RFI Form for 3rd and fourth floor d wing FA questions Signed.pdf
PDF 173 KB Posted
- Attached to
- Z1DA--528A7-19-708 SCI RENOVATION-THIRD AND FOURTH FLOOR D-WING Federal contract opportunity
- Solicitation number
- 36C24221B0016
About this file
This document contains a federal contract solicitation for renovation work at the Syracuse VA Medical Center. The solicitation is for renovating the third and fourth floors of Building 1, Wing D to create primary care spaces. It is a total SDVOSB set-aside requiring offerors to be verified in VetBiz and registered in SAM under NAICS code 236220. The site visit was scheduled for January 13, 2021 and questions are due by January 28, 2021 with bids to be emailed to the contracting officer. The award will be made to the responsive, responsible bidder submitting the lowest price. Work shall be performed at the Syracuse VA Medical Center located at 800 Irving Ave, Syracuse NY.
View the file
Other files for this federal contract opportunity
Show all 35
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
O’Connell Electric Company, Inc.
Industrial & Commercial Construction · Power Line & Substation · Communications
Transportation · Renewable Energy · Service & Maintenance · Technical Services
Corporate Headquarters 830 Phillips Road | Victor, NY 14564 | Phone 585.924.2176 | Fax 585.924.4973
Albany 2360 Maxon Road Ext | Schenectady, NY 12308 | Phone 518.346.0077 | Fax 518.346.0728 Rochester 390 Systems Road | Rochester, NY 14623 | Phone 585.424.3472 | Fax 585.424.3486
Buffalo 20 Lancaster Parkway | Lancaster, NY 14086 | Phone 716.675.9010 | Fax 716.686.0586 Rochester 400 Systems Road | Rochester, NY 14623 | Phone 585.869.4630 | Fax 585.272.0107
Syracuse Hancock Airpark 7001 Performance Drive |North Syracuse, NY 13212 |Phone 315.437.1453 | Fax 315.437.7431 www.oconnellelectric.com
Project:
Project
No.
Date:
To:
Number:
Spec.or Drawing
Reference
Attention:
Phone:
Email:
REQUEST:
Requested By:
Signed: Date:
ANSWER:
Answered By:
Signed: Date:
| Project: VA 3rd & 4th floor D wing renovations | |
| Project No: 528A7-19-708 | |
| Date: 1/22/2021 | |
| To: VA Hospital Syracuse NY | |
| Number: 3 | |
| To_2: | |
| Attention: Nicholas Winne | |
| Phone: 716-862-7461 EXT: 22438 | |
| Email: nicholas.winne@va.gov | |
| Specor Drawing Reference: 1-E-702, 7 Fire alarm riser | |
| REQUESTRow1: Where are fire alarm zone terminal cabinets located on EP-101 and EP- 102? | |
| undefined: Tyler Bulluck | |
| undefined_2: 1/22/2021 | |
| ANSWER: The Main Panels are located in Stairwell 3 of Building 1 as follows. 3rd floor D-Wing is Zone 38, and is connected to Panel 14 on 1st floor Stairwell 3, 4th floor D-Wing is Zone 46, and is connected to Panel 12 on 5th floor Stairwell. The Fire alarm devices are wired either in Parallel or in series circuits. With that said existing lines can be used to insert new devices as the start and finish(No T-taps). This is a loop system, and integrity of system must be keep. Therefore home runs back to the main controller should not be needed. | |
| undefined_3: | |
| undefined_4: | |
| 2021-01-26T07:31:37-0500 | |
| PAUL KERESTEDJIAN 1699249 |