVC.

A-102G

MECH.

TELE. EQPM

ROOM

A-101B

OFFICE

TELE.

SWITCH

A-101A

TELE. EQPM

ROOM

A-101C

VEST.

A-101B

MECH.

A-103B

VOLUNTEER

A-105A

HAC

A-159 TOILET

A-103B

P Q R S

ORTHOTIC

LAB

A-103D

ORTHOTIC

LAB

A-103E

FITTING AREA

A-103C

RECEPTION

A-103K

STORAGE

A-103F

TOILET

A-103B

WHEEL

CHAIR

REPAIR

A-103A

WASTE

A-103G

MECH.

ROOM

A-103J

CORRIDOR

A-103H

ELEC.

A-E-102

ELEC.

A-E-102D

PED

ORTHOTICS

A-103

STAIR

A-S7

TELEPHONE

OPERATOR

SUITE

A-102D

TOILET

A-102B

CHIEF

PROSTH.

PROS.

A-102E

ASSIST.

CHIEF

A-102B

PROSTH.

SVC.

A-102

PROSTH.

SVC.

A-102E

PROSTH.

SVC.

A-102F

PROSTH.

SVC.

A-102G

MECH.

TELE. EQPM

ROOM

A-101B

OFFICE

TELE.

SWITCH

A-101A

TELE. EQPM

ROOM

A-101C

VEST.

A-101B

MECH.

A-103B

VOLUNTEER

A-105A

HAC

A-159 TOILET

A-103B

N

PROJECT

NORTH

GENERAL AREA

OF WORK

PP

ELECTRICAL PANEL

FACP=FIRE ALARM CONTROL PANEL

DUPLEX RECEPTACLE

QUADRAPLEX RECEPTACLE

SIMPLEX RECEPTACLE

220V SPECIAL RECEPTACLE

WIFI ACCESS POINT

ANTENNA

FUSED DISCONNECT

MOTOR WITH DISCONNECT

2' X 4' LIGHTING FIXTURE

2' X2' LIGHTING FIXTURE

EXIT SIGN, CEILING MOUNTED

ELECTRICAL POWER POLE

ELECTRICAL POKE THRU

ENCLOSED CIRCUIT BREAKER

SINGLE POLE TOGGLE SWITCH

CELING MOUNTED SPEAKER

SECURITY CAMERA

PUSH BUTTON

DEMOLITION HATCH. REMOVE EQUIPMENT BACK TO SOURCE AND MARK AS 'SPARE'

ELECTRICAL DEMOLITION LEGEND

S

M PTZ

PT

CB

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

C U s e rs

\b z h a n g .A

C E

L A

\O n e

D ri v e

A c e la A rc h it e c ts

E n g in e e rs P

.C \D o c u m e n ts \2

-U

S D

V A

-0 M

E P b z h a n g

Y D

J Q

.r v t

/1

/2

:4

:3

A M

ED101

ELECTRICAL POWER AND

LIGHTING DEMOLITION PLANS

6/18/2021 DJW ACELA

EAST ORANGE VAMC 385 TREMONT AVE, EAST ORANGE, NJ

561-19-160UPGRADE PROSTHETIC LABFINAL BID DOCUMENTS

1/8" = 1'-0"1

POWER PLAN DEMOLITION

1/8" = 1'-0"2

LIGHTING PLAN DEMOLITION

KEY PLAN

1. EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC SHOWN WITHOUT INDICATIONS IN SCOPE SHALL BE DISCONNECTED AND DEMOLISHED. EXISTING CIRCUITRY SHALL BE REMOVED BACK TO SOURCE AND MARK 'SPARE'. ELECTRICAL EQUIPMENT SHOWING 'X' INDICATES EXISTING TO REMAIN. ELECTRICAL EQUIPMENT SHOWING 'RE' INDICATES EXISTING TO BE RELOCATED. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE

SAME IN THE BID SUBMITTAL.

2. ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL

BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.

3. REFER TO ELECTRICAL SYMBOL LEGENDS FOR ALL SYMBOL DESIGNATIONS.

4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING

REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO

ACHIEVE SAME.

5. CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY MANNER.

6. CONTRACTOR SHALL CONFIRM THE EQUIPMENT IN THE EXISTING LAB AREA TO REMAIN OR TO BE DEMOLISHED

PRIOR TO ROUGH-IN.

ELECTRICAL GENERAL DEMOLITION NOTES

ELECTRICAL KEYED PLAN DEMOLITION NOTES

1 PANEL A & B TO BE REMOVED AND REPLACED WITH NEW AT NEW LOCATIONS.

REFER TO POWER PLAN NEW WORK FOR DETAILS.

REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR EQUIPMENT LIST AND DETAILS.

CONTRACTOR SHALL RETURN DEMOLISHED EQUIPMENT BACK TO VA COR FOR FURTHER INSTRUCTIONS.

PANEL 'EMP AD' SHALL BE REMOVED/REINSTALLED BY OTHERS.

EXISTING WALL MOUNTED LIGHTING FIXTURE AND CONDUIT SHALL BE DEMOLISHED. COORDINATE WITH COR TO REMOVE THE CIRCUIT BACK TO SOURCE AND MARK AS 'SPARE' OR RELOCATE THE LIGHTING FIXTURE TO NEW

LOCATION.

Revisions: Date: Page 37 of 43

DLVDLV

DLV

W

W

P H

PHPH

OS

RC

OSRC

OS

P H

LV

OS

RC

OS

PH

OS

OS

LV

P H

D L V

OS

RC

RC

PH

W

OS

OS

OS

OS

RC

L V

L V

W

T R

T R

T R

T R

J

TR

J

T R

J

J

J

T R

T R

T R

TV

T R

J

N

PROJECT

NORTH

GENERAL AREA

OF WORK

P Q R S

PANEL 'LPA2'

PANEL 'LCP2'

PANEL 'P2A'

PANEL 'DP-A'

PANEL 'DP-B'

PANEL 'B'

PANEL 'A'

TELEPHONE BOARD

E

E

E

E

E

E

E

2 (TYP. FOR

ALL EXIT SIGNS)

P2A-9

EM

EM

EM

A-8

A-8 A-8

A-8

A-8

A-8

A-8

A-10 b

NL NL

NL

NL

NL NL

A A A

A A A

A A A

A A A

A A A

A A A

A A A

A A A

A

A A

A A

A A

A A A A

A A A A

A A A A

A A A A

A

A

A A

A A

B

B

B

B

B

B

B

B

B

B

B

B B B

C C

CC

D

D

D a

P2A-9

A-10

G

G

G

G

G

A A

G

P2A-9

G

A A

A A

A A

A A

A A

A A

A A

A

A

A

A

A-10 a a a b b b

A-10

P2A-9 a,b ab ba a,b a a b b a,b

P2A-9 P2A-9

A-10 A-10

A-10

A-10

B B

B

B

F

F

B F

B BF

B BF

B BF

G

P2A-9

NL

NL

NL

NL

NL

C

C

C

A

A

A

A

C C

CC

C C

C C

CC

A

A

A-10

B

NL

E

E

E

G

4 E

TOILET ROOM

A-103

CORRIDOR

A-700A

W/C REPAIR

A-703

EXAM

A-704

CORRIDOR

A-700B

WAITING

A-700

EXAM

A-705

RECEPTION

A-701

SHOE FITTING

A-706

STORAGE

A-707

CORRIDOR

A-700C

ELEC.

