S02 DWG 2021-503 Emergency Power B118.pdf

PDF 955 KB Posted

Attached to
Z1DA--528A5-21-503 PROVIDE EMERGENCY POWER TO BUILDING 118
Solicitation number
36C24221B0031
Issued by

View the file

Other files

File Type Posted
E. 4160V TapBox.jpg JPG image
F. 4160V TapBox.jpg JPG image
D. 4160V TapBox.jpg JPG image
C. 4160V TapBox.jpg JPG image
B. 4160V TapBox.jpg JPG image
36C24221B0031 0001.docx DOCX document
A. 4160V TapBox.jpg JPG image
S02 Specs - 528A5 21-503 Provide Emergency Power to Building 118.pdf PDF
36C24221B0031_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DISCIPLINE/

SHEET NO. DESCRIPTION

G001 COVER SHEET, DRAWING INDEX AND NOTES

EP101 B118 FLOOR PLAN

EP102 B118 ROOM 9

E601 ELECTRICAL SINGLE LINE, DEMOLITION AND NEW WORK

E602 DETAILS

ELECTRICAL GENERAL NOTES

1. THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL

CONTRACT DRAWINGS.

2. THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR" THE CONTRACTOR IS

RESPONSIBLE FOR THAT WORK.

3. DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK. BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND RELATED SPECIFICATION SECTIONS FOR THE PROPER

INSTALLATION OF ALL WORK.

4. DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED SPECIFICATION SECTIONS

FOR ADDITIONAL REQUIREMENTS.

5. PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.

6. ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT THE USE OF

SPECIALIZED TOOLS.

7. FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.

8. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED), AND ALL OTHER APPLICABLE

CODES AND STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.

9. THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED

ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.

10. ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S

RECOMMENDATIONS.

11. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED

TESTING LABORATORY.

12. THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.

13. THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL EXISTING OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNERS REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR SHALL PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.

14. THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR

INSTALLATIONS.

15. THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO

PERFORMING ANY WORK.

16. ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING

AND/OR BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.

17. THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORK PERFORMED SHALL BE IN

ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL UTILITY COMPANIES.

18. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH

THE OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.

19. THE LOCATIONS OF EXISTING UTILITIES, STRUCTURE AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING ANY WORK.

20. ARC FLASH LABELS SHALL BE PROVIDED TO ALL NEW EQUIPMENT BASED ON THE OUTCOME OF THE CONTRACTORS ARC FLASH STUDY. ANY EQUIPMENT MODIFIED AS PART OF THIS PROJECT SHALL ALSO BE INCLUDED IN THE ARC FLASH STUDY, AND RE LABELLED AS REQUIRED.

21. ALL SHUT DOWNS TO BE SCHEDULED FOR SATURDAYS OR AS APPROVED BY COR.

22. ALL PENETRATIONS SHALL BE SEALED WITH FIRE CAULKED IN FIRE/SMOKE BARRIERS.

23. CONTRACTOR SHALL INSTALL CODE COMPLIANT WIRE AND CONDUIT SIZE PER NEC, LATEST EDITION.

DRAWING INDEX

DEPARTMENT OF VETERANS AFFAIRS

SCALE: NONE

SITE PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date:

NOTE:

USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING

EXISTING DIMENSIONS AND CONDITIONS IN THE FIELD

o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

Canandaigua VAMC

SCALE: NONE

SITE LOCATION

EAST STREET

FORT HILL

AVENUE

PARKING

PARKING

PARKING

WATER TOWER

C H

AP

EL

S

TR

EE

T

EAST STREET

COURTYARD 2

COURTYARD 2

COURTYARD 2

COURTYARD 2

COURTYARD 1

2 HRVISITOR

33 3

RESERVED & VISITOR 2 HR TYP.

1 1A

OUTPATIENT

RAMP

UNDER

CONSTRUCTION

35T

BUSHWOOD LN.

