DISCIPLINE/
SHEET NO. DESCRIPTION
G001 COVER SHEET, DRAWING INDEX AND NOTES
EP101 B118 FLOOR PLAN
EP102 B118 ROOM 9
E601 ELECTRICAL SINGLE LINE, DEMOLITION AND NEW WORK
E602 DETAILS
ELECTRICAL GENERAL NOTES
1. THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL
CONTRACT DRAWINGS.
2. THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR" THE CONTRACTOR IS
RESPONSIBLE FOR THAT WORK.
3. DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK. BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND RELATED SPECIFICATION SECTIONS FOR THE PROPER
INSTALLATION OF ALL WORK.
4. DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED SPECIFICATION SECTIONS
FOR ADDITIONAL REQUIREMENTS.
5. PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.
6. ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT THE USE OF
SPECIALIZED TOOLS.
7. FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.
8. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED), AND ALL OTHER APPLICABLE
CODES AND STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
9. THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED
ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.
10. ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S
RECOMMENDATIONS.
11. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED
TESTING LABORATORY.
12. THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.
13. THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL EXISTING OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNERS REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR SHALL PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.
14. THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR
INSTALLATIONS.
15. THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO
PERFORMING ANY WORK.
16. ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING
AND/OR BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.
17. THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORK PERFORMED SHALL BE IN
ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL UTILITY COMPANIES.
18. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH
THE OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.
19. THE LOCATIONS OF EXISTING UTILITIES, STRUCTURE AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING ANY WORK.
20. ARC FLASH LABELS SHALL BE PROVIDED TO ALL NEW EQUIPMENT BASED ON THE OUTCOME OF THE CONTRACTORS ARC FLASH STUDY. ANY EQUIPMENT MODIFIED AS PART OF THIS PROJECT SHALL ALSO BE INCLUDED IN THE ARC FLASH STUDY, AND RE LABELLED AS REQUIRED.
21. ALL SHUT DOWNS TO BE SCHEDULED FOR SATURDAYS OR AS APPROVED BY COR.
22. ALL PENETRATIONS SHALL BE SEALED WITH FIRE CAULKED IN FIRE/SMOKE BARRIERS.
23. CONTRACTOR SHALL INSTALL CODE COMPLIANT WIRE AND CONDUIT SIZE PER NEC, LATEST EDITION.
DRAWING INDEX
DEPARTMENT OF VETERANS AFFAIRS
SCALE: NONE
SITE PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
NOTE:
USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING
EXISTING DIMENSIONS AND CONDITIONS IN THE FIELD
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
Canandaigua VAMC
SCALE: NONE
SITE LOCATION
EAST STREET
FORT HILL
AVENUE
PARKING
PARKING
PARKING
WATER TOWER
C H
AP
EL
S
TR
EE
T
EAST STREET
COURTYARD 2
COURTYARD 2
COURTYARD 2
COURTYARD 2
COURTYARD 1
2 HRVISITOR
33 3
RESERVED & VISITOR 2 HR TYP.
1 1A
OUTPATIENT
RAMP
UNDER
CONSTRUCTION
35T
BUSHWOOD LN.
RETENTION
POND
5CANANDAIGUA, NY
COVER SHEET, DRAWING
LEGEND AND NOTES
BID DOCUMENTS PROVIDE EMERGENCY
POWER TO BUILDING 118
528A5-21-503
G001
CANANDAIGUA VAMC
RTBECS11/20/2020
ERIC SMITH
N/AN/A
PROVIDE EMERGENCY
POWER TO BUILDING 118
PROJECT NUMBER 528A5-21-503
11A
22 23
5B 5C
14B
14C
14A
15A
12A
5A
1A
6A
ELECTRIC ROOM 9
7 6
CBX2
CBX3
CBX1
AREA OF WORK
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
VA MEDICAL
CENTER
ENGINEERING
CANANDAIGUA /
BATH, NEW YORK
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
No. Revision: Date:
NOTE:
USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING EXISTING DIMENSIONS AND
CONDITIONS IN THE FIELD.