A-E-102D

ELECTRICAL

A-E-102

CORRIDOR

A-700D

STORAGE

A-711

TOILET

A-709

STAIR

A-S7

MECH. ROOM

A-103J

MAIN WASTE

A-103G

OFFICE

A-712

OPEN OFFICE

A-700E

OFFICE

A-713

OFFICE

A-714

MECHANICAL ROOM

A-716

LABORATORY

A-715

P Q R S

48"

PANEL 'LPA2'

PANEL 'LCP2'

PANEL 'P2A'

PANEL 'DP-A'

PANEL 'DP-B'

AC

E E

E E

E

E

PANEL 'B'

PANEL 'A'

E

E

TELEPHONE BOARD

LPA2-29

LPA2-29

LPA2-27

LPA2-29

LPA2-29

LPA2-27

LPA2-16

LPA2-31

LPA2-14

LPA2-31

LPA2-33

B-28

LPA2-18 LPA2-18

LPA2-18

LPA2-18

LPA2-18 LPA2-18

P2A-3

P2A-3 P2A-3

FOR SEWING MACHINE

TYPE F

240V/30A/2P

NEMA 1

DISCONNECT

B-13,15

240V/30A/3P

NEMA 1

DISCONNECT

B-20,22,24

DC S2

S2

S1

BS

DP

B-27,29,31

B-8,10,12

240V/30A/3P

NEMA 1

DISCONNECT

240V/30A/3P

NEMA 1

DISCONNECT

B-26

B-26

B-17,19,21

240V/30A/3P

NEMA 1

DISCONNECT

B-14,16,18

B-6

A-18B-26

B-4 B-2

NEW 125A/3P/240V

DEMA 1

FUSED DISCONNECT

FOR HUMIDIFIER

FUSED AT 125A

AC

SC

AC

(TYP. FOR RECEPTACLES

IN WAITING ROOM)

A-18

A-18

P2A-3

AC

P2A-5

P2A-5

LPA2-27

48"

LPA2-16

LPA2-14

LPA2-16

AC

LPA2-29

LPA2-29

LPA2-24

LPA2-24

LPA2-12

LPA2-12

48"

B-30

B-32

B-33

B-33

B-33

AC

LPA2-16

AC AC

48"

SC

LPA2-12

LPA2-31

LPA2-14

LPA2-14

LPA2-14

B-33

B-33

B-33

B-34

B-34

B-34

B-34

B-36

B-33

A-18

A-18

B-35

240V/60A/2P

NEMA 1

DISCONNECT

B-1,3

OV

LPA2-27

P2A-13

TS

TS

P2A-3

LPA2-27

LPA2-31

CLG

CLG

B-26

LPA2-27

LPA2-33

FOR DOOR HOLDER

LPA2-29

P2A-15

TR

TR

LIGHTING FIXTURE SCHEDULE

TYPE

A

B

C

F

MANUFACTURER

COLUMBIA LIGHTING

HUBBELL

MODEL NUMBER

LJT22-35MWG-FSA12-EDU

CWW4-35VW-2WW-EDU

LTR-6SQD-H-ML25L-DM1-LTR-6SQD-T-ML35K8MD-SS

WATTAGE

18W

31W

22.8W

LUMENS

CCT DESCRIPTION

COLUMBIA LIGHTING

6" SQUARE DOWNLIGHT

4' STRIP LIGHTING FIXTURE

2' X 2' TROFFER RECESSED MOUNTED3500K

3500K

3500K

D HUBBELL 4L-P-D-SC254-4-C1-35K 36W 2252 4' PENDANT LIGHTING FIXTURE3500K

G DUAL LITE SESGW 4W EXIT SIGN

CWW2-35VW-2WW-EDUCOLUMBIA LIGHTING 2' STRIP LIGHTING FIXTURE3500K15W 1489

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

C U s e rs

\b z h a n g .A

C E

L A

\O n e

D ri v e

A c e la A rc h it e c ts

E n g in e e rs P

.C \D o c u m e n ts \2

-U

S D

V A

-0 M

E P b z h a n g

Y D

J Q

.r v t

/1

/2

:3

:1

P

M

E101

ELECTRICAL POWER AND

LIGHTING NEW WORK PLANS

6/18/2021 DJW ACELA

EAST ORANGE VAMC 385 TREMONT AVE, EAST ORANGE, NJ

561-19-160UPGRADE PROSTHETIC LABFINAL BID DOCUMENTS

KEY PLAN

REPLACE EXISTING 100A-3P CIRCUIT BREAKER WITH NEW 125A-3P FUSED DISCONNECT FUSED AT 125A. THE EXISTING FEEDERS FROM PANEL 'LCP2' TO THE NEW HUMIDIFIER SHALL BE REPLACED WITH (4)#1 & (1)#6 GRD

IN 2"C.

RECEPTACLES IN WAITING ROOM A-700 AND SHOE FITTING A-702 SHALL BE TAMPER RESISTANT AND

CONTAINS USB PORT FOR CHARGING. (HUBBELL USB15A5I OR EQUIVALENT)

THE FIRE SHUTTER SHALL INTERLOCK WITH FIRE ALARM SYSTEM. WHEN FIRE ALARM SYSTEM IS ACTIVATED, THE FIRE SHUTTER WOULD AUTOMATICALLY OPERATE. REFER TO INSTALLATION MANUAL FOR DETAILS.

(CORNELL COUNTER FIRE DOOR OR EQUIVALENT.)

CONTRACTOR SHALL REROUTE THE CONDUIT RUN WHERE THE NEW DOOR IS BUILT. PROVIDE ENOUGH CONDUCTORS AND CONDUITS FOR EXTENSION OF THE BRANCH CIRCUIT. REFER TO ARCHITECTURAL

DRAWINGS FOR EXACT DOOR LOCATION.

RECEPTACLE MOUNTED ON CEILING FOR PLUG-IN CABLES ON REEL.

REFER TO ELECTROMAGNETIC DOOR HOLDER DETAIL FOR WIRING DIAGRAM.

POWER PLAN KEYED NEW WORK NOTES

1/8" = 1'-0"2

LIGHTING PLAN NEW WORK

CONNECT NEW LIGHTING FIXTURE IN CORRIDOR TO THE EXISTING CORRIDOR LIGHTING CONTROL CIRCUIT ON LIFE SAFETY CIRCUIT VIA NEW ROOM CONTROLLER.THE TOTAL CONNECTED POWER OF THIS BRANCH CIRCUIT SHALL BE LESS THAN 1800VA @120V WITH A 20A-1P CIRCUIT BREAKER. (PANEL

'P2A')

NEW EXIT SIGNS SHALL BE LED GREEN LIGHT AND WALL MOUNTED. REFER TO LIGHTING FIXTURE

SCHEDULE FOR DETAILS.

NEW EXIT SIGNS SHALL BE CONNECTED TO LIFE SAFETY PANEL 'P2A' AHEAD OF SWITCHING.

(1)L-SHAPED RECESSED CHANNEL LED FIXTURE, (1)RECESSED CHANNEL LED FIXTURE ON THE CEILING AND (1)RECESSED CHANNEL LED FIXTURE MOUNTED ON THE WALL SHALL BE PROVIDED. REFER TO

ARCHITECTURAL DRAWING AE201 DETAIL #9. (CORONET LSR1 LED SERIES OR EQUIVALENT.)

LIGHTING FIXTURE MARKED WITH 'NL' AS NIGHT LIGHT SHALL BE CONNECTED TO LIFE SAFETY PANEL

'P2A' AHEAD OF SWITCHING.

LIGHTING PLAN KEYED NEW WORK NOTES

1. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND

MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED

CASEWORK, EQUIPMENT, ETC. VERIFY ALL CHANGES PRIOR TO ROUGH-IN.

2. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, AND CONNECTION REQUIREMENTS (RECEPTACLES, SWITCHES, DISCONNECTS) WITH EQUIPMENT VENDOR

PRIOR TO ROUGH-IN.

3. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V BRANCH CIRCUIT. MULTIWIRE

BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.

4. NEW SPEAKERS IN CORRIDOR SHALL BE CONNECTED TO THE EXISTING PAGING SYSTEM. CONTRACTOR

SHALL VERIFY THE QUANTITIES AND TYPE WITH COR PRIOR TO ROUGH-IN.

5. COMMUNICATION EQUIPMENT SHALL CONNECT TO EXISTING IT ROOM. COORDINATE WITH VA OIT.

6. CONTRACTOR SHALL PROVIDE WIRED SMOKE DETECTORS IN THE CONSTRUCTION AREA DURING

CONSTRUCTION UNTIL NEW SPRINKLER SYSTEM IS FUNCTIONAL. COORDINATE WITH SPRINKLER

CONTRACTOR FOR DETAILS.

7. ALL FIRE ALARM WORK SHALL BE SUPERVISED BY THE FACILITY'S EXISTING FIRE ALARM MAINTENANCE

CONTRACTOR. CONTACT 'KINETIX' @877-223-3000.

POWER PLAN GENERAL NEW WORK NOTES

1/8" = 1'-0"1

POWER PLAN NEW WORK

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATION OF ALL NEW CEILING MOUNTED LIGHTING FIXTURES. CLOSELY COORDINATE LOCATION OF LIGHTING FIXTURES AND SMOKE DETECTORS WITH HVAC DUCTS, DIFFUSERS, SPRINKLERS, PLUMBING, ETC. AND ADJUST LOCATIONS

OF SELECTED ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.

2. REFER TO ELECTRICAL DETAILS PLANS FOR OCCUPANCY SENSOR WIRING DIAGRAMS AND PROGRAM

SCHEDULE FOR ADDITIONAL INFORMATION.

3. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V BRANCH CIRCUIT.

MULTIWIRE BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.

4. NO MORE THAN (3) SINGLE-PHASE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT.

DIFFERENT POWER SYSTEMS (NORMAL, CRITICAL, LIFE SAFETY) SHALL NOT BE INSTALLED IN THE

SAME CONDUIT.

5. REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS.

6. LIGHTING FIXTURE MARK WITH 'NL' SHALL BE CONNECTED TO PANEL 'P2A' AHEAD OF LOCAL

SWITCHING VIA 3/4"C - 2#12 AND 1 #12GRD.

LIGHTING PLAN GENERAL NEW WORK NOTES

Revisions: Date:

T

T N T

NL

M PTZ

P

M P

T Z

NT

N

L

N

PROJECT

NORTH

GENERAL AREA

OF WORK

P Q R S

PANEL 'LPA2'

PANEL 'LCP2'

PANEL 'P2A'

PANEL 'DP-A'

PANEL 'DP-B'

E E

E E

EE

E

TELEPHONE BOARD

E

E

E

E

E

E

E

E

E

E

RF-1

CU-1

AHU

WP

240V/3P/100A

NEMA 3R

DISCONNECT

240V/3P/60A

NEMA 1

DISCONNECT

240V/3P/30A

NEMA 1

DISCONNECT

A-15

(TYP. FOR

ALL VAV BOXES)

A-1,3,5

A-2,4,6

B-7,9,11

E

A-17

E

E

RELOCATED DUCT HEATER

VFD

HUMIDIFIER H-1

(125A FUSED DISC

IN A-E-102)

CONDENSATE PUMP CP-2

(A-22)

E

(TYP. FOR ALL

BASEBOARD HEATERS)

VAV-A-2

VAV-A-1

VAV-A-3

VAV-A-4

VAV-A-5

VAV-A-6

VAV-A-7

VAV-A-8

B-13

MOTOR OPERATED

DAMPERS

(TYP. FOR 4)

EF-3

PANEL 'B'

PANEL 'A'

A-19

NEW 125A-3P/240V

NEMA 1

FUSED DISCONNECT

FOR H-1

FUSED AT 125A

REFER TO POWER

PLAN FOR DETAILS

CONDENSATE PUMP SCP-1

(A-20)

EF-2

A-19

VAV-A-9

TOILET ROOM

A-103

VESTIBULE

A-101B

W/C REPAIR

A-703

EXAM

A-704

CORRIDOR

A-700A

WAITING

A-700

CORRIDOR

A-700B

EXAM

A-705

SHOE FITTING

A-706

RECEPTION

A-701

STORAGE

A-707

CORRIDOR

A-700C

ELEC.

A-E-102D

ELECTRICAL

A-E-102

STAIR

A-S7

MECH. ROOM

A-103J

MAIN WASTE

A-103G

CORRIDOR

A-700D

STORAGE

A-711

TOILET

A-709

OFFICE

A-712

OPEN OFFICE

A-700E

OFFICE

A-713

OFFICE

A-714

MECHANICAL ROOM

A-716

LABORATORY

A-715

MECHANICAL EQUIPMENT SCHEDULE

DESIGNATION

AHU

CU-1

RF-1

VOLTAGE/PHASE

208/3

FLA

18A

OCPD

40A

DESCRIPTION

HUMIDIFIER

EXHAUST FAN

CONDENSING UNIT

AIR HANDLING UNIT

RETURN FAN

H-1

EF-2,3 120/1

208/3

56A208/3

4.1A,0.19A

11A

80A

20A

15A

125A

VARIABLE-AIR-VOLUME BOXVAV-A-1~8 120/1 20A

208/3 93.4A

CONDENSATE PUMPCP-2 120/1 5.8A 20A

CONDENSATE PUMPSCP-1 120/1 7.2A 20A

P Q R S

TOILET ROOM

A-103

CORRIDOR

A-700A

W/C REPAIR

A-703

EXAM

A-704

WAITING

A-700

CORRIDOR

A-700B

EXAM

A-705

SHOE FITTING

A-706

RECEPTION

A-701

STORAGE

A-707

CORRIDOR

A-700C

ELEC.

A-E-102D

ELECTRICAL

A-E-102

STAIR

A-S7

MECH. ROOM

A-103J

MAIN WASTE

A-103G

CORRIDOR

A-700D

STORAGE

A-711

TOILET

A-709

OFFICE

A-712

OPEN OFFICE

A-700E OFFICE

A-713

OFFICE

A-714

LABORATORY

A-715

MECHANICAL ROOM

A-716

VESTIBULE

A-101B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

C U s e rs

\b z h a n g .A

C E

L A

\O n e

D ri v e

A c e la A rc h it e c ts

E n g in e e rs P

.C \D o c u m e n ts \2

-U

S D

V A

-0 M

E P b z h a n g

Y D

J Q

.r v t

/1

/2

:4

:3

A

M

E102

ELECTRICAL EQUIPMENT AND

AUXILIARY NEW WORK PLANS

6/18/2021 DJW ACELA

EAST ORANGE VAMC 385 TREMONT AVE, EAST ORANGE, NJ

561-19-160UPGRADE PROSTHETIC LABFINAL BID DOCUMENTS

KEY PLAN

1/8" = 1'-0"1

EQUIPMENT PLAN NEW WORK

EXISTING BRANCH CIRCUIT FOR THE BASEBOARD HEATER TO REMAIN.

COORDINATE WITH MECHANICAL CONTRACTOR REGARDING THE INSTALLATION OF VAV BOXES. DISCONNECT

SWITCH AND LOW

VOLTAGE TRANSFORMER SHALL BE PROVIDED BY MANUFACTURER OR MECHANICAL CONTRACTOR.

