RFI Form Electrical Data Jacks Welch Signed.pdf
PDF 140 KB Posted
- Attached to
- Z1DA--528A7-19-708 SCI RENOVATION-THIRD AND FOURTH FLOOR D-WING Federal contract opportunity
- Solicitation number
- 36C24221B0016
About this file
This document contains a request for information (RFI) regarding electrical data jacks and a related federal contract opportunity to renovate the third and fourth floors of the D wing at the Syracuse VA Medical Center.
The RFI clarifies that the electrical contractor is responsible for running cable and terminating phone and data jacks on both ends of the connection for the renovation project. The federal contract opportunity is a total service-disabled veteran-owned small business set-aside to renovate the specified floors. Offerors must be verified as SDVOSBs and registered in SAM and VetBiz at the time of offer and award. The NAICS code is 236220 for construction of commercial and institutional buildings with a size standard of $39.5 million. Questions are due by January 28th and bids should be emailed to the contracting officer by the response date.
View the file
Other files for this federal contract opportunity
Show all 35
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project:
Project
No.
Date:
To: Number:
Spec.or Drawing
Reference Attention:
Phone:
Email:
REQUEST:
Requested By:
Signed: Date:
ANSWER:
Answered By:
Signed: Date:
| Project: VA 3rd & 4th floor D wing renovations |
| Project No: 528A7-19-708 |
| Date: 1/22/2021 |
| To: VA Hospital Syracuse NY |
| Number: 1 |
| To_2: |
| Attention: Nicholas Winne |
| Phone: 716-862-7461 EXT: 22438 |
| Email: nicholas.winne@va.gov |
| Specor Drawing Reference: 1-E-702, Detail 5 |
| REQUESTRow1: A question from our electricians that has come up about the D-wing project: |
On detail 1-E-702/5, the data drop detail shows a stub into the hallway. Can it be confirmed that the EC is responsible for just the rough-in to the hallway and that cabling, IT jacks will be by others?
| undefined: Paul Kerestedjian on Behalf of Matthew Welch | |
| undefined_2: 1/26/2021 | |
| ANSWER: Electricians are responsible to do Ruff in, as well as cabling, Phone and Data Jacks terminations on both ends. A Complete job is required Point A to B. | |