RETENTION

POND

5CANANDAIGUA, NY

COVER SHEET, DRAWING

LEGEND AND NOTES

BID DOCUMENTS PROVIDE EMERGENCY

POWER TO BUILDING 118

528A5-21-503

G001

CANANDAIGUA VAMC

RTBECS11/20/2020

ERIC SMITH

N/AN/A

PROVIDE EMERGENCY

POWER TO BUILDING 118

PROJECT NUMBER 528A5-21-503

11A

22 23

5B 5C

14B

14C

14A

15A

12A

5A

1A

6A

ELECTRIC ROOM 9

7 6

CBX2

CBX3

CBX1

AREA OF WORK

LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

VA MEDICAL

CENTER

ENGINEERING

CANANDAIGUA /

BATH, NEW YORK

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

No. Revision: Date:

NOTE:

USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING EXISTING DIMENSIONS AND

CONDITIONS IN THE FIELD.

SCALE: (FOR REFERENCE ONLY)

BUILDING 118 FLOOR PLAN BID DOCUMENTS PROVIDE EMERGENCY

POWER TO BUILDING 118

528A5-21-503

EP101

CANANDAIGUA VAMC

RTBECS11/20/2020

ERIC SMITH

N/AN/A

SCALE:1 BUILDING 118 FLOOR PLAN

NTS

EXISTING MDP

EXISTING 4160V

EMERGENCY TAP BOX

NEW 400A

Automatic Transfer

Switch

NEW 150KVA

EMERGENCY

DISCONNECT

EXISTING

DATA CAGE

EXISTING

COMPRESSOR

NEW 150 KVA

TRANSFORMER

NEW 400A Enclosed Circuit Breaker

NEW 400A

ATS

NEW 150 KVA

TRANSFORMER

NEW 150KVA

EMERGENCY

DISCONNECT

NEW 400A ENCLOSED

CIRCUIT BREAKER

EXISTING MAIN

DISTRIBUTION

PANEL

4160V EMERGENCY 4160V EMERGENCY

V

EM

ER

G

EN

C

Y

8Y

/1

E M

ER

G

EN

C

Y

8Y

/1

N O

R M

AL

208Y/120 NORMAL

8Y

/1

N O

R M

AL

208Y/120 FEED

SWITCHBOARD

SIDE

LOAD

PROTECTED

SIDE

NEW 4" CONCRETE

HOUSEKEEPING PAD

NEW 4" CONCRETE

HOUSEKEEPING PAD

FROM EXISTING 4160V

EMERGENCY TAP BOX

1. HOUSEKEEPING PAD SHALL BE 4" HIGH WITH 12" CHAMFERED EDGES.

REFER TO DETAIL 3/E602

2. FINAL LOCATION OF ALL EQUIPMENT TO BE COORDINATED WITH COR

3. REFER TO DRAWING E601 FOR EQUIPMENT INFORMATION

4. ELECTRICAL FEEDS SHOWN FOR REFERENCE ONLY.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

VA MEDICAL

CENTER

ENGINEERING

CANANDAIGUA /

BATH, NEW YORK

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

No. Revision: Date:

NOTE:

USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING EXISTING DIMENSIONS AND

CONDITIONS IN THE FIELD.

SCALE: (FOR REFERENCE ONLY)

BUILDING 118 ROOM 9 BID DOCUMENTS PROVIDE EMERGENCY

POWER TO BUILDING 118

528A5-21-503

EP102

CANANDAIGUA VAMC

RTBECS11/20/2020

ERIC SMITH

N/AN/A

SCALE:1 ELECTRIC ROOM #9

1/2"=1'

ELECTRICAL NOTES

SCALE:2 SECTION

NTS

12'-4"

3'-3"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

VA MEDICAL

CENTER

ENGINEERING

CANANDAIGUA /

BATH, NEW YORK

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

No. Revision: Date:

NOTE:

USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING EXISTING DIMENSIONS AND

CONDITIONS IN THE FIELD.

SCALE: (FOR REFERENCE ONLY)

ELECTRICAL SINGLE LINE,

DEMOLITION AND NEW WORK

BID DOCUMENTS PROVIDE EMERGENCY

POWER TO BUILDING 118

528A5-21-503

E601

CANANDAIGUA VAMC

RTBECS11/20/2020

ERIC SMITH

N/AN/A

SCALE:

SHEET KEYNOTES:

1. 4160V TAP BOX: PROVIDE FEED TO NEW EMERGENCY DISCONNECT FROM TAP BOX.

PROVIDE LIGHT AT TAP BOX WHEN ON BUILDING EMERGENCY POWER. COORDINATE

EMERGENCY POWER SHUTDOWN WITH VAMC COR.