EXISTING BRANCH CIRCUIT FOR THE DUCT HEATER TO REMAIN. CONTRACTOR SHALL PROVIDE ADEQUATE

MATERIALS TO EXTEND

EXISTING BRANCH CIRCUIT INCLUDING CONDUCTORS AND CONDUITS. NEW MATERIALS SHALL MATCH THE

EXISTING.

EQUIPMENT PLAN KEYED NEW WORK NOTES

1. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND

MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED

CASEWORK, EQUIPMENT, ETC. VERIFY ALL CHANGES PRIOR TO ROUGH-IN.

2. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, AND CONNECTION REQUIREMENTS (RECEPTACLES, SWITCHES, DISCONNECTS) WITH EQUIPMENT VENDOR AND

MECHANICAL/PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.

3. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V BRANCH CIRCUIT. MULTIWIRE

BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.

EQUIPMENT GENERAL NEW WORK NOTES

1/8" = 1'-0"2

AUXILIARY PLAN NEW WORK

SECURITY EQUIPMENT SHALL CONNECT TO MONITORING SYSTEM OF VA SECURITY CONTROL CENTER (SCC).

VASS CAMERA SHALL BE INTEGRATED WITH PANIC ALARM. ONCE THE ALARM HAS BEEN ACTIVATED THE

VASS SHALL MONITOR AND RECORD ALL EVENTS ASSOCIATED WITH THE ALARM.

THE EMERGENCY PULL CORD AND INDICATOR SHALL CONNECT TO THE MONITORING SYSTEM OF VA

SECURITY CONTROL CENTER (SCC) AND SEND NOTIFICATION TO THE RECEPTION DESK.

AUXILIARY PLAN KEYED NEW WORK NOTES

1. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND

MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED

CASEWORK, EQUIPMENT, ETC. VERIFY ALL CHANGES PRIOR TO ROUGH-IN.

2. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, AND CONNECTION REQUIREMENTS (CALL STATIONS, PULL CORDS, ETC.) WITH EQUIPMENT VENDOR PRIOR TO

ROUGH-IN.

3. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V BRANCH CIRCUIT. MULTIWIRE

BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.

AUXILIARY PLAN GENERAL NEW WORK NOTES

Revisions: Date: Page 39 of 43

F S

F S

S

S

S

S

S

S

S

S

S

S

FS

DH

P Q R S

1(TYP.)

AC

AC

TOILET ROOM

A-103

CORRIDOR

A-700A

VESTIBULE

A-101B

W/C REPAIR

A-703

EXAM

A-704

CORRIDOR

A-700A

EXAM

A-705

CORRIDOR

A-700B

WAITING

A-700

SHOE FITTING

A-706

RECEPTION

A-701

STORAGE

A-707

CORRIDOR

A-700C

ELEC.

A-E-102D

ELECTRICAL

A-E-102

STAIR

A-S7

STORAGE

A-711

TOILET

A-709

OFFICE

A-712 CORRIDOR

A-700D

MAIN WASTE

A-103G

MECH. ROOM

A-103J

OFFICE

A-713

OPEN OFFICE

A-700E

OFFICE

A-714

MECHANICAL ROOM

A-716

LABORATORY

A-715

P Q R S

FACP

E

2(TYP. FOR CLG SPEAKER)

TS

FD

FD

VESTIBULE

A-101B

TOILET ROOM

A-103

CORRIDOR

A-700A

W/C REPAIR

A-703

EXAM

A-704

EXAM

A-705CORRIDOR

A-700B

WAITING

A-700

RECEPTION

A-701

SHOE FITTING

A-706

STORAGE

A-707

CORRIDOR

A-700C

ELEC.

A-E-102D

ELECTRICAL

A-E-102

STAIR

A-S7

CORRIDOR

A-700D

STORAGE

A-711

TOILET

A-709

OFFICE

A-712

MECH. ROOM

A-103J

MAIN WASTE

A-103G

OFFICE

A-713

OPEN OFFICE

A-700E

OFFICE

A-714

MECHANICAL ROOM

A-716

LABORATORY

A-715

CONTROL

MODULE

TYPICAL

INITIATING

CIRCUIT LOOP

TYPICAL A/V SIGNAL

CIRCUITEOL

E X

IS

T

IN

G

F

IR

E A

L A

R M

C O

N T

R O

L P

A N

E L

(A -E

-1

NOT TO SCALE

NOTES:

1. CONTRACTOR SHALL PROVIDE FIRE ALARM SHOP DRAWINGS IN

ACCORDANCE WITH THE 2015 IBC SECTION 907.1.2. THE SHOP

DRAWINGS SHALL BE SIGNED & SEALED BY A LICENSED

PROFESSIONAL ENGINEER WHICH SHALL INCLUDE BUT NOT LIMITED TO

THE FOLLOWING:

a. FIRE ALARM PLAN

b. POINT TO POINT RISER DIAGRAM

c. BATTERY CALCULATIONS

d. VOLT DROP CALCULATIONS

e. FIRE ALARM WIRE TYPES

f. CUT SHEETS OF PANEL & ALL DEVICES

2. THIS DIAGRAM IS FOR BASIC CONCEPT ONLY. SYSTEM SHALL BE

WIRED IN ACCORDANCE W/AN APPROVED SET OF WIRING DIAGRAMS

INCLUDED IN THE FIRE ALARM SHOP

DRAWINGS.

3. PROVIDE LINE ISOLATION MONITOR MODULES.

FIRE ALARM SYSTEM WIRING

FS

S S

SHUTOFF

RELAYDUCT SMOKE

DETECTOR

SHUTOFF

RELAYFIRE DOOR

SHUTTER MOTOR

(A-701)

FD DH

N

PROJECT

NORTH

GENERAL AREA

OF WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

C U s e rs

\b z h a n g .A

C E

L A

\O n e

D ri v e

A c e la A rc h it e c ts

E n g in e e rs P

.C \D o c u m e n ts \2

-U

S D

V A

-0 M

E P b z h a n g

Y D

J Q

.r v t

/1

/2

:4

:4

A

M

E103

ELECTRICAL TELECOM AND FIRE

ALARM PLANS

6/18/2021 DJW ACELA

EAST ORANGE VAMC 385 TREMONT AVE, EAST ORANGE, NJ

561-19-160UPGRADE PROSTHETIC LABFINAL BID DOCUMENTS

1/8" = 1'-0"1

TELECOMMUNICATION PLAN NEW WORK

1/8" = 1'-0"2

FIRE ALARM PLAN NEW WORK

PROVIDE 2-PORT SURFACE MOUNTED BOX WITH RJ45 JACKS ABOVE FINISHED CEILING FOR WIRELESS ACCESS POINTS (WAP). PROVIDE 15' OF ADDITIONAL CAT6A CABLING FOR FUTURE ADJUSTMENTS.

COORDINATE LOCATION OF WAPs WITH VA COR PRIOR TO INSTALLATION. REFER TO TECHNOLOGY DETAILS FOR ADDITIONAL INFORMATION. TYPICAL FOR ALL WAPs.

TELECOM OUTLET FOR TV SHALL BE MOUNTED AT THE SAME HEIGHT AS THE TV POWER RECEPTACLE.

TELECOMMUNICATION PLAN KEYED NEW WORK NOTES

1. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND

MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED

CASEWORK, EQUIPMENT, ETC. VERIFY ALL CHANGES PRIOR TO ROUGH-IN.

2. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, AND CONNECTION REQUIREMENTS (DATA OUTLETS, WIFI ACCESS POINTS, ANTENNA.) WITH EQUIPMENT

VENDOR PRIOR TO ROUGH-IN.

3. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V BRANCH CIRCUIT. MULTIWIRE

BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.

4. TELECOMMUNICATION EQUIPMENT SHALL CONNECT TO EXISTING IT ROOM. COORDINATE WITH VA OIT.

TELECOMMUNICATION PLAN GENERAL NEW WORK NOTES

CONNECT NEW FIRE ALARM EQUIPMENT TO THE EXISTING FIRE ALARM CONTROL PANEL.

THE CEILING MOUNTED SPEAKER SHALL INTERLOCK WITH EXISTING FIRE ALARM SYSTEM AND NOTIFICATION SYSTEM. EC SHALL COORDINATE WITH FIRE ALARM CONTRACTOR AND VA OIT FOR CONNECTION DETAILS.

INSTALL NEW DUCT SMOKE DETECTOR WITH SHUT OFF RELAY AND TEST SWITCH FOR NEW AIR HANDLER UNIT SUPPLY AIR DISCHARGE. COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT LOCATION.

THE FIRE SHUTTER SHALL INTERLOCK WITH FIRE ALARM SYSTEM VIA THE SMOKE DETECTOR. WHEN FIRE ALARM SYSTEM IS ACTIVATED, THE FIRE SHUTTER WOULD AUTOMATICALLY OPERATE. REFER TO

INSTALLATION MANUAL FOR DETAILS. (CORNELL COUNTER FIRE DOOR OR EQUIVALENT.)

REFER TO ELECTROMAGNETIC DOOR HOLDER DETAIL FOR WIRING DIAGRAM.

FIRE ALARM PLAN KEYED NEW WORK NOTES

1. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND

MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED

CASEWORK, EQUIPMENT, ETC. VERIFY ALL CHANGES PRIOR TO ROUGH-IN.

2. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, AND CONNECTION REQUIREMENTS (PULL STATIONS, SPEAKERS, DUCT SMOKE DETECTOR.) WITH EQUIPMENT

VENDOR PRIOR TO ROUGH-IN.

3. NEW SPEAKERS IN CORRIDOR SHALL BE CONNECTED TO THE EXISTING PAGING SYSTEM. CONTRACTOR

SHALL VERIFY THE QUANTITIES AND TYPE WITH COR PRIOR TO ROUGH-IN.

4. CONTRACTOR SHALL PROVIDE WIRED SMOKE DETECTORS IN THE CONSTRUCTION AREA DURING

CONSTRUCTION UNTIL NEW SPRINKLER SYSTEM IS FUNCTIONAL. COORDINATE WITH SPRINKLER

CONTRACTOR FOR DETAILS.

5. ALL FIRE ALARM WORK SHALL BE SUPERVISED BY THE FACILITY'S EXISTING FIRE ALARM MAINTENANCE

CONTRACTOR. CONTACT 'KINETIX' @877-223-3000.

FIRE ALARM PLAN GENERAL NEW WORK NOTES

Revisions: Date:

KEY PLAN

(E) SUBSTATION AE

3200A

600A

(E)

PANEL

DP-B

BKR-19

(E)

PANEL

P2A

(E) SUBSTATION AN

3200A

300A

(E)

PANEL

LCP2

BKR-12

(E)

PANEL

LPA2

400ABKR-7

(N)

PANEL

A

(N)

PANEL

B

3200A

(E)800KW GENERATOR

G

FROM MAIN SWITCHGEAR

FROM MAIN SWITCHGEAR

225A (A-E-106)

SEE NOTE #1

PROPOSED SINGLE-LINE DIRAGRAM

NTS

3200A

208/120V 208/120V

NEW HUMIDIFIER

IN MECHANICAL ROOM

A-716

125A/3P/240V

NEMA 1

FUSED DISC

FUSED AT

125A

(A-E-102)

(4) #3/0 & (1) #6 GRD IN 2"C

(4) #1 & (1) #6 GRD IN 2"C

NORMAL POWER IN

MECHANICAL ROOM A-716

NORMAL POWER IN

ELECTRICAL A-E-102

CRITICAL/LIFE SAFETY POWER

IN ELEC. A-E-102D

NOTE:

1. REFER TO ARCHITECTURAL DRAWING GI201 FOR ELECTRICAL CLOSET A-E-106 LOCATION. EC SHALL

VERIFY THE LOCATION OF THE EXISTING ENCLOSED CIRCUIT BREAKER AND THE LENGTH OF THE

FEEDERS TO PANEL A AND B. THE ELECTRICAL WORK SHALL BE ONLY AT NIGHT TIME.

PROJECT: 20-USDVA-04

RATING: 208/120V, 4W, 3PH, 200A

CKT. CIRCUIT

DESCRIPTION

13 EXISTING SHOE MACHINE (EQ S2)

NEW FLOOR RECEPT

SEWING MACHINE (EQ SM)

(EQ B2)

SPACE

SPACE

SPACE

PANEL TYPE: NEMA 1

MOUNTING: SURFACE

MAIN LUGS ONLY

INTERRUPTING RATING: 14KA SYM.

FED FROM: 225A DISCONNECT IN A-128D

NOTES

1. ALL BUSING TO BE COPPER

2. BOLT ON BREAKERS ONLY

3. CONTRACTOR IS RESPONSIBLE TO COORDINATE THE SHORT CIRCUIT RATING AT THE UTILITY TRANSFORMER SECONDARY'S PRIOR TO PURCHASING ANY EQUIPMENT.

4. ALL WIRE SIZES ARE BASED ON 75 DEGREE WIRE.

5. EXISTING CONDUCTORS AND FEEDERS TO REMAIN. CONTRACTOR SHALL PROVIDE NEW TO EXTEND EXISTING WIRES AND CONDUITS. NEW WIRES AND CONDUITS SHALL MATCH THE EXISTING.

6. CONTRACTOR SHALL VERIFY BRANCH CIRCUITS (WIRE SIZE AND PHASE) ON DEMOLISHED PANEL B AND RELOCATE TO NEW PANEL B IF IN USE.

OVEN (EQ OV)

SPARE

NEW CONDENSING UNIT

PANEL 'B'

(NEW)

POLE LOAD BKR.

KVA SIZE

6.7

6.7

6.7

1.2

1.2

1.4

1.4

1.4

BRANCH

CIRCUIT

7.4

4#4&1#8GRD IN 1-1/4"C

EXISTING

4#12&1#12GRD IN 3/4"C

1.0

3.0

1.8

1.7

0.0

0.0

0.0

TOTAL (PHASE):

TOTAL CONN.:

21.8 22.6 17.6

62.0 KVA

TOT. CONN. + SPARE: 68.2 KVA

DEMAND: 54.6 KVA

DEMAND: 151.7 AMPS

SPARE CAPACITY

DEMAND FACTOR

10 %

80 %

3.0

3.0

3.0

3.0

3.2

2.7

2.7

1.3

2#12&1#12GRD IN 3/4"C 20

EXISTING 20

EXISTING 20

7.4

7.4

EXISTING 20

A

4.7

4.7

1.0

B C BRANCH

CIRCUIT

EXISTING

EXISTING

2#12&1#12GRD IN 3/4"C

BKR. LOAD POLE

SIZE KVA

0.7

0.7

1.0

0.7

0.7

0.7

1.8

1.8

1.8

1.3

1.3

1.3

1.0

LOCATION: MECHANICAL ROOM

CIRCUIT

DESCRIPTION

EXISTING DISC SANDER (EQ S1)

EXISTING ROLL SANDER (EQ S2) 4

MICROWAVE

EXISTING

DRILL PRESS (EQ DP)

AIR COMPRESSOR (EQ C)

DUST COLLECTOR (EQ DC)

WORKSTATION

SPACE

SPACE

SPACE

(RELOCATED FROM B-32,34,36) 12

EXISTING 14

(RELOCATED FROM B-32,34,36) 18

EXISTING

(RELOCATED FROM B-38,40,42) 24

FLOOR DUPLEX RECEPT

CKT.