SCALE: (FOR REFERENCE ONLY)
BUILDING 118 FLOOR PLAN BID DOCUMENTS PROVIDE EMERGENCY
POWER TO BUILDING 118
528A5-21-503
EP101
CANANDAIGUA VAMC
RTBECS11/20/2020
ERIC SMITH
N/AN/A
SCALE:1 BUILDING 118 FLOOR PLAN
NTS
EXISTING MDP
EXISTING 4160V
EMERGENCY TAP BOX
NEW 400A
Automatic Transfer
Switch
NEW 150KVA
EMERGENCY
DISCONNECT
EXISTING
DATA CAGE
EXISTING
COMPRESSOR
NEW 150 KVA
TRANSFORMER
NEW 400A Enclosed Circuit Breaker
NEW 400A
ATS
NEW 150 KVA
TRANSFORMER
NEW 150KVA
EMERGENCY
DISCONNECT
NEW 400A ENCLOSED
CIRCUIT BREAKER
EXISTING MAIN
DISTRIBUTION
PANEL
4160V EMERGENCY 4160V EMERGENCY
V
EM
ER
G
EN
C
Y
8Y
/1
E M
ER
G
EN
C
Y
8Y
/1
N O
R M
AL
208Y/120 NORMAL
8Y
/1
N O
R M
AL
208Y/120 FEED
SWITCHBOARD
SIDE
LOAD
PROTECTED
SIDE
NEW 4" CONCRETE
HOUSEKEEPING PAD
NEW 4" CONCRETE
HOUSEKEEPING PAD
FROM EXISTING 4160V
EMERGENCY TAP BOX
1. HOUSEKEEPING PAD SHALL BE 4" HIGH WITH 12" CHAMFERED EDGES.
REFER TO DETAIL 3/E602
2. FINAL LOCATION OF ALL EQUIPMENT TO BE COORDINATED WITH COR
3. REFER TO DRAWING E601 FOR EQUIPMENT INFORMATION
4. ELECTRICAL FEEDS SHOWN FOR REFERENCE ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
VA MEDICAL
CENTER
ENGINEERING
CANANDAIGUA /
BATH, NEW YORK
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
No. Revision: Date:
NOTE:
USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING EXISTING DIMENSIONS AND
CONDITIONS IN THE FIELD.
SCALE: (FOR REFERENCE ONLY)
BUILDING 118 ROOM 9 BID DOCUMENTS PROVIDE EMERGENCY
POWER TO BUILDING 118
528A5-21-503
EP102
CANANDAIGUA VAMC
RTBECS11/20/2020
ERIC SMITH
N/AN/A
SCALE:1 ELECTRIC ROOM #9
1/2"=1'
ELECTRICAL NOTES
SCALE:2 SECTION
NTS
12'-4"
3'-3"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
VA MEDICAL
CENTER
ENGINEERING
CANANDAIGUA /
BATH, NEW YORK
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
No. Revision: Date:
NOTE:
USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING EXISTING DIMENSIONS AND
CONDITIONS IN THE FIELD.
SCALE: (FOR REFERENCE ONLY)
ELECTRICAL SINGLE LINE,
DEMOLITION AND NEW WORK
BID DOCUMENTS PROVIDE EMERGENCY
POWER TO BUILDING 118
528A5-21-503
E601
CANANDAIGUA VAMC
RTBECS11/20/2020
ERIC SMITH
N/AN/A
SCALE:
SHEET KEYNOTES:
1. 4160V TAP BOX: PROVIDE FEED TO NEW EMERGENCY DISCONNECT FROM TAP BOX.
PROVIDE LIGHT AT TAP BOX WHEN ON BUILDING EMERGENCY POWER. COORDINATE
EMERGENCY POWER SHUTDOWN WITH VAMC COR.
2. DISCONNECT - NEW WORK: PROVIDE NEW DISCONNECT. MOUNT ON STAND.
BOD: SQUARE D MINIBREAK HVMB305200
3. TRANSFORMER - NEW WORK: PROVIDE NEW PAD-MOUNTED DRY-TYPE TRANSFORMER.
REFER TO GROUNDING DETAIL 2/E602.