2. DISCONNECT - NEW WORK: PROVIDE NEW DISCONNECT. MOUNT ON STAND.

BOD: SQUARE D MINIBREAK HVMB305200

3. TRANSFORMER - NEW WORK: PROVIDE NEW PAD-MOUNTED DRY-TYPE TRANSFORMER.

REFER TO GROUNDING DETAIL 2/E602.

BOD: SQUARE D EX150T18H

4. ATS - NEW WORK: INSTALL NEW ATS MOUNTED ON STAND. CONNECT NORMAL POWER

TO LOAD PROTECTED SIDE OF MDP. CONNECT EMERGENCY POWER TO NEW

TRANSFORMER. CONNECT NEW FEED TO SWITCHBOARD.

BOD: ASCO 7000 SERIES, J07ATSB30400C5ZC,6DL,18B,31Z,125A,150AT

5. SERVICE DISCONNECT - NEW WORK: INSTALL NEW 400A SERVICE DISCONNECT

MOUNTED ON UNISTRUT FRAME.

6. EXISTING SWITCHBOARD MDP: ISOLATE LOAD PROTECTED SIDE OF MDP. PROVIDE

NEW 400A FEED TO NEW ATS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

VA MEDICAL

CENTER

ENGINEERING

CANANDAIGUA /

BATH, NEW YORK

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

No. Revision: Date:

NOTE:

USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING EXISTING DIMENSIONS AND

CONDITIONS IN THE FIELD.

SCALE: (FOR REFERENCE ONLY)

DETAILS BID DOCUMENTS PROVIDE EMERGENCY

POWER TO BUILDING 118

528A5-21-503

E602

CANANDAIGUA VAMC

RTBECS11/20/2020

ERIC SMITH

N/AN/A

NOTES:

1. A 1" MIN. THICKNESS OF 3M FIRE DAM 150 CAULK (OR APPROVED EQUAL) IS TO BE INSTALLED

AROUND THE CONDUIT ON BOTH SIDES OF THE WALL. AN ADDITIONAL 1/4" BEAD SHALL BE PLACED

AROUND THE PERIMETER OF THE OPENING OVERLAPPING THE WALL 1/4" MIN.

2. A 1-1/2" MIN. THICKNESS OF MINERAL WOOL DAMMING OR CERAMIC FIBER INSULATION IS REQUIRED IN THE PENETRATION AROUND THE CONDUIT & RECESSED 2" MIN. FROM EACH SIDE OF

THE WALL.

3. A 1" MIN. CLEARANCE IS REQUIRED BETWEEN ADJACENT CONDUIT & THE PERIMETER THROUGH

THE OPENING.

4. THESE RECOMMENDATIONS ARE BASED ON PRODUCT PERFORMANCE PER ASTM E-814 (UL 1479)

FIRE TEST & UL THROUGH-PENETRATION FIRE STOP SYSTEM #170.

3M FIRE BARRIER

CP 150 CAULK OR

APPROVED

EQUAL

FIRE RATED

CONCRETE BLOCK

WALL

3M FIRE BARRIER FS-195

(OR APPROVED EQUAL)

WRAP/STRIP, MINERAL

WOOL, OR CERAMIC

FIBER

CONDUIT

TRANSFORMER

ENCLOSURE

PRIMARY

WINDING

SECONDARY

WINDING

BOND TO

ENCLOSURE

GROUNDING

ELECTRODE

CONDUCTOR

TO MAIN BLDG

GROUND BAR

VIA BLDG

STEEL

FLEXIBLE CONDUIT

WITH GROUNDING

ELECTRODE

CONDUCTOR.

SCALE:1

PENETRATION FIRE STOP FOR CONDUIT

THROUGH BLOCK WALL

NTS SCALE:2 TYPICAL TRANSFORMER GROUNDING DETAIL

NTS

POWER OUTPOWER IN

SCALE:3 CONCRETE HOUSEKEEPING PAD

NTS

6 X 6 WOVEN

WIRE MESH

2" DOWELL 24" SPACING

INTO EXISTING

HOUSEKEEPING PAD

AND BUILDING SLAB

ALL EDGES

SHALL HAVE 12"

CHAMFER

File details come from the government source that posted it. Updated .