PROJECT: 20-USDVA-04

RATING: 208/120V, 4W, 3PH, 200A

CKT. CIRCUIT

DESCRIPTION

RETURN FAN RF-1 - NOTE 5

BASEBOARD HEAT A-103C&K

BASEBOARD HEAT

VAV BOXES -NOTE 5

ACTUATORS - NOTE 5

EF-2, EF-3 - NOTE 5

SPARE

SPARE

SPACE

SPACE

SPACE

PANEL TYPE: NEMA 1

MOUNTING: SURFACE

MAIN CIRCUIT BREAKER: 225A

INTERRUPTING RATING: 14KA SYM.

FED FROM: 225A DISCONNECT IN A-128D

NOTES

1. ALL BUSING TO BE COPPER

2. BOLT ON BREAKERS ONLY

3. CONTRACTOR IS RESPONSIBLE TO COORDINATE THE SHORT CIRCUIT RATING AT THE UTILITY TRANSFORMER SECONDARY'S PRIOR TO PURCHASING ANY EQUIPMENT.

4. ALL WIRE SIZES ARE BASED ON 75 DEGREE WIRE.

5. REUSE EXISTING CIRCUIT BREAKER.

6. REPLACE WITH NEW CIRCUIT BREAKER. NEW CIRCUIT BREAKER SHALL MATCH WITH EXISTING IN SO AS MANUFACTURER, TYPE AND AIC RATING.

7. CONTRACTOR SHALL VERIFY BRANCH CIRCUITS ON DEMOLISHED PANEL A AND RELOCATE TO NEW PANEL A IF IN USE.

PANEL 'A'

(NEW)

POLE LOAD BKR.

KVA SIZE

1.3

1.3

1.3

1.2

1.2

1.2

1.2

0.5

0.5

1.5

0.0

0.0

0.0

TOTAL (PHASE):

TOTAL CONN.:

0.0

10.2 9.3 7.3

26.8 KVA

TOT. CONN. + SPARE: 29.5 KVA

DEMAND: 23.6 KVA

DEMAND: 65.5 AMPS

SPARE CAPACITY

DEMAND FACTOR

10 %

80 %

BRANCH

CIRCUIT

4#12&1#12GRD IN 3/4"C

EXISTING

EXISTING

2.2

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

1.5

1.6 2.3

2.1

0.0

2#12&1#12GRD IN 3/4"C

2.2

2.2

2.2

EXISTING

A

3.5

3.5

3.5

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

4#8&1#10GRD IN 1"C

B C BRANCH

CIRCUIT

BKR. LOAD POLE

SIZE KVA

2.2

2.2

2.2

1.0

1.0

1.0

1.0

1.0

1.1

LOCATION: MECHANICAL ROOM

CIRCUIT

DESCRIPTION

AIR HANDLING UNIT - NOTE 6

LIGHTING - NOTE 6

LIGHTING - NOTE 6

EXISTING

SPARE

SPARE

SPACE

SPACE

SPACE

(RELOCATED FROM A-16,18,20) 16

MECHANICAL ROOM REC 18

CKT.

PROJECT: 20-USDVA-04

RATING: 208/120V, 4W, 3PH, 100A

CKT. CIRCUIT

DESCRIPTION

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

27 WAITING/RECEP RECS - NOTE 5

EXAM RECS - NOTE 5

CORRIDOR RECS - NOTE 5

WAITING ROOM TV - NOTE 5

SPACE

PANEL TYPE: NEMA 1

MOUNTING: SURFACE

MAIN LUGS ONLY

INTERRUPTING RATING: 14KA SYM.

FED FROM: 300A DISCONNECT ON PANEL LCP2

NOTES

1. ALL BUSING TO BE COPPER

2. BOLT ON BREAKERS ONLY

3. CONTRACTOR IS RESPONSIBLE TO COORDINATE THE SHORT CIRCUIT RATING AT THE UTILITY TRANSFORMER SECONDARY'S PRIOR TO PURCHASING ANY EQUIPMENT.

4. ALL WIRE SIZES ARE BASED ON 75 DEGREE WIRE.

5. REUSE EXISTING CIRCUIT BREAKER.

PANEL 'LPA2'

(EXISTING)

POLE LOAD BKR.

KVA SIZE

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.1

1.1

1.1

BRANCH

CIRCUIT

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

A

2.0

2.0

2.0

2.0

2.0

1.7

1.9

1.7

2.1

2.0

2.0

2.1

2.0

1.7

2.1

2.1

2.0

TOTAL (PHASE):

TOTAL CONN.:

12.0 11.8 0.0 10.0

33.8 KVA

TOT. CONN. + SPARE: 37.2 KVA

DEMAND: 29.7 KVA

DEMAND: 82.7 AMPS

SPARE CAPACITY

DEMAND FACTOR

10 %

80 %

EXISTING 20

EXISTING 30

EXISTING

B C BRANCH

CIRCUIT

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

EXISTING

EXISTING

BKR. LOAD POLE

SIZE KVA

1.0

1.0

1.0

1.0

1.0

0.7

0.9

1.1

1.0

1.0

1.0

1.0

1.0

1.0

1.0

LOCATION: A-E-102

CIRCUIT

DESCRIPTION

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

RECS FOR OFFICES - NOTE 5

EXISTING

EXISTING

W/C REPAIR RECS - NOTE 5

EXISTING

EXISTING

EXISTING

SPACE

CKT.

PROJECT: 20-USDVA-04

RATING: 208/120V, 4W, 3PH, 125A

CKT. CIRCUIT

DESCRIPTION

A/C 171

RECEPTION RECS - NOTE 5

EXAM ROOM - NOTE 5

EXAM ROOM - NOTE 5

FUME FAN

PANEL 'P2A'

(EXISTING)

9 MECH/EXAM/WAITING LTG -NOTE 5 1

DOOR HOLDER - NOTE 6

DEMO TO SPARE

PANEL TYPE: NEMA 1

MOUNTING: SURFACE

MAIN LUGS ONLY

INTERRUPTING RATING: 14KA SYM.

FED FROM: 125A DISCONNECT ON PANEL DP-B

NOTES

1. ALL BUSING TO BE COPPER

2. BOLT ON BREAKERS ONLY

3. CONTRACTOR IS RESPONSIBLE TO COORDINATE THE SHORT CIRCUIT RATING AT THE UTILITY TRANSFORMER SECONDARY'S PRIOR TO PURCHASING ANY EQUIPMENT.

4. ALL WIRE SIZES ARE BASED ON 75 DEGREE WIRE.

5 . REUSE EXISTING CIRCUIT BREAKER.

POLE LOAD BKR.

KVA SIZE

1.5

1.0

1.0

1.0

1.0

1.5

0.0

TOTAL (PHASE):

TOTAL CONN.:

7.3

1.0

6.5

0.0

4.5

18.3 KVA

TOT. CONN. + SPARE: 22.0 KVA

DEMAND: 17.6 KVA

DEMAND: 48.8 AMPS

SPARE CAPACITY

DEMAND FACTOR

EXISTING 20

20 %

80 %

1.0 1

EXISTING

SPACE

BRANCH

CIRCUIT

EXISTING

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

EXISTING

A

2.5

2.0

2.0

2.0

2.0

2.5

2.8

1.5

0.0 20

EXISTING 20

B C BRANCH

CIRCUIT

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

BKR. LOAD POLE

SIZE KVA

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

LOCATION: A-E-102D

CIRCUIT

DESCRIPTION

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

SPARE

CKT.