BOD: SQUARE D EX150T18H
4. ATS - NEW WORK: INSTALL NEW ATS MOUNTED ON STAND. CONNECT NORMAL POWER
TO LOAD PROTECTED SIDE OF MDP. CONNECT EMERGENCY POWER TO NEW
TRANSFORMER. CONNECT NEW FEED TO SWITCHBOARD.
BOD: ASCO 7000 SERIES, J07ATSB30400C5ZC,6DL,18B,31Z,125A,150AT
5. SERVICE DISCONNECT - NEW WORK: INSTALL NEW 400A SERVICE DISCONNECT
MOUNTED ON UNISTRUT FRAME.
6. EXISTING SWITCHBOARD MDP: ISOLATE LOAD PROTECTED SIDE OF MDP. PROVIDE
NEW 400A FEED TO NEW ATS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
VA MEDICAL
CENTER
ENGINEERING
CANANDAIGUA /
BATH, NEW YORK
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
No. Revision: Date:
NOTE:
USERS OF THESE DRAWINGS ARE RESPONSIBLE FOR VERIFYING EXISTING DIMENSIONS AND
CONDITIONS IN THE FIELD.
SCALE: (FOR REFERENCE ONLY)
DETAILS BID DOCUMENTS PROVIDE EMERGENCY
POWER TO BUILDING 118
528A5-21-503
E602
CANANDAIGUA VAMC
RTBECS11/20/2020
ERIC SMITH
N/AN/A
NOTES:
1. A 1" MIN. THICKNESS OF 3M FIRE DAM 150 CAULK (OR APPROVED EQUAL) IS TO BE INSTALLED
AROUND THE CONDUIT ON BOTH SIDES OF THE WALL. AN ADDITIONAL 1/4" BEAD SHALL BE PLACED
AROUND THE PERIMETER OF THE OPENING OVERLAPPING THE WALL 1/4" MIN.
2. A 1-1/2" MIN. THICKNESS OF MINERAL WOOL DAMMING OR CERAMIC FIBER INSULATION IS REQUIRED IN THE PENETRATION AROUND THE CONDUIT & RECESSED 2" MIN. FROM EACH SIDE OF
THE WALL.
3. A 1" MIN. CLEARANCE IS REQUIRED BETWEEN ADJACENT CONDUIT & THE PERIMETER THROUGH
THE OPENING.
4. THESE RECOMMENDATIONS ARE BASED ON PRODUCT PERFORMANCE PER ASTM E-814 (UL 1479)
FIRE TEST & UL THROUGH-PENETRATION FIRE STOP SYSTEM #170.
3M FIRE BARRIER
CP 150 CAULK OR
APPROVED
EQUAL
FIRE RATED
CONCRETE BLOCK
WALL
3M FIRE BARRIER FS-195
(OR APPROVED EQUAL)
WRAP/STRIP, MINERAL
WOOL, OR CERAMIC
FIBER
CONDUIT
TRANSFORMER
ENCLOSURE
PRIMARY
WINDING
SECONDARY
WINDING
BOND TO
ENCLOSURE
GROUNDING
ELECTRODE
CONDUCTOR
TO MAIN BLDG
GROUND BAR
VIA BLDG
STEEL
FLEXIBLE CONDUIT
WITH GROUNDING
ELECTRODE
CONDUCTOR.
SCALE:1
PENETRATION FIRE STOP FOR CONDUIT
THROUGH BLOCK WALL
NTS SCALE:2 TYPICAL TRANSFORMER GROUNDING DETAIL
NTS
POWER OUTPOWER IN
SCALE:3 CONCRETE HOUSEKEEPING PAD
NTS
6 X 6 WOVEN
WIRE MESH
2" DOWELL 24" SPACING
INTO EXISTING
HOUSEKEEPING PAD
AND BUILDING SLAB
ALL EDGES
SHALL HAVE 12"
CHAMFER