NEW BAND SAW

2.0

3 25 4#10&1#10GRD IN 3/4"C2.0

2.0

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

0.8

0.6

CONDENSATE PUMP SCP-1

CONDENSATE PUMP CP-2

WORKSTATION

WORKSTATION

1.0

1.0

1.0

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C

2#12&1#12GRD IN 3/4"C 0.7 STORAGE RM RECS - NOTE 5

1.12#12&1#12GRD IN 3/4"C 20

SPARE 1 20

2#12&1#12GRD IN 3/4"C

SPACE

1 20

LAB RECEPTACLES 1 20 2#12&1#12GRD IN 3/4"C1.1

FIRE SHUTTER - NOTE 5

W/C REPAIR RECS - NOTE 5

STORAGE RM RECS - NOTE 5

COPIER 1 20 2#12&1#12GRD IN 3/4"C0.7

20 OFFICE A-712 & BREAK AREA0.7 12#12&1#12GRD IN 3/4"C

20 REFRIGERATOR1.0 12#12&1#12GRD IN 3/4"C

1 20

3#6&1#10GRD IN 1"C

1.8 2#12&1#12GRD IN 3/4"C

4.0 4.0

SPARE 1 20

SPARE 1 20

33 1.0 2#12&1#12GRD IN 3/4"C

6. REPLACE WITH NEW CIRCUIT BREAKER. NEW CIRCUIT BREAKER SHALL MATCH WITH EXISTING IN SO AS MANUFACTURER, TYPE AND AIC RATING.

200.5 2#12&1#12GRD IN 3/4"C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

C U s e rs

\b z h a n g .A

C E

L A

\O n e

D ri v e

A c e la A rc h it e c ts

E n g in e e rs P

.C \D o c u m e n ts \2

-U

S D

V A

-0 M

E P b z h a n g

Y D

J Q

.r v t

/1

/2

:4

:4

A

M

E201

ELECTRICAL PANEL SCHEDULES

AND SINGLE LINE DIAGRAM

6/18/2021 DJW ACELA

EAST ORANGE VAMC 385 TREMONT AVE, EAST ORANGE, NJ

561-19-160UPGRADE PROSTHETIC LABFINAL BID DOCUMENTS

Revisions: Date: Page 41 of 43

Violet G

V1 H1 N

Dimming

Load

#1

G

H2 N

B la c k

/2

/3

V

A C

W h it e

N e u tr a l)

Gray

R e d

B lu e V io le t/ S tr ip e d

G ra y

White

W h it e

Dimming

Load

#2

V2

NXRC-2RD

BA

CAT5 Cable

OCC

PC

B u il d in g A u to m a ti o n

H U

B B

E L L

R

Red 24VDC

Yellow Black

18AWG standard low voltage wire

NXDS-U

Photo Sensor

(As required per Room)

S V

C

P W

R S

V C

P

IN

NXSW SERIES

(As required per Room)

(As required per Room)

OCC

PC

B u il d in g A u to m a ti o n

H U

B B

E L L

R

Red 24VDC

Blue

Black

18AWG standard low voltage wire

Low Voltage

Occupancy Sensor

(OMNI)

Low Voltage

Occupancy Sensor

(OMNI)

Low Voltage

Occupancy Sensor

(OMNI)

S V

C

P W

R S

V C

P

IN

S V

C

P W

R S

V C

P

IN

S V

C

P W

R S

V C

P

IN

Low Voltage Occupancy Sensor

(NX-OS-LODTR)

ROOM

CONTROLLER

2 OUTPUTS

WITH

DIMMING

Typical Mounting

HubNET Network

NX Bridge Module (Typical)

(As required) Junction Box

CAT5 Cable

To next bridge

From previous bridge

CAT5 Cable

CAT5 Cable

NXRC-2R

BA

CAT5 Cable

OCC

PC

B u il d in g A u to m a ti o n

H U

B B

E L L

R

Red 24VDC

Yellow Black

18AWG standard low voltage wire

NXDS-U

Photo Sensor

(As required per Room)

S V

C

P W

R S

V C

P

IN

NXSW SERIES

(As required per Room)

(As required per Room)

OCC

PC

B u il d in g A u to m a ti o n

H U

B B

E L L

R

Red 24VDC

Blue

Black

18AWG standard low voltage wire

Low Voltage

Occupancy Sensor

(OMNI)

Low Voltage

Occupancy Sensor

(OMNI)

Low Voltage

Occupancy Sensor

(OMNI)

S V

C

P W

R S

V C

P

IN

S V

C

P W

R S

V C

P

IN

S V

C

P W

R S

V C

P

IN

Low Voltage Occupancy Sensor

(NX-OS-LODTR)

ROOM

CONTROLLER

2 OUTPUT

ON/OFF

H1 N

Load #1

H2 N

B la c k

/2

/3

V

A C

W h it e

N e u tr a l)

R e d

B lu e

White

W h it e

Load #2

Typical Mounting

HubNET Network

NX Bridge Module (Typical)

(As required) Junction Box

CAT5 Cable

To next bridge

From previous bridge

CAT5 Cable

CAT5 Cable

LUMINAIRE MOUNTING - LAY-IN CEILING

NTS

LUMINAIRE

SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION

26 51 00

3 TWIST

MINIMUM

(TYP)

FIXTURE WHIP FROM

JUNCTION BOX

(1829mm (6') LONG

MAX.)

LUMINAIRE.

REFER TO

SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING

HARDWARE

REFER TO SPECIFICATION SECTION 26

51 00

ACOUSTICAL CEILING

TILE

(TYP)

ARCHITECTURAL

CEILING GRID

LUMINAIRE.

REFER TO

SCHEDULE

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND USING

THE RECOMMENDED MOUNTING HARDWARE.

WALL

PHONE

6"

WALL

JOIST

8'-0"

18"

4'-0"

LIGHT

SWITCHES

3"

TSTAT/SENSOR

OR

ANNUNCIATOR

EXIT

RECEPTACLE

6'-6" TO

TOP OF

MCB

ELEC.

PANEL

1'-0"

FLOOR

CEILING

DETAIL NOTES :

1. COORDINATE ALL LOCATIONS OF ELECTRICAL EQUIPMENT WITH ARCHITECTURAL

DRAWINGS.

2. USE THESE DEVICE MOUNTING HEIGHTS UNLESS OTHERWISE INDICATED ON ARCHITECTURAL

DRAWINGS.

3. DEVICE HEIGHTS SHOWN FOR INFORMATIONAL PURPOSES ONLY. HEIGHTS APPLY FOR INSTALLED DEVICES AND

EQUIPMENT.

RECEPTACLE(S)

VOICE/DATA JACKS

AND JBOXES CENTER

BETWEEN JOISTS

44" MAX

STANDARD MOUNTING HEIGHTS

NTS

TYPICAL DUAL OUTPUT DIMMING ROOM CONTROLLER DETAIL

NTS

TYPICAL DUAL OUTPUT ON/OFF ROOM CONTROLLER DETAIL

NTS

CEILING

FLOOR

SIDE

WALL

4"

4"

NOTE:

MEASUREMENTS ARE

SHOWN TO THE

CLOSEST EDGE OF

THE DETECTOR

HEAT DETECTORS

NEVER IN SHADED

AREA

WALL MOUNTED

SMOKE/HEAT

DETECTOR

CEILING MOUNTED

SMOKE/HEAT

DETECTOR

12"

MAX

3'

MIN

HVAC SUPPLY OR

RETURN DIFFUSER

MAGNETIC DOOR

HOLDER

FIRE

PULL

TO EXIT DOOR

5' MAX

MANUAL PULL

STATION

48" MAX

MEASUREMENT

SHOWN TO TOP

OF PULL HANDLE

NFPA 72 AUDIBLE APPLIANCE,

6" MIN BELOW FINISHED CEILING

/ 90" MIN AFF. (OTHER

MOUNTING HEIGHTS SHALL BE

PERMITTED BY THE AHJ

PROVIDING IT MEETS THE SOUND

LEVEL OUTPUT REQUIRED.

AUDIBLE

ONLY

FOR CEILING HEIGHTSLESS THAN 86". THE

VISUAL LENS MOUNTINGHEIGHT SHALL BE

WITHIN 6" OF THE CEILING

AUDIBLE/VISUAL & VISUAL

ONLY APPLIANCES

SYNCHRONIZE MORE THAN

TWO APPLIANCES IN ANY

FIELD OF VIEW

REF. 80" MIN (IBC)

REF. 96" MAX (IBC)

ABOVE FINISHED

FLOOR

NOTE:

REFER TO THE PROPER

DEVICES INSTALLATION

INSTRUCTIONS FOR

BACKBOX MOUNTING

HEIGHT

96" MAX

(NFPA ADA)

ABOVE

FINISHED FLOOR

TO TOP OF LENS

FIRE ALARM STANDARD MOUNTING DETAIL

NTS

DOOR WIDTH LESS THAN 3"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

C U s e rs

\b z h a n g .A

C E

L A

\O n e

D ri v e

A c e la A rc h it e c ts

E n g in e e rs P

.C \D o c u m e n ts \2

-U

S D

V A

-0 M

E P b z h a n g

Y D

J Q

.r v t

/1

/2

:4

:4

A

M

E301

ELECTRICAL DETAILS

6/18/2021 DJW ACELA

EAST ORANGE VAMC 385 TREMONT AVE, EAST ORANGE, NJ

Revisions: Date: Page 42 of 43

208V 3PH 30A

EP6 7-9-11

PANEL

DESIGNATION

SPECIAL PURPOSE

POWER RECEPTACLE

AS REQUIRED. PRIOR

TO WORK, CONFIRM

FINAL RECEPTACLE

REQUIREMENTS WITH

OWNER'S END USER

120 VAC POWER

RECEPTACLE

AS REQUIRED.

SEE NOTE 1.

VOLTAGE PHASE

EP6 16

CIRCUIT

NUMBER(S)

3/16" HEIGHT

LETTERING (TYP)

PANEL

DESIGNATION

CIRCUIT

NUMBER(S)

AMPACITY

DEVICE COVER

PLATE AS

REQUIRED

DEVICE COVER

PLATE AS

REQUIRED

CONTROL DEVICE

(SWITCH,DIMMER,ETC.)

AS REQUIRED.

DEVICE COVER

PLATE AS

REQUIRED

DETAIL NOTES :

1. ALL WIRING DEVICES SHALL BE FLUSH-MOUNTED (IN ALL FINISHED

SPACES) IN THE VERTICAL POSITION (WHERE POSSIBLE) IN A

CODE COMPLIANT ROUGH-IN BOX AS REQUIRED. EXAMPLES

SHOWN ABOVE SHALL APPLY TO ALL WIRING DEVICE PROVISIONS.

2. ALL VERTICALLY-MOUNTED STANDARD 120V SINGLE AND DUPLEX

POWER RECEPTACLES SHALL BE INSTALLED "GROUND DOWN".

3. PROVIDE A DETAILED PRODUCT SHOP DRAWING SUBMITTAL

(INCLUDING FINISH OPTIONS FOR ALL COMPONENTS) FOR

REVIEW/SELECTION BY THE ENGINEER AND ARCHITECT.

DAT 7-9-11

TEL 7-9-11

COORDINATED

DESIGNATION LABEL

COORDINATED

DESIGNATION LABEL

DEVICE COVER

PLATE AS

REQUIRED

TELE/DATA JACK

AS REQUIRED. CONFIRM

FINAL JACK REQUIREMENTS

AND CONFIGURATION WITH

OWNER'S END USER. BASE

ACCORDINGLY

TYPICAL FLUSH-MOUNTED WIRING DEVICES

NTS

TYPICAL WALL VACANCY SWITCH DETAIL

NTS

BUTTON 1

(TEST BUTTON)

COVER RELEASE

CATCH

PHOTOCELL

PUSH BUTTON

LINE

CIRCUIT

BLACK

LOAD

RED

GROUND

CONNECTION

BUTTON A

(TEST BUTTON)

COVER RELEASE

CATCH

PHOTOCELL

PUSH BUTTON

LINE

CIRCUIT

BLACK

LOAD 1

RED

GROUND

CONNECTION

LOAD 2

BLUE

BUTTON B

NEUTRAL

WHITE

BUTTON A

(RAISE BUTTON)

BUTTON B

(ON/OFF BUTTON)

BUTTON C

(LOWER BUTTON)

COVER RELEASE

CATCH

PHOTOCELL

PUSH BUTTON

NEUTRAL

WHITE

LINE

CIRCUIT

BLACK

DIMMING

FIXTURE

RED

VIOLET

GRAY

GROUND

CONNECTION

TYPICAL WALL DIMMING VACANCY SWITCH DETAIL

NTS

ELECTROMAGNETIC DOOR HOLDER WIRING DETAIL

NTS

24-60 optimal

Operation Narrative

Doors are to be normally held open. the electromagnetic door releases will be energized with the voltage shown

(at right) in the hardware set for this opening. Power shall be controlled by the fire control system. it will interrupt the power if alarmed, causing the doors to be released, thus allowing the door closers to close the doors. When power is restored the magnets will re-energize, permitting the doors to be manually returned to their held open position.

Fire Alarm Panel 24VAC Output

COM

24 VAC/DC

120 VAC

12 VDC

COM

24 VAC/DC

120 VAC

12 VDC

COM

24 VAC/DC

120 VAC

12 VDC

Fire Alarm Panel 24VDC Output

Fire Alarm Panel 12VDC Output

Fire Alarm Panel

120VAC

Output

COM

HOT

GND

COM

24 VAC/DC

120 VAC

12 VDC

Ground to Screw on Mounting Bracket

Electrical Specifications:

12VDC @ .O40 AMPS

24VAC/DC @ .020

AMPS

120VAC @ .020 AMPS

(or see specific model)

NOTE: All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction. Proper wire gauge should be used.

24 VAC WIRING

24 VDC WIRING

12 VDC WIRING

Electromagnetic Door Release

Power Supply/ Junction BoxB

A

C

C

B

Local Detector

To Fire Control System Power

120 VAC WIRING

A A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

C U s e rs

\b z h a n g .A

C E

L A

\O n e

D ri v e

A c e la A rc h it e c ts

E n g in e e rs P

.C \D o c u m e n ts \2

-U

S D

V A

-0 M

E P b z h a n g

Y D

J Q

.r v t

/1

/2

:4

:4

A

M

E302

ELECTRICAL DETAILS

6/18/2021 DJW ACELA

EAST ORANGE VAMC 385 TREMONT AVE, EAST ORANGE, NJ

Revisions: Date: Page 43 of 43